Requirements at a glance
| Agency | Wyoming Department of Fire Prevention and Electrical Safety (State Fire Marshal); exam by ICC through Pearson VUE |
|---|---|
| Exam | 30 questions, 1 hour 30 minutes, 70% to pass |
| Experience | 4,000 hours over at least 2 years. |
| Books allowed | NEC or NEC Handbook (2023 per ICC's August 2025 bulletin), Ugly's (any edition), Ferm's Fast Finder, Tom Henry's Key Word Index |
| Fees | $115 per exam to Pearson VUE; the license is $100 for 3 years. |
Technicians applying to the Wyoming State Fire Marshal for a low-voltage alarm technician license. You need 4,000 hours of experience over at least 2 years.
Official links
- Wyoming State Fire Marshal: electrical licensing (opens in a new tab)
- Apply and pay for your license (Wyoming electrical licensing portal) (opens in a new tab)
- Register with ICC at Pearson VUE (opens in a new tab)
- ICC Wyoming Electrical Contractor/Trades Bulletin (PDF) (opens in a new tab)
- 041-5 Wyo. Code R. § 3 (examinations and passing scores) (opens in a new tab)
How to get licensed, step by step
Check your experience
Make sure you meet the State Fire Marshal's requirements for the low-voltage alarm technician license: 4,000 hours over at least 2 years.
Wyoming State Fire Marshal: electrical licensing (opens in a new tab)
Apply and get approved
Apply through the Wyoming electrical licensing portal. Wait for your approval notice, then allow 24 to 48 hours before you schedule so ICC can process your record.
Apply and pay for your license (Wyoming electrical licensing portal) (opens in a new tab)ICC Wyoming Electrical Contractor/Trades Bulletin (PDF) (opens in a new tab)
Register and pay with Pearson VUE
Create a Pearson VUE account for ICC, pick the Wyoming exam, pay $115 and book a seat at a test center.
Pass the exam
Bring your tabbed references. Your result shows right after the exam. If you fail, you must wait 10 days before you retest, and each attempt costs a new fee.
Register with ICC at Pearson VUE (opens in a new tab)041-5 Wyo. Code R. § 3 (examinations and passing scores) (opens in a new tab)
How to prepare
- ICC's August 2025 bulletin still lists the 2023 NEC, but Wyoming has adopted the 2026 NEC. Check ICC's exam catalog for your exam before you buy a book.
- Tab your books before exam day. There's no time to look up every answer, so know where Articles 90, 100, 110, 210 to 250, 300 to 392, 430 and Chapter 9 sit.
- The six areas are 5 questions each. Half the exam is remote-control and signaling circuits (Articles 722, 724 and 725: Class 1, 2 and 3) and half is fire alarm (Article 760).
- Tab the Article 760 parts for non-power-limited and power-limited fire alarm circuits and the cable substitution table.
- Start with the free questions above to find your weak topics, then drill those first.
- Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
- Read every explanation, including for questions you got right, and look the section up in your own book.
Books for this exam
This is an open-book exam: you can bring the references below, and most questions come from the NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.
NFPA 70: National Electrical Code (NEC), 2023 Edition (or the NEC Handbook)Essential
Bring your own; the exam is based on the code provisions only. ICC's August 2025 bulletin lists the 2023 edition even though Wyoming adopted the 2026 NEC, so check ICC's exam catalog before you buy.
NFPA store (opens in a new tab)Free online access (opens in a new tab)
Ugly's Electrical References (any edition)
Allowed in the exam room. Formulas for Ohm's law, voltage drop, motors and transformers.
Ferm's Fast Finder Index or Tom Henry's Key Word Index
Both are allowed, and a good index saves time on the questions you must look up.
Official reference list (as published by the testing agency)
- NFPA 70: National Electrical Code (NEC) or NEC Handbook (code provisions only are tested), 2023 Edition per ICC's August 2025 bulletin
- Ugly's Electrical References (any edition)
- Optional: Ferm's Fast Finder Index or Tom Henry's Key Word Index
What's on the exam
Official content outline from the International Code Council (ICC), delivered by Pearson VUE, (number of questions per topic):
| Topic | Questions | |
|---|---|---|
| General Remote-control Signaling and Power-limited Alarm Systems | 5 | |
| Installation of Class 1 Circuits | 5 | |
| Installation of Class 2 and 3 Circuits | 5 | |
| General Fire Alarm Systems | 5 | |
| Non-power-limited Fire Alarm Circuits | 5 | |
| Power-limited Fire Alarm Circuits | 5 |
Exam day details
- Administered by the International Code Council (ICC), delivered by Pearson VUE, for the Wyoming Department of Fire Prevention and Electrical Safety (State Fire Marshal).
- Fee: $115 per exam, paid to Pearson VUE when you schedule. State license fees are separate.
- 30 questions in 1 hour 30 minutes; 70% to pass (041-5 Wyo. Code R. § 3).
- Open book. ICC's August 2025 bulletin lists the 2023 NEC as the reference, even though Wyoming has adopted the 2026 NEC for enforcement. Check ICC's exam catalog for your exam before you buy a book.
- Apply to the State Fire Marshal and get approved first, then register with ICC through Pearson VUE. ICC suggests waiting 24 to 48 hours after approval before you schedule.
- Questions are four-option multiple choice and there is no penalty for guessing. Your result shows right after the exam.
- You must wait 10 days before retaking a failed exam. Each attempt needs a new fee.
- ICC exam number 235. "General Remote-control Signaling and Power-limited Alarm Systems" is 5 of the 30 questions, so weight your study there.
Frequently asked questions
What's on the Wyoming low-voltage alarm technician exam?
ICC's August 2025 outline, 30 questions: General Remote-control Signaling and Power-limited Alarm Systems 5; Installation of Class 1 Circuits 5; Installation of Class 2 and 3 Circuits 5; General Fire Alarm Systems 5; Non-power-limited Fire Alarm Circuits 5; Power-limited Fire Alarm Circuits 5.
Which NEC edition do I bring to the Wyoming electrical exam?
ICC's August 2025 bulletin lists the 2023 NEC, although Wyoming has adopted the 2026 NEC for enforcement. The NEC Handbook, Ugly's (any edition), Ferm's Fast Finder and Tom Henry's Key Word Index are also allowed. Check ICC's exam catalog before you buy a book.
Who gives the Wyoming electrical exams?
ICC, through Pearson VUE. The State Fire Marshal approves your application first; then you register and pay Pearson VUE $115 and test at a Pearson VUE center.
Free questions with answers
Show all 10 free questions and answers
A 24-volt Class 2 circuit from a listed supply will control a motorized shutoff valve that stops fuel flow to a boiler. If the circuit failed to operate, a direct fire hazard would result. Which classification and wiring method apply to this circuit?
Answer: It must meet Class 1 requirements and use Class 1 wiring methods, because the circuit controls safety-control equipment
Section 722.31 says remote-control circuits to safety-control equipment must be classified as Class 1 if failure of the equipment to operate would introduce a direct fire or life hazard. The 24-volt rating does not change this, and a Class 3 classification or a parallel Class 2 supply would not satisfy the rule. Class 1 wiring methods then apply.
Reference: NFPA 70, National Electrical Code, 2023, 722.31
An apprentice asks why a Class 2 door-chime cable can be run exposed above a ceiling without conduit while 120-volt branch-circuit wiring cannot. What is the Code basis for the difference?
Answer: The listed source limits the circuit's voltage and power, so lighter remote-control and signaling rules apply
Class 2 and Class 3 circuits get their reduced wiring requirements from the power limitations of the listed source, not from the wire itself. They are covered by the remote-control, signaling and power-limited articles (Article 725 and the general rules of Article 722). The NEC still applies to them, and a typical Class 2 source is 24 volts or more, not under 5 volts.
Reference: NFPA 70, National Electrical Code, 2023, 725.1
What is the maximum voltage permitted for a Class 1 remote-control or signaling circuit?
Answer: 600 volts, with no power limit placed on the source
A Class 1 remote-control or signaling circuit may operate at up to 600 volts and has no power limit on its source. Only a Class 1 power-limited circuit is held to 30 volts and 1,000 volt-amperes, which is why the 30 V and 1,000 values are tempting wrong answers. See 724.40.
Reference: NFPA 70, National Electrical Code, 2023, 724.40
An alarm designer wants a Class 1 power-limited circuit. Which source meets the source rating limits of Section 724.40?
Answer: A 24-volt transformer rated 750 volt-amperes
A Class 1 power-limited source may be rated no more than 30 volts and 1,000 volt-amperes. Only the 24 V, 750 VA source meets both limits. The 36 V source exceeds the voltage limit, and the 1,500 VA and 1,200 VA sources exceed the power limit.
Reference: NFPA 70, National Electrical Code, 2023, 724.40
A Class 2 alarm cable must enter a device box that also contains 120-volt switch conductors. What does the Code permit?
Answer: Permanent barrier separating the Class 2 conductors from the power conductors
Under 725.136 Class 2 and Class 3 conductors may be in an enclosure with light and power conductors only when a permanent barrier separates them (or in the limited case where the power conductors are introduced solely to connect the same equipment). Tape and an air gap do not make a barrier, and Class 2 conductors are not assumed to be 600-volt rated.
Reference: NFPA 70, National Electrical Code, 2023, 725.136(B)
A circuit is designated Class 3 and its drawings call for Type CL3 cable. Only Type CL2 cable is available, with the same fire rating as the CL3 type. Per the substitution rules in Section 722.135, what applies?
Answer: CL2 may not replace CL3 because its insulation is rated for lower voltage
Class 3 circuits may operate at higher voltage than Class 2, and Class 3 cable carries a higher voltage rating (not less than 300 V, versus 150 V for Class 2 cable). For that reason the substitution table lets CL3 stand in for CL2 but not the other way around. Matching the conductor size does not change the voltage rating, and a raceway does not either.
Reference: NFPA 70, National Electrical Code, 2023, Table 722.135(E)
A fire alarm cable is run through a 2-hour fire-resistance-rated wall, and the installer leaves the hole around the cable open. Which Article 760 cross-reference applies to this installation?
Answer: Firestop the opening with an approved method (300.21)
Section 760.3(A) directs that electrical installations in hollow spaces and fire-rated assemblies follow 300.21, so penetrations through fire-resistance-rated walls and floors must be firestopped with an approved method. A cable's jacket rating does not make an open penetration acceptable, and ordinary foam is not an approved firestop.
Reference: NFPA 70, National Electrical Code, 2023, 760.3(A)
A fire alarm control panel and a building automation panel share a terminal cabinet. Which statement matches Section 760.30 about the fire alarm circuits in it?
Answer: They must be identified at terminal and junction locations to help prevent unintentional signals
Section 760.30 requires fire alarm circuits to be identified at terminal and junction locations in a manner that helps prevent unintentional signals on the fire alarm circuits during testing and servicing of other systems. It does not require a separate locked cabinet or a particular conductor color, and listing of the panel does not remove the identification requirement.
Reference: NFPA 70, National Electrical Code, 2023, 760.30
The branch circuit that supplies an NPLFA control panel is protected by a breaker in the main panelboard. What must be done at the fire alarm control unit about this breaker?
Answer: Permanently identify the breaker's location at the control unit
Section 760.41(B) requires the location of the branch-circuit overcurrent device that supplies the fire alarm circuit to be permanently identified at the fire alarm control unit. This lets a person servicing the panel find the right breaker. The circuit may not be supplied through a GFCI or AFCI, and a second breaker in series is not required.
Reference: NFPA 70, National Electrical Code, 2023, 760.41(B)
What marking is required for equipment that supplies PLFA circuits?
Answer: Durable marking showing which circuits are power-limited fire alarm circuits
Section 760.124 requires equipment that supplies PLFA circuits to be durably marked where plainly visible to indicate each circuit that is a power-limited fire alarm circuit. The marking identifies the circuit class for the installer and inspector. High-voltage, inspection or license labels are not part of this rule.
Reference: NFPA 70, National Electrical Code, 2023, 760.124
Sources
- ICC: Wyoming Electrical Contractor/Trades Bulletin (8/2025, PDF) (opens in a new tab)
- Wyoming State Fire Marshal: Electrical licensing (opens in a new tab)
- 041-5 Wyo. Code R. § 3 (examinations and passing scores) (opens in a new tab)
Questions last verified October 29, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.