New Jersey Alarm Systems Electrical Contractor Exam: Practice Test & Licensing Guide

The PSI exam for the New Jersey alarm systems electrical contractor: 50 questions on fire alarm and intrusion and security systems, installation and wiring under the 2023 NEC and NFPA 72 (2022). Open book, 70% to pass.

Questions
50
Time limit
2.75 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10General Electrical Knowledge

A 12-volt alarm zone has a 1,000-ohm resistor and a 2,000-ohm resistor connected in series across the supply. What current flows?

Requirements at a glance

AgencyState Board of Examiners of Electrical Contractors (Division of Consumer Affairs); exams by PSI
EligibilityAge 21 and five years of employment in electrical construction (see N.J.A.C. 13:31)
ExamsElectrical Contractor and Alarm Systems Electrical Contractor, plus Business and Law
Fees$49 to PSI (Business and Law is $47), plus Board application and license fees

Electrical contractor candidates in New Jersey. The Electrical Contractors Board requires this exam along with the Electrical Contractor and Business and Law exams.

How to get licensed, step by step

  1. Apply to the board

    Get the Board's approval to test. It sends an Examination Eligibility Notice with instructions for paying and scheduling.

    New Jersey Division of Consumer Affairs: professional boards (opens in a new tab)

  2. Schedule the alarm systems electrical contractor exam and Business and Law with PSI

    Pay and schedule with PSI online or at (855) 340-3713. First-time candidates take all required exams on the same day. Fees are not refundable or transferable and are valid for one year.

    Schedule with PSI (NJ electrical contractors) (opens in a new tab)

  3. Retake if needed

    Retake only the exams you failed, after the waiting period your board sets (6 months between attempts for most boards). Check your Eligibility Notice for the exact limits.

    Schedule with PSI (NJ electrical contractors) (opens in a new tab)

  4. Get licensed

    PSI sends your results to the board. Contact the board for the license application, fees and insurance requirements.

    New Jersey Division of Consumer Affairs: professional boards (opens in a new tab)

How to prepare

  • Bring the exact editions on PSI's outline, and check the bulletin again before test day. New Jersey adopted newer codes in August 2026, but the exam bulletins still name the 2023 NEC, the 2021 National Standard Plumbing Code and the 2021 IMC and IFGC.
  • First-time candidates take all required exams on the same day, so practice the trade exam and Business and Law together.
  • You can highlight, underline and index books you bring, but not write in them. The 2023 NEC is provided at the electrical and alarm test centers.
  • Fire alarm application (12), intrusion and security application (12) and installation requirements (12) are 36 of the 50 questions: split your time between NFPA 72 and the NTC Blue Book.
  • You bring NFPA 72 (2022), the NTC books (2025 editions) and CCTV from Light to Pixels; PSI provides only the NEC.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2023 NEC and NFPA 72 and the NTC Yellow Book and the NTC Blue Book. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (NEC), 2023 Edition (provided at the test center; you can't use your own copy)
  • NFPA 72: National Fire Alarm and Signaling Code, 2022 Edition (bring your own)
  • NTC Yellow Book: Video Security Systems Handbook, 2025 (bring your own)
  • NTC Blue Book: Security System Design and Installation, 2025 print (bring your own)
  • NTC Blue Book: Low Voltage Systems Handbook, 2025 (bring your own)
  • CCTV from Light to Pixels, 3rd Edition, 2014 (bring your own)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
General Electrical Knowledge5
Application of Fire Alarm Systems12
Application of Intrusion and Security Systems12
Installation Requirements12
Wiring Methods and Materials6
Special Occupancies and Conditions3

Exam day details

  • Administered by PSI Services for the New Jersey Division of Consumer Affairs boards.
  • Fee: $49 to PSI. Board application and license fees are separate.
  • 50 questions in 165 minutes; 35 correct (70%) to pass.
  • An alarm systems contractor may install, repair, maintain and connect equipment and wiring for fire detection and alarm and intrusion alarm systems. Connection to the power source is by cord and plug only, to receptacles installed by the appropriately licensed person.
  • First-time electrical contractor candidates must pass the Electrical Contractor, Alarm Systems Electrical Contractor and Business and Law exams.
  • Electrical Contractors Board rules differ from the Committee's: check your Examination Eligibility Notice for the retake limits that apply to you.
  • Your board (or committee) must approve your application first and sends an Examination Eligibility Notice. Then you pay and schedule with PSI by phone at (855) 340-3713 or online.
  • Exam fees are not refundable or transferable and are valid for one year from payment.
  • References may be highlighted, underlined and indexed before the exam but not written in; loose or attached papers are not allowed. A book PSI provides at the test center can't be marked.

Frequently asked questions

What's on the New Jersey alarm systems electrical contractor exam?

50 questions: application of fire alarm systems 12, application of intrusion and security systems 12, installation requirements 12, wiring methods and materials 6, general electrical knowledge 5 and special occupancies and conditions 3.

Which books does it use?

The 2023 NEC (provided at the test center), NFPA 72 (2022), the NTC Yellow and Blue Books (2025) and CCTV from Light to Pixels, 3rd Edition. You bring everything except the NEC.

Is this a separate exam from the electrical contractor exam?

Yes. It is a separate 50-question PSI exam with its own fee, listed in the electrical bulletin alongside the Electrical Contractor and Business and Law exams.

Free questions with answers

Show all 10 free questions and answers
  1. A 12-volt alarm zone has a 1,000-ohm resistor and a 2,000-ohm resistor connected in series across the supply. What current flows?

    Answer: 4 milliamperes

    Series resistances add: 1,000 + 2,000 = 3,000 ohms. I = 12 V / 3,000 ohms = 0.004 A = 4 mA. Using only the 1,000-ohm resistor gives 12 mA, using only the 2,000-ohm resistor gives 6 mA, and 8 mA comes from averaging the two resistors (1,500 ohms), which is not how series resistance works.

    Reference: General practice, Series circuits, R total = R1 + R2

  2. Smoke detectors with a listed spacing of 30 ft are installed on a smooth, flat ceiling. What is the greatest distance allowed from any point on the ceiling to the nearest detector?

    Answer: 21 feet

    The 0.7 rule: every point on the ceiling must be within 0.7 times the listed spacing of a detector, so 0.7 x 30 = 21 ft. Half the spacing (15 ft) applies to a straight-line wall distance, 30 ft is the spacing itself, and 42 ft divides by 0.7 instead of multiplying.

    Reference: NFPA 72, National Fire Alarm and Signaling Code, 2022, Chapter 17, Initiating Devices (smoke detector spacing, smooth ceiling)

  3. A heat detector listed for 25 ft spacing is used in a storeroom with a smooth ceiling. Using the 0.7 rule, what is the greatest distance from any ceiling point to the nearest detector?

    Answer: 17.5 feet

    Multiply the listed spacing by 0.7: 0.7 x 25 = 17.5 ft. Half the spacing (12.5 ft) is the wall-distance rule, 25 ft ignores the reduction, and 35.7 ft divides by 0.7 instead of multiplying.

    Reference: NFPA 72, National Fire Alarm and Signaling Code, 2022, Chapter 17, Initiating Devices (heat detector spacing, smooth ceiling)

  4. Which of the following may supply a Class 2 circuit for an intrusion alarm system?

    Answer: A listed Class 2 power supply

    The power source for a Class 2 or Class 3 circuit must be a listed Class 2 or Class 3 transformer or power supply, or other listed equipment marked to identify the Class 2 or Class 3 source. An unmarked or non-listed source does not meet 725.60(A).

    Reference: NFPA 70, National Electrical Code (NEC), 2023, 725.60(A)

  5. A Class 2 power-and-data cable carries power to a camera over 24 AWG conductors. The power source's rated current is 0.25 ampere per conductor. Must the installer apply the ampacity limits of Table 725.144?

    Answer: No; the table is not required for 24 AWG or larger conductors at not more than 0.3 ampere per conductor

    The exception to 725.144(A) says compliance with Table 725.144 is not required where the conductors are 24 AWG or larger and the rated current per conductor of the power source does not exceed 0.3 A. Here 0.25 A on 24 AWG meets that exception, so the table is not required.

    Reference: NFPA 70, National Electrical Code (NEC), 2023, 725.144(A), Exception

  6. May the branch circuit that supplies a fire alarm control unit be protected by a ground-fault circuit interrupter or an arc-fault circuit interrupter?

    Answer: No; the branch circuit shall not be supplied through GFCIs or AFCIs

    760.121(B)(2) (and 760.41(B) for non-power-limited circuits) says the fire alarm branch circuit shall not be supplied through GFCIs or AFCIs, because a nuisance trip would silently disable the system.

    Reference: NFPA 70, National Electrical Code (NEC), 2023, 760.121(B)(2)

  7. What must be permanently identified at the fire alarm control unit?

    Answer: The location of the branch-circuit overcurrent protective device

    The location of the branch-circuit overcurrent protective device that supplies the fire alarm equipment shall be permanently identified at the fire alarm control unit (760.121(B)(3)), so service personnel can find the source of power.

    Reference: NFPA 70, National Electrical Code (NEC), 2023, 760.121(B)(3)

  8. Which conductor material is permitted for fire alarm system wiring?

    Answer: Copper only

    Only copper conductors are permitted for fire alarm systems; they may be solid or stranded (760.49(A) and (C)). Aluminum and copper-clad aluminum are not permitted for fire alarm wiring.

    Reference: NFPA 70, National Electrical Code (NEC), 2023, 760.49(A)

  9. Non-power-limited fire alarm cables installed as wiring within buildings must have what minimum temperature rating?

    Answer: 60 degrees C (140 degrees F)

    Non-power-limited fire alarm cables shall have a temperature rating of not less than 60 degrees C (140 degrees F) (760.176). They must also use 18 AWG or larger copper conductors with insulation rated at 600 V or more.

    Reference: NFPA 70, National Electrical Code (NEC), 2023, 760.176

  10. A fire alarm installer asks whether wiring may be run inside a commercial kitchen's grease exhaust duct. What does the Code say?

    Answer: No wiring system of any type may be installed in it

    No wiring system of any type shall be installed in ducts used to transport dust, loose stock or flammable vapors, or in any duct or shaft containing only such ducts used for vapor removal or ventilation of commercial-type cooking equipment (300.22(A)).

    Reference: NFPA 70, National Electrical Code (NEC), 2023, 300.22(A)