Massachusetts licensing exam

Massachusetts Master Electrician Exam (Part 1): Practice Test & Licensing Guide

Part 1 of the Massachusetts master electrician exam: 90 questions in 240 minutes on the NEC and Massachusetts amendments, including state-specific requirements and advanced electrical theory. Open book, 70% (63) to pass.

Questions
90
Time limit
4 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10State Specific Electrical Requirements

A permit holder has not started the authorized wiring work or has made no progress for the preceding 12 months. What may the Inspector of Wires do under 527 CMR 12.00?

Requirements at a glance

AgencyBoard of State Examiners of Electricians (Division of Occupational Licensure); exams by PSI
LicenseMaster Electrician
FormatPart 1: 90 questions, 240 minutes, open book, 70% to pass
ExamsPart 1 (90 questions, 240 minutes), then Part 2 Business and Law (50 questions, 120 minutes)
Fees$80 to PSI for Part 1 and $55 for Part 2, plus the Board application and license fee

Massachusetts journeyman electricians applying for a master electrician license from the Board of State Examiners of Electricians.

How to get licensed, step by step

  1. Apply to the Board

    Apply through the Board with your education and work hours, a CORI authorization and a 15-hour code update certificate. Review takes up to 30 days. Approval lasts 12 months.

    Board of State Examiners of Electricians (opens in a new tab)

  2. Schedule the master electrician exam with PSI

    PSI emails an exam confirmation notice after approval. Test at a PSI site in Auburn, Boston, Fall River, Lawrence or West Springfield. Cancel at least 2 days ahead.

    Schedule with PSI (Massachusetts electricians) (opens in a new tab)

  3. Pass both parts

    Each part is scored separately at 70%. If you fail one, retake only that part, up to 6 times within a year of approval.

    Schedule with PSI (Massachusetts electricians) (opens in a new tab)

  4. Get licensed

    Your scores go to the Division of Occupational Licensure. Pay the license fee in the eLIPSE portal to get your license.

    Board of State Examiners of Electricians (opens in a new tab)

How to prepare

  • Massachusetts adopted the 2026 NEC with state amendments (527 CMR 12.00) effective 4/24/2026. The PSI bulletin names no NEC year and adds code items about seven months after adoption, so check the bulletin for your test date.
  • Bring the NEC, the Massachusetts amendments and NFPA 72. Highlighting, underlining and margin notes are allowed before the exam; only a silent, non-programmable calculator is allowed.
  • Wiring methods and devices (15), services (11), grounding and bonding (10) and special occupancies (10) lead Part 1.
  • Part 1 adds 4 state-specific items and 6 advanced theory items: know the 527 CMR 12.00 amendments and 237 CMR rules.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • National Electrical Code (NFPA 70), the edition adopted by the Board
  • 527 CMR 12.00: Massachusetts amendments to the NEC
  • NFPA 72 National Fire Alarm and Signaling Code
  • Ugly's Electrical References and American Electricians' Handbook (listed by PSI as sources, not allowed in the exam room)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
State Specific Electrical Requirements4
Advanced Elec Knowledge and Elec Theory6
Services11
Grounding and Bonding10
Wiring Methods and Devices15
Motors7
Transformers1
Low-Voltage Distribution2
Special Occupancies and Equipment10
Overcurrent Protection6
Lighting2
Alarm Systems6
Solar6
Battery Storage4

Exam day details

  • Administered by PSI Services for the Massachusetts Board of State Examiners of Electricians.
  • Fee: $80 to PSI for Part 1 and $55 for Part 2 (Business and Law). Board application and license fees are separate.
  • 90 questions in 240 minutes; 70% (63) to pass. Part 2 is the Business and Law exam (50 questions in 120 minutes), which is not part of this practice bank.
  • Open book and two parts. Each part is scored on its own and you must pass both. Journeyman Part 2 is the Applied exam; Master Part 2 is Business and Law.
  • If you fail a part, you can retake just that part up to 6 times within 1 year of your application approval date. Application approval lasts 12 months. Under 237 CMR 14.02 (amended 11/21/2025), after 3 failed attempts the Board requires proof of a Board-approved exam review or prep course, and after 6 you must repeat the required education hours.
  • Allowed in the exam room: the adopted NEC, the Massachusetts amendments (527 CMR 12.00), NFPA 72, the Board's rules (237 CMR) and the listed Massachusetts laws. Highlighting and underlining are allowed, and so are handwritten notes in the margins before the exam; only a silent, non-programmable calculator is allowed.
  • Exams are scheduled daily at PSI sites in Auburn, Boston, Fall River, Lawrence and West Springfield. Cancel at least 2 days ahead or you forfeit the fee.
  • The Board approves your application first (high school diploma, 600 hours of journeyman education, 4 years and 8,000 hours of work, a CORI check and a 15-hour code update certificate; masters need a 150-hour master course and 1 year as a Massachusetts journeyman). Applications take up to 30 days.

Note: 527 CMR 12.00 adopted the 2026 NEC with Massachusetts amendments, effective 4/24/2026. The PSI bulletin (effective 9/30/2026) names no NEC year, but says new code items can be added seven months after a code takes effect, which is about late November 2026. Our questions follow the 2026 NEC; check your PSI bulletin for the edition on your test date.

Frequently asked questions

What is on the Massachusetts master electrician Part 1 exam?

90 questions: services 11, wiring methods and devices 15, grounding and bonding 10, special occupancies and equipment 10, motors 7, advanced electrical knowledge and theory 6, overcurrent protection 6, alarm systems 6, solar 6, state-specific requirements 4, battery storage 4, low-voltage distribution 2, lighting 2 and transformers 1.

Which NEC edition is on the Massachusetts exam?

Massachusetts adopted the 2026 NEC with state amendments effective 4/24/2026. The PSI bulletin names no year, so check it for your test date.

What is Part 2?

Business and Law: 50 questions in 120 minutes, 70% to pass, covering Massachusetts licensing, contracts, liens, taxes and risk management.

Free questions with answers

Show all 10 free questions and answers
  1. A permit holder has not started the authorized wiring work or has made no progress for the preceding 12 months. What may the Inspector of Wires do under 527 CMR 12.00?

    Answer: Deem the permit abandoned and invalid

    Rule 8 of 527 CMR 12.00 says permits are limited as to time of ongoing construction, and the inspector may deem a permit abandoned and invalid if work has not commenced or progressed during the preceding 12-month period. A written application for an extension may be granted for reasonable cause. The rule does not authorize license action or transfer of the permit.

    Reference: 527 CMR 12.00 (2026 NEC with Massachusetts amendments), 527 CMR 12.00, Rule 8

  2. A new two-family dwelling is being built in Massachusetts. Where does 230.70(A)(1), as amended by 527 CMR 12.00, require the service disconnect to be installed?

    Answer: In a readily accessible outdoor location

    The Massachusetts amendment to 230.70(A)(1) applies to one- and two-family dwellings and new buildings of double occupancy where at least one occupancy is a dwelling unit, and requires service disconnects in a readily accessible outdoor location. The NEC's general rule allowing the nearest point of entrance inside does not control for these buildings.

    Reference: 527 CMR 12.00 (2026 NEC with Massachusetts amendments), 230.70(A)(1) as amended by 527 CMR 12.00

  3. An engineer's coordination study for a Massachusetts building shows the feeder and branch breakers are not selective for faults that clear in less than 0.1 second. Under the Massachusetts revision of the Article 100 definition of Selective Coordination, for which events must the devices still localize the outage to the affected circuit?

    Answer: Overcurrents lasting longer than 0.1 second, from overload, ground fault or short circuit

    The Massachusetts definition describes localization of an overcurrent condition to restrict outages to the circuit or equipment affected for fault current events that extend beyond 0.1 second, whether from overload, ground fault or short circuit, over the full range of overcurrent device opening times applicable to such events.

    Reference: 527 CMR 12.00 (2026 NEC with Massachusetts amendments), Article 100, Coordination, Selective (527 CMR 12.00)

  4. Type NM cable is run parallel to wood studs in a Massachusetts house where nails or screws are likely to penetrate. What spacing from the nearest edge of the framing member does the amended 334.17 require, or what protection if that spacing cannot be kept?

    Answer: 19 mm (3/4 in.) from the edge, or a steel plate or sleeve at least 1.6 mm (1/16 in.) thick

    Massachusetts 334.17 requires the nearest outside surface of cable run parallel to framing members or furring strips to be at least 19 mm (3/4 in.) from the nearest edge where nails or screws are likely to penetrate. Where that cannot be maintained, a steel plate, sleeve or equivalent at least 1.6 mm (1/16 in.) thick is required (or a listed and marked thinner steel plate giving equal protection).

    Reference: 527 CMR 12.00 (2026 NEC with Massachusetts amendments), 334.17 (527 CMR 12.00)

  5. A designer of a Massachusetts hospital's essential electrical system assumes all of Article 700 (Emergency Systems) governs every branch. Under the revised 517.26, how much of Article 700 actually applies?

    Answer: Only the fire protection rules of 700.10(D), and only to the life safety branch

    The Massachusetts revision of 517.26 provides in (A) that, other than as specified in (B), the requirements of Article 700 do not apply, and in (B) that the life safety branch of the essential electrical system must comply with 700.10(D) (fire protection of emergency system wiring).

    Reference: 527 CMR 12.00 (2026 NEC with Massachusetts amendments), 517.26 (527 CMR 12.00)

  6. Under 690.31(D)(2) as revised in Massachusetts, how must the required PV circuit labels be formatted?

    Answer: Reflective, all capital letters, at least 9.5 mm (3/8 in.) high, white on a red background

    Massachusetts revises the second sentence of 690.31(D)(2): labels must be reflective, all letters capitalized, with a minimum letter height of 9.5 mm (3/8 in.) in white on a red background.

    Reference: 527 CMR 12.00 (2026 NEC with Massachusetts amendments), 690.31(D)(2) (527 CMR 12.00)

  7. A service has two parallel sets of 350 kcmil copper ungrounded conductors per phase. The grounding electrode conductor runs to a metal underground water pipe and to building steel. Using Table 250.66, what is the minimum copper GEC?

    Answer: 2/0 AWG

    For parallel sets, Table 250.66 is entered with the equivalent area of the largest ungrounded set: 2 x 350 = 700 kcmil. The row for copper over 600 through 1100 kcmil requires 2/0 AWG. A single 350 kcmil set (over 3/0 through 350 kcmil) would call for 2 AWG, and 1/0 AWG is the over 350 through 600 row. 3/0 AWG applies only above 1100 kcmil.

    Reference: NFPA 70, National Electrical Code, 2026, 250.66; Table 250.66

  8. A 40 hp, 460-volt, 3-phase squirrel-cage motor (not Design B energy-efficient) is protected by an inverse-time circuit breaker. What is the maximum standard breaker rating permitted by Table 430.52(C)(1), using the next-higher-standard-size allowance?

    Answer: 150 A

    Use the Table 430.250 FLC, not the nameplate (430.6(A)(1)): 40 hp at 460 V is 52 A. Table 430.52(C)(1) allows an inverse-time breaker at 250 percent: 52 x 2.5 = 130 A. 130 A is not a standard size in 240.6(A), so 430.52(C)(1)(a) permits the next higher standard rating, 150 A. 125 A rounds down, and 130 A is the unrounded value.

    Reference: NFPA 70, National Electrical Code, 2026, 430.52(C)(1); Table 430.52(C)(1); Table 430.250

  9. What is the full-load line current of a balanced 112.5 kVA, 3-phase load supplied at 208 volts?

    Answer: 312 A

    For a balanced 3-phase load, I = VA / (1.732 x V) = 112,500 / (1.732 x 208) = 312 A. 541 A divides by only 208 (112,500 / 208), 180 A divides by 624 (3 x 208), and 271 A uses 240 V instead of 208 V (112,500 / (1.732 x 240)).

    Reference: NFPA 70, National Electrical Code, 2026, Electrical theory (three-phase power: I = kVA x 1000 / (1.732 x E))

  10. A non-power-limited fire alarm circuit is supplied by a single-phase transformer with a 120-volt primary and a 2-wire, 24-volt secondary. The secondary conductors have an ampacity of 20 A. Under Exception No. 1 to 760.45, what is the largest primary-side overcurrent protection that may be relied on to protect the secondary conductors?

    Answer: 4 A

    Exception No. 1 to 760.45 lets primary-side protection protect the conductors of a 2-wire (single-voltage) secondary if it does not exceed the secondary conductor ampacity multiplied by the secondary-to-primary voltage ratio: 20 x (24 / 120) = 20 x 0.2 = 4 A. 100 A inverts the ratio (20 x 120 / 24), 20 A ignores the ratio, and 5 A is just the primary-to-secondary voltage ratio (120 / 24) mistaken for amperes. Secondaries other than 2-wire are not considered protected by the primary device.

    Reference: NFPA 70, National Electrical Code, 2026, 760.45, Exception No. 1

Sources

Questions last verified November 15, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.