Ohio licensing exam

Ohio Low-Pressure Boiler Operator Exam: Practice Test & Licensing Guide

The PSI exam for Ohio's low-pressure boiler operator license (steam boilers up to 15 psi): 30 questions on boiler principles, devices, feedwater, valves and piping, burners, makeup water and operating procedures. Closed book.

Questions
30
Time limit
3 hours
Passing score
70%
Books
Closed book
What to study ↓

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Principles and Standards, Combustion and Draft

Under Ohio law, what is the maximum steam pressure for a low pressure boiler?

Requirements at a glance

AgencyOhio Division of Industrial Compliance; exam by PSI
Experience2,000 hours on a steam boiler of 15 psi or less, or 400 hours plus a 50-hour approved course
Exam30 questions, 3 hours, 70% to pass, closed book; calculator allowed
Fees$25 application, $100 PSI exam fee, $72 license (renews yearly at $72)

People who operate steam boilers of 15 psi or less in Ohio. You need 2,000 hours operating a low-pressure steam boiler, or 400 hours plus a 50-hour approved boiler course.

How to get licensed, step by step

  1. Document your hours

    Gather an employment history report or an hours-worked statement from your employer, any course certificate and the boiler's nameplate or state ID.

    Ohio Commerce: boiler operator and steam engineer licenses (opens in a new tab)

  2. Apply to the Division

    Submit the signed, notarized exam application and the $25 fee through the IC Customer Portal (you need an OHID).

    Ohio Commerce: boiler operator and steam engineer licenses (opens in a new tab)

  3. Take the PSI exam

    Once approved, the Division registers you with PSI. The low-pressure exam is closed book; you need 70% to pass and can retake as needed ($100 each time).

    PSI: Ohio steam engineer/boiler operator bulletin (opens in a new tab)

  4. Get licensed and renew yearly

    Pay the $72 license fee after you pass. Licenses expire every year; renew online before the expiration date.

    Ohio Commerce: boiler operator and steam engineer licenses (opens in a new tab)

How to prepare

  • The exam is short (30 questions), so each topic matters: boiler devices, heating sources and operating procedures are 5 questions each.
  • PSI writes the questions from Low Pressure Boilers (Steingress and Walker), which isn't allowed in the room. Learn the water column, low water cutoff, safety valve and feeder tests cold.
  • Know what to do on low water (secure the fire, don't add cold water) and the Ohio basics: the 15 psig limit and the 360 sq ft licensing threshold.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

What to study

This is a closed-book exam, so nothing comes into the exam room. Study from these:

Official reference list (as published by the testing agency)
  • Low Pressure Boilers, Steingress and Walker, American Technical Publishers (2019) (not allowed in the exam room)
  • Ohio Revised Code Chapter 4104 and Ohio Administrative Code Chapter 4101:4 (boilers)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
Principles and Standards, Combustion and Draft5
Boiler Devices5
Feedwater Arrangement4
Valves, Piping and Accessories3
Heating Sources5
Makeup Water3
Operating Procedures5

Exam day details

  • Administered by PSI Services for the Ohio Division of Industrial Compliance.
  • Fee: $100 to PSI, plus the Division's $25 application fee and $72 license fee.
  • 30 questions in 3 hours; 21 correct (70%) to pass. PSI may add a few unscored experimental questions.
  • Closed book. You may bring a silent, non-printing, non-programmable calculator.
  • Apply to the Division of Industrial Compliance first ($25, signed and notarized, through the IC Customer Portal). Once approved, the Division registers you with PSI.
  • The PSI fee is $100 per attempt and you can retake as many times as needed. Licenses cost $72 and renew every year.

Frequently asked questions

What's on the Ohio low-pressure boiler exam?

30 questions: principles and standards including combustion and draft 5, boiler devices 5, heating sources 5, operating procedures 5, feedwater arrangement 4, valves, piping and accessories 3 and makeup water 3.

Who needs a low-pressure boiler license in Ohio?

Operators of steam boilers that don't exceed 15 psi. Higher-pressure steam boilers need a high-pressure boiler operator license, which also covers low-pressure boilers.

What experience do I need?

2,000 hours operating a steam boiler of 15 psi or less, or 400 hours plus a 50-hour steam boiler operation course approved by the superintendent.

Free questions with answers

Show all 10 free questions and answers
  1. Under Ohio law, what is the maximum steam pressure for a low pressure boiler?

    Answer: 15 psig

    Ohio defines a low pressure boiler as a steam boiler operating at not more than 15 psig, or a hot water heating boiler at not more than 160 psig or 250 F. A steam boiler above 15 psig is a power boiler. 160 psig is the hot water limit, not the steam limit.

    Reference: Ohio Revised Code Chapter 4104 (Boilers), 4104.01(D) and (F)

  2. What is the most important safety device on a steam boiler for preventing overpressure?

    Answer: The safety valve

    The safety valve opens automatically to relieve pressure before it exceeds the safe limit. TM 5-642 says never to operate a boiler without one or more safety valves of sufficient ASME capacity, kept free and in working order.

    Reference: TM 5-642, Operation and Maintenance: Small Heating Systems (Department of the Army, 1990), Par. 4-41a, safety valves

  3. A safety valve set to pop at 15 psig is to be tested by hand with the try lever. At about what boiler pressure should the test be done?

    Answer: 12 to 13 psig

    TM 5-642 says to lift the valve by hand only when boiler pressure is 80 to 85 percent of the popping pressure. For a 15 psig valve that is 12 to about 12.75 psig, so about 12 to 13 psig. At lower pressure the valve may not reseat cleanly, and debris can damage the seat.

    Reference: TM 5-642, Operation and Maintenance: Small Heating Systems (Department of the Army, 1990), Par. 4-41c, safety valves

  4. What is the purpose of the Hartford loop on a gravity-return steam boiler?

    Answer: To keep boiler water from backing out into the return line and dropping the level

    The Hartford loop connects the return to an equalizing line between the supply and return headers, with the connection at the minimum safe water level. It prevents an unsafe drop in the water line from boiler water backing into the return, as from a failed check valve.

    Reference: TM 5-642, Operation and Maintenance: Small Heating Systems (Department of the Army, 1990), Par. 4-13, installation (boiler headers, Hartford loop)

  5. How should a boiler's main steam stop valve be left during operation?

    Answer: Fully open or tightly closed, never cracked partway

    TM 5-642 says the main steam valve should be tightly closed or fully opened, not left cracked, to avoid corrosion and wear of the stem, seat and disk. It should be closed and reopened periodically during the season to check that it works.

    Reference: TM 5-642, Operation and Maintenance: Small Heating Systems (Department of the Army, 1990), Par. 4-14, maintenance (boiler headers, valves and piping)

  6. Which fuel oil grade is a light distillate commonly burned in small high-pressure gun burners without preheating?

    Answer: No. 2 oil

    No. 2 is a distillate oil used in domestic and small commercial atomizing burners, at about 139,000 Btu per gallon. No. 5 and No. 6 are heavier residual oils, and No. 6 needs preheating for pumping and atomizing.

    Reference: TM 5-642, Operation and Maintenance: Small Heating Systems (Department of the Army, 1990), Par. 2-3c, commercial grade fuel oils

  7. In Ohio, what is the minimum safety valve relieving capacity required for an electric steam boiler rated at 200 kW?

    Answer: 700 lb of steam per hour

    OAC 4101:4-4-03(D) requires 3.5 lb of steam per hour of relieving capacity per kilowatt for electric boilers: 3.5 x 200 = 700 lb/hr. 350 uses 1.75 lb/kW, and 1,400 doubles the factor.

    Reference: Ohio Administrative Code Chapter 4101:4 (Boiler and Pressure Vessel Rules), 4101:4-4-03(D)

  8. What problem does hardness in boiler makeup water cause?

    Answer: Scale buildup that cuts efficiency and can cause tube failure

    Hardness minerals such as calcium and magnesium form scale and cause foaming, which reduce boiler efficiency and can cause tube failure. Softeners remove hardness by ion exchange.

    Reference: U.S. DOE, Improving Steam System Performance: A Sourcebook for Industry, 2nd Edition, Steam system basics: boiler feedwater system (softener)

  9. What is the most important item to watch in boiler operation, according to TM 5-642?

    Answer: Keeping a proper water level

    TM 5-642 calls maintaining the proper water level the most important item in boiler operation. Too low can permanently damage the boiler; too high causes wet steam, carryover and water hammer.

    Reference: TM 5-642, Operation and Maintenance: Small Heating Systems (Department of the Army, 1990), Par. 4-73, water level

  10. An operator finds the water out of sight below the bottom of the gauge glass on a fired boiler. What should be done first?

    Answer: Shut off the fuel and let the boiler cool slowly; don't add cold water

    TM 5-642 says when low water is detected, shut off automatic firing immediately (or shut the draft on hand-fired boilers) to cool the boiler gradually, and do not open cold water makeup lines. Cold water on overheated metal can crack it or cause an explosion.

    Reference: TM 5-642, Operation and Maintenance: Small Heating Systems (Department of the Army, 1990), Par. 4-78, low water level

Sources

Questions last verified October 26, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.