Ohio licensing exam

Ohio Hydronics Contractor Exam: Practice Test & Licensing Guide

The PSI trade exam for Ohio's commercial hydronics contractor license: 50 questions on steam and hot-water heating, chilled-water systems, boilers, piping, controls and tests. Open book.

Questions
50
Time limit
2.5 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10General Knowledge

Under Ohio's boiler rules, a steam boiler operating at what pressure is classified as a low-pressure boiler?

Requirements at a glance

AgencyOhio Construction Industry Licensing Board (OCILB); exams by PSI
ExperienceAt least 5 years as a tradesperson in the trade immediately before you apply (registered engineers can qualify with 3 years of construction business experience)
Exams50 questions, 2.5 hours, 70%, plus the Contractor's Business and Law exam
Books allowedOAC 4101:4 boiler rules, 2024 Ohio Mechanical Code and the Boiler Operator's Guide
Fees$69 per PSI exam, plus OCILB application and license fees and contractor's liability insurance

Qualifying individuals for an Ohio commercial hydronics contractor license (steam and hot-water heating and chilled-water systems) from the OCILB.

How to get licensed, step by step

  1. Confirm you qualify

    You must be 18, a U.S. citizen or legal resident, and have 5 years in the trade. The OCILB also checks your conduct record.

    Ohio Construction Industry Licensing Board (OCILB) (opens in a new tab)Ohio Revised Code Chapter 4740 (OCILB) (opens in a new tab)

  2. Apply to the OCILB

    Send the exam application and fee to the OCILB. When it approves you, get a state (BCI) and federal (FBI) background check before you sit. Approval is good for one year.

    Ohio Construction Industry Licensing Board (OCILB) (opens in a new tab)

  3. Schedule the Business and Law exam and the hydronics exam with PSI

    Book both exams with PSI ($69 each). If you fail, wait 60 days; you can test up to 5 times in a year. Pass the business and law exam once and it covers any other trade licenses you add for three years.

    Schedule with PSI (Ohio contractors) (opens in a new tab)PSI: Ohio contractor trade exam bulletin and outlines (opens in a new tab)

  4. Get insured and licensed

    After you pass both exams, send the OCILB your results, the license fee and proof of contractor's liability insurance. Licenses renew every year with 10 hours of continuing education.

    Ohio Construction Industry Licensing Board (OCILB) (opens in a new tab)

How to prepare

  • Bring the exact editions on PSI's outline. Ohio's code books are the 2024 Ohio Plumbing Code and Ohio Mechanical Code (the 2021 IPC and IMC with Ohio amendments) and the 2023 NEC.
  • Tab your books before exam day. You can highlight, underline and index them, but you can't write in them or add loose papers.
  • Ohio's licenses are for commercial work. Residential work is handled by local jurisdictions, so questions stay on commercial buildings.
  • General knowledge (16) is almost a third of the exam: boiler and pressure vessel terms, steam and hot-water basics, safety valves and low-water cutoffs.
  • Know the IMC Chapter 10 boiler requirements and the OAC 4101:4 rules for relief valves, inspections and operating certificates.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from OAC 4101:4 and the Ohio Mechanical Code. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • Ohio Administrative Code Chapter 4101:4, Boiler and Unfired Pressure Vessel Rules (allowed in the exam room)
  • Ohio Mechanical Code, 2024 (allowed in the exam room)
  • Boiler Operator's Guide, 4th Edition (1998) or 5th Edition (2020), McGraw-Hill (allowed in the exam room)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
General Knowledge16
Heating Equipment10
Piping, Pumps, Valves10
Fuel Gas and Oil1
Venting5
Controls5
Tests and Inspections3

Exam day details

  • Administered by PSI Services for the Ohio Construction Industry Licensing Board (OCILB).
  • Fee: $69 to PSI per exam. OCILB application and license fees are separate.
  • 50 scored questions plus 2 unscored pretest items in 2.5 hours; 35 correct (70%) to pass.
  • Boiler questions come from OAC Chapter 4101:4 as well as the Ohio Mechanical Code.
  • Open book: bring your own copies of the allowed references. You may highlight, underline and index them beforehand, but not write in them.
  • PSI may add unscored pretest questions, which count against your time.
  • If you fail an exam, wait 60 days to retest. You can test up to 5 times in a year.
  • The OCILB must approve your application first and you need a state and federal background check before you sit. Approval is good for one year.
  • Every commercial trade license also needs the Contractor's Business and Law exam, which you pass once every three years however many trade licenses you add.

Frequently asked questions

What's on the Ohio hydronics contractor exam?

50 scored questions: general knowledge 16, heating equipment 10, piping, pumps and valves 10, venting 5, controls 5, tests and inspections 3 and fuel gas and oil 1.

Which books are allowed on the Ohio hydronics exam?

OAC Chapter 4101:4 (boiler and unfired pressure vessel rules), the Ohio Mechanical Code (2024) and the Boiler Operator's Guide (4th or 5th edition).

What is a hydronics contractor in Ohio?

A contractor who builds, installs, alters, repairs, maintains or services steam and hot-water heating or chilled-water systems.

Free questions with answers

Show all 10 free questions and answers
  1. Under Ohio's boiler rules, a steam boiler operating at what pressure is classified as a low-pressure boiler?

    Answer: Not exceeding 15 psig

    Rule 4101:4-1-01(H) defines a low-pressure boiler as a steam boiler operating at pressures not exceeding 15 psig, or a hot water heating boiler operating at not more than 160 psig or 250°F. The 160 psig figure is the hot water limit, not the steam limit.

    Reference: Ohio Administrative Code Chapter 4101:4 (Boiler and Unfired Pressure Vessel Rules), Rule 4101:4-1-01(H)

  2. Before an inspection or other work begins on an electric boiler, what must be done?

    Answer: The boiler must be isolated electrically and a warning tag posted on the disconnect

    Rule 4101:4-8-01(D) requires an electric boiler to be isolated electrically, with an appropriate warning tag posted on the disconnect, before inspection or any other work is started.

    Reference: Ohio Administrative Code Chapter 4101:4 (Boiler and Unfired Pressure Vessel Rules), Rule 4101:4-8-01(D)

  3. How wide must passageways around the sides of a boiler be, unless otherwise approved?

    Answer: At least 18 inches

    Section 1004.3 requires clearances for inspection, servicing and replacement and unobstructed passageways of at least 18 inches around all sides of boilers unless otherwise approved.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), 1004.3

  4. A hot water heating system has a volume of 300 gallons. Using Table 1009.2 when the necessary data for the tank equation is not known, what is the minimum pressurized diaphragm-type expansion tank capacity?

    Answer: 25 gallons

    Table 1009.2 gives 25 gallons for a pressurized diaphragm-type tank and 45 gallons for a nonpressurized (plain steel) tank for a 300-gallon system. The 45-gallon figure is the nonpressurized value.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), Table 1009.2

  5. A shutoff valve is required in which location in a hydronic piping system?

    Answer: On the supply and return of a heat exchanger not integral to a boiler

    Section 1205.1.1 requires shutoff valves on the supply and return side of a heat exchanger unless the exchanger is integral with a boiler or part of a packaged unit that can be isolated by the boiler supply and return valves.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), 1205.1.1

  6. Hydronic pipe penetrating a wall must have an opening that is:

    Answer: Larger than the pipe, sleeved in concrete or masonry, annular space protected

    Section 1206.4 requires openings for pipe penetrations in walls, floors or ceilings to be larger than the penetrating pipe, openings through concrete or masonry to be sleeved, and the annular space to be protected per the International Building Code.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), 1206.4

  7. An oil burner is served by a tank that has part of its volume above the burner inlet, with the fuel supply line taken from the top of the tank. What must be installed in place of a shutoff valve?

    Answer: An approved antisiphon valve or other siphon-breaking device

    Section 1301.4 requires an approved antisiphon valve or other siphon-breaking device, instead of the shutoff valve, where any part of the tank is above the burner inlet and the fuel supply line is taken from the top of the tank.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), 1301.4

  8. What minimum vertical height must a vent have above the highest connected appliance flue collar?

    Answer: 5 feet

    Section 802.6 requires vents to terminate not less than 5 feet in vertical height above the highest connected appliance flue collar, except for direct vent appliances and certain listed outdoor appliances.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), 802.6

  9. Which statement about a boiler low-water cutoff is correct?

    Answer: Required, and must stop combustion, except flow-protected coil or tube boilers

    Section 1007.1 requires steam and hot water boilers to have a low-water cutoff control, with an exception for coil-type and water-tube boilers requiring forced circulation that are protected by a flow sensing control. Section 1007.2 requires the control to stop combustion automatically.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), 1007.1, 1007.2

  10. A hydronic piping system has a maximum design pressure of 80 psi. At what hydrostatic test pressure must it be tested?

    Answer: 120 psi

    Section 1208.1 requires a hydrostatic test at 1-1/2 times the maximum system design pressure but not less than 100 psi, held for not less than 15 minutes: 1.5 × 80 = 120 psi, which exceeds the 100 psi minimum.

    Reference: 2024 Ohio Mechanical Code (2021 IMC with Ohio amendments), 1208.1

Sources

Questions last verified October 25, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.