Ohio licensing exam

Ohio HVAC Contractor Exam: Practice Test & Licensing Guide

The PSI trade exam for Ohio's commercial HVAC contractor license: 100 questions on warm air heating, ductwork, ventilation, air conditioning, piping and appliances using the Ohio Mechanical Code and IFGC. Open book.

Questions
100
Time limit
4 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10General Knowledge and Requirements

Appliances regulated by the Ohio Mechanical Code must be:

Requirements at a glance

AgencyOhio Construction Industry Licensing Board (OCILB); exams by PSI
ExperienceAt least 5 years as a tradesperson in the trade immediately before you apply (registered engineers can qualify with 3 years of construction business experience)
Exams100 questions, 4 hours, 70%, plus the Contractor's Business and Law exam
Books allowed2024 Ohio Mechanical Code, 2021 IFGC and Modern Refrigeration and Air Conditioning
Fees$69 per PSI exam, plus OCILB application and license fees and contractor's liability insurance

Qualifying individuals for an Ohio commercial HVAC contractor license (central heating, air conditioning, ventilation and ductwork) from the OCILB.

How to get licensed, step by step

  1. Confirm you qualify

    You must be 18, a U.S. citizen or legal resident, and have 5 years in the trade. The OCILB also checks your conduct record.

    Ohio Construction Industry Licensing Board (OCILB) (opens in a new tab)Ohio Revised Code Chapter 4740 (OCILB) (opens in a new tab)

  2. Apply to the OCILB

    Send the exam application and fee to the OCILB. When it approves you, get a state (BCI) and federal (FBI) background check before you sit. Approval is good for one year.

    Ohio Construction Industry Licensing Board (OCILB) (opens in a new tab)

  3. Schedule the Business and Law exam and the HVAC exam with PSI

    Book both exams with PSI ($69 each). If you fail, wait 60 days; you can test up to 5 times in a year. Pass the business and law exam once and it covers any other trade licenses you add for three years.

    Schedule with PSI (Ohio contractors) (opens in a new tab)PSI: Ohio contractor trade exam bulletin and outlines (opens in a new tab)

  4. Get insured and licensed

    After you pass both exams, send the OCILB your results, the license fee and proof of contractor's liability insurance. Licenses renew every year with 10 hours of continuing education.

    Ohio Construction Industry Licensing Board (OCILB) (opens in a new tab)

How to prepare

  • Bring the exact editions on PSI's outline. Ohio's code books are the 2024 Ohio Plumbing Code and Ohio Mechanical Code (the 2021 IPC and IMC with Ohio amendments) and the 2023 NEC.
  • Tab your books before exam day. You can highlight, underline and index them, but you can't write in them or add loose papers.
  • Ohio's licenses are for commercial work. Residential work is handled by local jurisdictions, so questions stay on commercial buildings.
  • Warm air heating and air distribution (25) and equipment and appliances (20) are 45 of the 100 questions: tab IMC Chapters 6 and 9 and IFGC Chapters 3 and 5.
  • Ventilation and exhaust (15) comes from IMC Chapters 4 and 5: ventilation rates, kitchen hoods and dryer exhaust.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the Ohio Mechanical Code and Modern Refrigeration and Air Conditioning. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • Ohio Mechanical Code, 2024, based on the 2021 International Mechanical Code (allowed in the exam room)
  • International Fuel Gas Code (IFGC), 2021 (allowed in the exam room)
  • Modern Refrigeration and Air Conditioning, 22nd Edition, Goodheart-Willcox (allowed in the exam room)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
General Knowledge and Requirements10
Warm Air Heating and Air Distribution25
Ventilation and Exhaust Systems15
Air Conditioning10
Piping Systems10
Equipment and Appliances20
Testing and Inspection10

Exam day details

  • Administered by PSI Services for the Ohio Construction Industry Licensing Board (OCILB).
  • Fee: $69 to PSI per exam. OCILB application and license fees are separate.
  • 100 scored questions plus 10 unscored pretest items in 4 hours; 70 correct (70%) to pass.
  • The Ohio Mechanical Code is the 2021 IMC with Ohio amendments; our questions use the Ohio text.
  • Open book: bring your own copies of the allowed references. You may highlight, underline and index them beforehand, but not write in them.
  • PSI may add unscored pretest questions, which count against your time.
  • If you fail an exam, wait 60 days to retest. You can test up to 5 times in a year.
  • The OCILB must approve your application first and you need a state and federal background check before you sit. Approval is good for one year.
  • Every commercial trade license also needs the Contractor's Business and Law exam, which you pass once every three years however many trade licenses you add.

Frequently asked questions

What's on the Ohio HVAC contractor exam?

100 scored questions: warm air heating and air distribution 25, equipment and appliances 20, ventilation and exhaust systems 15, general knowledge and requirements 10, air conditioning 10, piping systems 10 and testing and inspection 10.

Which code books do I need for the Ohio HVAC exam?

The Ohio Mechanical Code (2024), the 2021 International Fuel Gas Code and Modern Refrigeration and Air Conditioning (22nd edition).

Does the Ohio HVAC license cover refrigeration?

No. Ohio licenses refrigeration contractors separately, for food and product preservation systems.

Free questions with answers

Show all 10 free questions and answers
  1. Appliances regulated by the Ohio Mechanical Code must be:

    Answer: Listed and labeled for the application, unless otherwise approved

    Section 301.7 requires appliances to be listed and labeled for the application in which they are installed and used unless approved otherwise under Section 114 of the building code. Refrigeration equipment listing is governed by Section 1101.2.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), 301.7

  2. A room without mechanical ventilation relies on windows for natural ventilation. What minimum openable area to the outdoors is required?

    Answer: 4 percent of the floor area being ventilated

    Section 402.2 requires the minimum openable area to the outdoors to be 4 percent of the floor area being ventilated. The 8 percent figure is the opening between an interior room and an adjoining room that provides the ventilation under 402.3.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), 402.2

  3. A return air opening is being located in a mechanical room that also contains a gas-fired water heater with a draft hood. How far from the draft hood must the return opening be, measured in any direction?

    Answer: At least 10 feet

    Section 601.5 requires return air openings to be at least 10 feet, measured in any direction, from an open combustion chamber or draft hood of another appliance in the same room or space.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), 601.5

  4. The same 100,000 Btu/h furnace uses two openings that connect to the outdoors through horizontal ducts. What minimum free area is required for each opening?

    Answer: 50 sq in

    IFGC Section 304.6.1 requires 1 square inch per 2,000 Btu/h where the openings communicate with the outdoors through horizontal ducts: 100,000 ÷ 2,000 = 50 square inches each.

    Reference: 2021 International Fuel Gas Code, 304.6.1

  5. Each gas appliance must have a shutoff valve. Where the valve is in the same room as the appliance, how close must it be?

    Answer: Within 6 feet, upstream of the union, connector or quick disconnect

    IFGC Section 409.5.1 requires the appliance shutoff valve to be in the same room, within 6 feet of the appliance, installed upstream of the union, connector or quick-disconnect device it serves, with access.

    Reference: 2021 International Fuel Gas Code, 409.5.1

  6. How wide must the unobstructed passageway be around all sides of a boiler, unless otherwise approved?

    Answer: 18 inches

    Section 1004.3 requires clearances around boilers, generators, heaters and tanks for inspection, servicing and replacement, with passageways around all sides of boilers at least 18 inches wide unless otherwise approved.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), 1004.3

  7. Where must a condensate drain from a cooling coil NOT discharge?

    Answer: Directly into a plumbing drain, waste or vent pipe

    Section 307.2.1.1 prohibits condensate drains from connecting directly to any plumbing drain, waste or vent pipe. They may discharge to a floor sink, floor drain, trench drain, mop sink, hub drain, standpipe, utility sink or laundry sink, but not to a lavatory tailpiece wye or tub overflow.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), 307.2.1.1

  8. What is the maximum horizontal support spacing for steel pipe in a mechanical piping system under Table 305.4?

    Answer: 12 feet

    Table 305.4 allows 12 feet horizontally and 15 feet vertically for steel pipe. Steel tubing is limited to 8 feet horizontally and 10 feet vertically.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), Table 305.4

  9. Which of the following may NOT be used as a pressure test medium for a refrigerant system (other than R-744 or R-718 systems)?

    Answer: Compressed air

    Section 1110.3 permits oxygen-free nitrogen, helium or argon as test media and prohibits oxygen, air, combustible gases and mixtures containing them. Carbon dioxide is allowed for R-744 systems and water for R-718.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), 1110.3

  10. For which refrigeration systems must the installing contractor issue a certificate of test to the code official?

    Answer: Systems containing 55 pounds or more of refrigerant

    Section 1110.8 requires the installing contractor or registered design professional to issue a certificate of test for all systems containing 55 pounds (25 kg) or more of refrigerant, showing the test date, refrigerant, test medium and field test pressures on the high- and low-pressure sides.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), 1110.8

Sources