Question 1 of 10Installation of Equipment

A gas furnace is installed in an attic. What is the minimum height and width of the unobstructed passageway to the appliance, and the maximum passageway length (no exceptions applying)?

Requirements at a glance

AgencyMichigan LARA, Bureau of Construction Codes; exam by PSI
Exam150 questions, 3 hours, 75% to pass
Books allowed2021 Michigan Mechanical Code, 2015 Michigan Residential Code, 2021 IFGC, ACCA Manual J and D, SMACNA duct standards, PA 407 and PA 230
Fees$100 to PSI per attempt, plus LARA application and license fees
ExperienceAt least 3 years or 6,000 hours of HVAC equipment experience, backed by sworn statements from your contractor-of-record employers; a 2-year HVAC program can count for up to 1 year or 2,000 hours (MCL 339.5807)

Anyone applying to LARA for a Michigan mechanical contractor license covering HVAC equipment, including ductwork and gas piping.

How to get licensed, step by step

  1. Apply to LARA

    Submit your mechanical contractor application. LARA approves you before you can pay for the exam.

    Michigan LARA: Bureau of Construction Codes (opens in a new tab)

  2. Schedule with PSI

    Follow your approval letter to book the HVAC Equipment exam. Retests are unlimited within the year at $100 each.

    Schedule with PSI (Michigan mechanical) (opens in a new tab)PSI: Michigan mechanical contractor candidate bulletin (opens in a new tab)

  3. Check the book list

    The bulletin points to LARA's mechanical reference materials list. Bring bound, unmarked copies of the allowed editions.

    PSI: Michigan mechanical contractor candidate bulletin (opens in a new tab)

How to prepare

  • Bring only what the bulletin allows. Michigan reference books must be bound and unmarked: no highlighting, underlining or loose papers.
  • Michigan's codes are the 2021 Michigan Plumbing Code and Mechanical Code (the 2021 IPC and IMC with Michigan amendments) and the 2015 Michigan Residential Code. Study the Michigan text, not the model code.
  • The exam spans residential and commercial work: heat pumps, mini splits, rooftop units, kitchen exhaust, duct systems, Type B vents and gas piping including CSST.
  • Practice Manual J load and Manual D duct sizing steps and gas pipe sizing from the fuel gas tables.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the Michigan Mechanical Code and the Michigan Residential Code. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • 2021 Michigan Mechanical Code
  • 2015 Michigan Residential Code
  • International Fuel Gas Code (IFGC), 2021
  • ACCA Manual J (2011) and Manual D (2016)
  • SMACNA HVAC Duct Construction Standards 006-2020 (4th edition) and SMACNA Fibrous Glass Duct Construction Standards (7th edition, 2010)
  • Skilled Trades Regulation Act, 2016 PA 407 and State Construction Code Act, 1972 PA 230

What's on the exam

Estimated topic weighting. No official breakdown is published:

TopicQuestions
Heating and Cooling Principles25
Installation of Equipment40
Ductwork25
Gas Piping25
Venting15
Exhaust10
Codes10

Exam day details

  • Administered by PSI Services for the Michigan Department of Licensing and Regulatory Affairs (LARA), Bureau of Construction Codes.
  • Fee: $100 to PSI per attempt, non-refundable and valid for one year. LARA application and license fees are separate.
  • 150 questions in 3 hours; 75% to pass. Fee $100 (other mechanical exams are $50).
  • The bulletin describes the content but gives no per-topic weights. Our topic weights are an estimate that adds up to 150.
  • Content covers forced air heating and cooling in residential and commercial work (heat pumps, mini splits, rooftop units from 2 to 25 tons, geothermal), commercial kitchen exhaust (Type I and II), duct systems, Type B vents, gas piping for natural gas, propane and fuel oil, CSST layout and exhaust and special venting.
  • Reference books must be bound and unmarked, with no highlighting or loose papers. Check LARA's mechanical reference materials list for what you may bring.
  • If you fail you may retest an unlimited number of times within the year, paying the fee each attempt.
  • The Department (LARA BCC) must approve your application first. It sends a notification letter with instructions to pay and schedule with PSI; only the State decides eligibility.
  • PSI may add up to ten unscored experimental questions; they are not counted in your score and don't take time from the exam.
  • Cancel or reschedule at least 2 days before the appointment to keep your fee; late cancellations and no-shows forfeit it.

Frequently asked questions

What's on the Michigan HVAC Equipment exam?

150 questions on heating and cooling principles, installation of HVAC equipment and systems, ductwork, gas piping (natural gas, propane, fuel oil and CSST), venting, exhaust and codes and standards, including questions on 2016 PA 407 and 1972 PA 230.

Which books can I use on the Michigan HVAC Equipment exam?

It is open book. The bulletin lists the 2021 Michigan Mechanical Code, the 2015 Michigan Residential Code, the 2021 IFGC, ACCA Manual J and D and SMACNA duct standards. Confirm the current list on LARA's reference materials page before you go.

How much does the Michigan HVAC Equipment exam cost?

$100 to PSI per attempt. LARA application and license fees are separate.

Free questions with answers

Show all 10 free questions and answers
  1. A gas furnace is installed in an attic. What is the minimum height and width of the unobstructed passageway to the appliance, and the maximum passageway length (no exceptions applying)?

    Answer: 30 inches high, 22 inches wide, not more than 20 feet long

    Section 306.3 requires an attic passageway at least 30 inches high and 22 inches wide, with continuous solid flooring at least 24 inches wide, measured not more than 20 feet along the centerline. The 50-foot length applies only under the exception where the passageway is at least 6 feet high and 22 inches wide for its whole length.

    Reference: 2021 Michigan Mechanical Code, Section 306.3

  2. A fuel-fired appliance with an ignition source is to be installed in a private garage. What is the minimum height of the ignition source above the garage floor, absent a flammable-vapor-ignition-resistant listing?

    Answer: 18 inches

    Section 304.3 requires the source of ignition to be at least 18 inches above the floor in garages and other listed locations. An exception applies only to appliances listed as flammable vapor ignition resistant.

    Reference: 2021 Michigan Mechanical Code, Section 304.3

  3. Under Section 603.3, which relationship must hold between a duct's pressure classification and the system it serves?

    Answer: The duct classification must equal or exceed the design pressure of the air distribution system

    Section 603.3 classifies ducts at positive or negative 0.5, 1.0, 2.0, 3.0, 4.0, 6.0 or 10.0 inches of water column, and the classification must equal or exceed the design pressure of the system. Negative pressures are classified as well.

    Reference: 2021 Michigan Mechanical Code, Section 603.3

  4. What is the maximum length of a flexible air connector under the Michigan Mechanical Code?

    Answer: 14 feet

    Section 603.6.2.1 limits flexible air connectors to 14 feet. Section 603.6.2.2 also prohibits them from passing through any wall, floor or ceiling.

    Reference: 2021 Michigan Mechanical Code, Section 603.6.2.1

  5. Pipe volume calculations for a large commercial gas system come to 600 cubic feet. For how long, at minimum, must the pressure test be held?

    Answer: 60 minutes

    Section 406.4.2 requires 1/2 hour per 500 cubic feet or fraction thereof. 600 cubic feet is 2 increments (500 + a fraction), so 2 x 30 = 60 minutes. The test need not exceed 24 hours.

    Reference: International Fuel Gas Code (IFGC), 2021, Section 406.4.2

  6. A Type B-W gas vent serves a vented wall furnace. What is its minimum vertical height above the bottom of the furnace?

    Answer: 12 feet

    Section 503.6.6 sets the minimum termination height of a Type B-W gas vent at 12 feet above the bottom of the wall furnace. The 5-foot rule applies to Type B and L vents measured from the draft hood or flue collar.

    Reference: International Fuel Gas Code (IFGC), 2021, Section 503.6.6

  7. Which is required at the termination of a clothes dryer exhaust duct?

    Answer: A back-draft damper, with no screen installed

    Section 504.4 requires dryer exhaust ducts to terminate outside, be equipped with a back-draft damper, not terminate within 3 feet of a ventilated soffit section, and have no screens at the termination. Screws that obstruct flow are also prohibited.

    Reference: 2021 Michigan Mechanical Code, Section 504.4

  8. A mechanical permit has been issued but work has not started. After how many days does the permit expire under the Michigan Mechanical Code?

    Answer: 180 days

    Section 106.4.3 says a permit expires if work has not started within 180 days after issuance, or if the work is suspended or abandoned for 180 days.

    Reference: 2021 Michigan Mechanical Code, Section 106.4.3

  9. How many Btu/h equal one ton of refrigeration capacity?

    Answer: 12,000 Btu/h

    One ton of cooling is the heat needed to melt one ton of ice in 24 hours: 288,000 Btu / 24 h = 12,000 Btu/h. A 36,000 Btu/h system is 3 tons.

    Reference: General practice, General practice: cooling capacity units

  10. A system moves 1,200 cfm and the supply air is 20 degrees F cooler than the return air. Using sensible heat Q = 1.08 x cfm x TD, what is the sensible cooling delivered?

    Answer: 25,920 Btu/h

    Q = 1.08 x 1,200 x 20 = 25,920 Btu/h. The constant 1.08 combines air density (0.075 lb/ft3), specific heat (0.24 Btu/lb-F) and 60 minutes per hour.

    Reference: General practice, General practice: sensible heat equation