Question 1 of 10General Knowledge, Theory, Basic Load Calculations, and Definitions

A 240-volt circuit supplies a heating element that draws 12 amperes. What is the resistance of the element?

Requirements at a glance

AgencyWyoming Department of Fire Prevention and Electrical Safety (State Fire Marshal); exam by ICC through Pearson VUE
Exam50 questions, 3 hours, 70% to pass
Experience4,000 hours over at least 2 years.
Books allowedNEC or NEC Handbook (2023 per ICC's August 2025 bulletin), Ugly's (any edition), Ferm's Fast Finder, Tom Henry's Key Word Index
Fees$115 per exam to Pearson VUE; the license is $100 for 3 years.

Technicians applying to the Wyoming State Fire Marshal for a limited elevator technician license. You need 4,000 hours of experience over at least 2 years.

How to get licensed, step by step

  1. Check your experience

    Make sure you meet the State Fire Marshal's requirements for the limited elevator technician license: 4,000 hours over at least 2 years.

    Wyoming State Fire Marshal: electrical licensing (opens in a new tab)

  2. Apply and get approved

    Apply through the Wyoming electrical licensing portal. Wait for your approval notice, then allow 24 to 48 hours before you schedule so ICC can process your record.

    Apply and pay for your license (Wyoming electrical licensing portal) (opens in a new tab)ICC Wyoming Electrical Contractor/Trades Bulletin (PDF) (opens in a new tab)

  3. Register and pay with Pearson VUE

    Create a Pearson VUE account for ICC, pick the Wyoming exam, pay $115 and book a seat at a test center.

    Register with ICC at Pearson VUE (opens in a new tab)

  4. Pass the exam

    Bring your tabbed references. Your result shows right after the exam. If you fail, you must wait 10 days before you retest, and each attempt costs a new fee.

    Register with ICC at Pearson VUE (opens in a new tab)041-5 Wyo. Code R. § 3 (examinations and passing scores) (opens in a new tab)

How to prepare

  • ICC's August 2025 bulletin still lists the 2023 NEC, but Wyoming has adopted the 2026 NEC. Check ICC's exam catalog for your exam before you buy a book.
  • Tab your books before exam day. There's no time to look up every answer, so know where Articles 90, 100, 110, 210 to 250, 300 to 392, 430 and Chapter 9 sit.
  • Elevator wiring (Article 620) is half the exam, 25 of 50 questions. Know it cold and tab each of its parts.
  • The other four areas are 6 or 7 questions each: general knowledge, feeders and branch circuits, materials and installation, and motors, controls and transformers.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

  • NFPA 70: National Electrical Code (NEC), 2023 Edition (or the NEC Handbook)Essential

    Bring your own; the exam is based on the code provisions only. ICC's August 2025 bulletin lists the 2023 edition even though Wyoming adopted the 2026 NEC, so check ICC's exam catalog before you buy.

    NFPA store (opens in a new tab)Free online access (opens in a new tab)

  • Ugly's Electrical References (any edition)

    Allowed in the exam room. Formulas for Ohm's law, voltage drop, motors and transformers.

    Jones & Bartlett (opens in a new tab)

  • Ferm's Fast Finder Index or Tom Henry's Key Word Index

    Both are allowed, and a good index saves time on the questions you must look up.

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (NEC) or NEC Handbook (code provisions only are tested), 2023 Edition per ICC's August 2025 bulletin
  • Ugly's Electrical References (any edition)
  • Optional: Ferm's Fast Finder Index or Tom Henry's Key Word Index

What's on the exam

Official content outline from the International Code Council (ICC), delivered by Pearson VUE, (number of questions per topic):

TopicQuestions
General Knowledge, Theory, Basic Load Calculations, and Definitions7
Feeders, Branch Circuits, Conductors, Overcurrent Protection, and Grounding6
Electrical Materials and Installation6
Motors, Controls, and Transformers6
Elevator Wiring (Article 620)25

Exam day details

  • Administered by the International Code Council (ICC), delivered by Pearson VUE, for the Wyoming Department of Fire Prevention and Electrical Safety (State Fire Marshal).
  • Fee: $115 per exam, paid to Pearson VUE when you schedule. State license fees are separate.
  • 50 questions in 3 hours; 70% to pass (041-5 Wyo. Code R. § 3).
  • Open book. ICC's August 2025 bulletin lists the 2023 NEC as the reference, even though Wyoming has adopted the 2026 NEC for enforcement. Check ICC's exam catalog for your exam before you buy a book.
  • Apply to the State Fire Marshal and get approved first, then register with ICC through Pearson VUE. ICC suggests waiting 24 to 48 hours after approval before you schedule.
  • Questions are four-option multiple choice and there is no penalty for guessing. Your result shows right after the exam.
  • You must wait 10 days before retaking a failed exam. Each attempt needs a new fee.
  • ICC exam number 707. "Elevator Wiring (Article 620)" is 25 of the 50 questions, so weight your study there.

Frequently asked questions

What's on the Wyoming limited elevator technician exam?

ICC's August 2025 outline, 50 questions: General Knowledge, Theory, Basic Load Calculations, and Definitions 7; Feeders, Branch Circuits, Conductors, Overcurrent Protection, and Grounding 6; Electrical Materials and Installation 6; Motors, Controls, and Transformers 6; Elevator Wiring (Article 620) 25.

Which NEC edition do I bring to the Wyoming electrical exam?

ICC's August 2025 bulletin lists the 2023 NEC, although Wyoming has adopted the 2026 NEC for enforcement. The NEC Handbook, Ugly's (any edition), Ferm's Fast Finder and Tom Henry's Key Word Index are also allowed. Check ICC's exam catalog before you buy a book.

Who gives the Wyoming electrical exams?

ICC, through Pearson VUE. The State Fire Marshal approves your application first; then you register and pay Pearson VUE $115 and test at a Pearson VUE center.

Free questions with answers

Show all 10 free questions and answers
  1. A 240-volt circuit supplies a heating element that draws 12 amperes. What is the resistance of the element?

    Answer: 20 ohms

    R = E / I = 240 V / 12 A = 20 ohms. The 2,880 figure multiplies volts by amperes (that is watts), and 0.05 divides amperes by volts, inverting the formula.

    Reference: General electrical theory, Ohm's law

  2. As defined in Article 100, which term describes the maximum current a conductor can carry continuously under the conditions of use without exceeding its temperature rating?

    Answer: Ampacity

    Article 100 defines ampacity as that continuous current limit. Interrupting rating is the highest fault current a device can clear, and overload is operation above the rated current.

    Reference: NFPA 70, National Electrical Code, 2023, Article 100, Ampacity

  3. An elevator machine room has six luminaires rated 150 VA each on one 120-volt lighting circuit. What current do they draw when all are on?

    Answer: 7.5 amperes

    Total load = 6 x 150 VA = 900 VA. I = VA / E = 900 / 120 = 7.5 A. 6 A divides by the fixture rating instead of the voltage, and 0.13 A inverts the formula.

    Reference: General electrical theory, Load in VA and amperes

  4. A copper feeder to a 3-phase elevator controller must carry 82 amperes after all adjustments, and the equipment terminations are rated 75 C. Using Table 310.16, what is the smallest THWN-2 conductor?

    Answer: 4 AWG

    At the 75 C column, 4 AWG copper is 85 A and 6 AWG is 65 A, so 4 AWG is the smallest that carries 82 A. THWN-2 is 90 C rated, but termination temperature limits the usable ampacity to the 75 C column.

    Reference: NFPA 70, National Electrical Code, 2023, Table 310.16 and 110.14(C)

  5. A 100-ampere circuit breaker protects a 3-phase motor branch circuit. Using Table 250.122, what is the minimum copper equipment grounding conductor for that circuit?

    Answer: 8 AWG

    Table 250.122 gives 8 AWG copper for an overcurrent device rated up to 100 A. 10 AWG is the size for devices up to 60 A, and 6 AWG is the size for devices up to 200 A.

    Reference: NFPA 70, National Electrical Code, 2023, Table 250.122

  6. The main-line disconnecting means required by 620.51 must open which conductors?

    Answer: All ungrounded main power supply conductors to that elevator, but not the car light, receptacle and ventilation branch circuits

    The elevator main-line disconnect opens all ungrounded main power supply conductors for that elevator, but 620.51 says it must not disconnect the branch circuits required by 620.22, 620.23 and 620.24 (car lighting, receptacles and ventilation; machine room and pit lighting and receptacles), so light and power for workers stay on while the drive is locked out.

    Reference: NFPA 70, National Electrical Code, 2023, 620.51(A)

  7. For an elevator with the driving machine and controller in a machine room, where must the main-line disconnecting means be located?

    Answer: Where readily accessible to qualified persons and within sight of the motor controller

    Section 620.51(C) requires the disconnect to be readily accessible to qualified persons and, for a machine-room installation, within sight of the motor controller. Labeling alone does not replace location requirements.

    Reference: NFPA 70, National Electrical Code, 2023, 620.51(C)

  8. A cable runs through a hole bored in a wood stud. What is the minimum distance from the nearest edge of the stud to the cable, unless a steel plate protects it?

    Answer: 1-1/4 inches

    Section 300.4(A)(1) requires the hole to be at least 1-1/4 in. from the nearest edge, or the cable must be protected by a steel plate or sleeve at least 1/16 in. thick.

    Reference: NFPA 70, National Electrical Code, 2023, 300.4(A)(1)

  9. A box contains four 12 AWG conductors that terminate in it, one 12 AWG equipment grounding conductor, one single-pole switch (device yoke) and one internal cable clamp, with all conductors 12 AWG (2.25 cubic inches each). What minimum box volume is required?

    Answer: 18.0 cubic inches

    Count allowances: 4 conductors, 1 for all grounding conductors, 2 for the device, 1 for the clamps = 8 x 2.25 = 18.0 in3. 15.75 forgets one allowance, 13.5 forgets the device and the clamp (6), and 20.25 counts one too many (9).

    Reference: NFPA 70, National Electrical Code, 2023, 314.16(B)

  10. What is the minimum ampacity of the branch-circuit conductors for a 3-phase, 460-volt, 25-horsepower continuous-duty motor? (Use Table 430.250.)

    Answer: 42.5 amperes

    Table 430.250 lists 34 A for a 25 hp, 460 V motor. Section 430.22 requires the conductors to carry 125 percent: 34 x 1.25 = 42.5 A. 34 A forgets the 125 percent, and 54.4 A multiplies by 1.6.

    Reference: NFPA 70, National Electrical Code, 2023, Table 430.250 and 430.22