Maryland licensing exam

Maryland Restricted Ventilation Exam (Master and Journeyman): Practice Test & Licensing Guide

The PSI exam for the Maryland master restricted ventilation license: 40 questions on electrical controls, air distribution and safety. Open book, 70% to pass. The journeyman restricted ventilation exam is air distribution and safety only.

Questions
40
Time limit
90 min
Passing score
70%
Books
Open book

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Air Distribution Systems

An outdoor air intake for a ventilation system is being placed beside a building's loading dock. With no exception applied, what is the minimum horizontal distance the IMC requires between the intake and the dock?

Requirements at a glance

AgencyMaryland State Board of HVACR Contractors; exam by PSI
ExperienceMaster restricted: licensed and regularly employed as a journeyman, limited contractor or master restricted contractor for at least 3 years with at least 1,875 hours of HVACR work (or 6 years of documented experience). Journeyman restricted: a Maryland apprentice license for at least 3 years with 1,875 hours of training, or an approved apprentice program.
ExamMaster restricted: 40 questions, 90 minutes, 70% to pass. Journeyman restricted: 40 questions, 90 minutes, Air Distribution 35 and Safety 5
Books allowed2012 IMC, Modern Refrigeration and Air Conditioning, NAIMA Fibrous Glass Duct Construction (5th edition), SMACNA HVAC Duct Construction (3rd edition), 29 CFR 1926 and the ACCA Ductulator
Fees$50 to PSI, plus Board application and license fees

HVACR workers applying for a Maryland master restricted or journeyman restricted license in the ventilation specialty from the State Board of HVACR Contractors.

How to get licensed, step by step

  1. Confirm you qualify

    Master restricted: licensed and regularly employed as a journeyman, limited contractor or master restricted contractor for at least 3 years with at least 1,875 hours of HVACR work (or 6 years of documented experience). Journeyman restricted: a Maryland apprentice license for at least 3 years with 1,875 hours of training, or an approved apprentice program.

    Maryland Department of Labor: Occupational and Professional Licensing (opens in a new tab)Maryland Code (General Assembly) (opens in a new tab)

  2. Apply through PSI

    Submit the exam application online at the PSI site below (mailed or faxed applications are returned). PSI and the Board review your documents, then email you how to pay and schedule.

    Schedule with PSI (HVACR contractors) (opens in a new tab)

  3. Pass the open-book exam

    Exam fees are non-refundable and non-transferable. Exam fees are valid for 90 days, and you may not test more often than every 30 days.

    Schedule with PSI (HVACR contractors) (opens in a new tab)

  4. Apply for the license

    After you pass, the Board sends you the license application. Pay the license fee and file any required insurance.

    Maryland Department of Labor: Occupational and Professional Licensing (opens in a new tab)

How to prepare

  • Tab your books before exam day: permanent plastic tabs (Avery Swift or Redi-Tag), highlighting and underlining are allowed; Post-It flags and writing in the book are not.
  • Air distribution is 30 of the 40 master restricted questions (35 on the journeyman restricted exam); practice duct sizing with the ACCA Ductulator.
  • The practice bank does not quote Modern Refrigeration, Manual J, Stoecker, NAIMA or SMACNA (copyrighted); use those books in your tabs for the matching topics.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

    Official reference list (as published by the testing agency)
    • International Mechanical Code (IMC), 2012 or 2018 edition (allowed in the exam room)
    • Modern Refrigeration and Air Conditioning, 19th, 20th or 21st edition, Goodheart-Willcox (allowed in the exam room)
    • 29 CFR Part 1926 (OSHA construction standards), with latest amendments, or the PSI selections (allowed in the exam room)
    • Fibrous Glass Duct Construction Standards, 5th edition (2002), NAIMA (allowed in the exam room)
    • HVAC Duct Construction Standards: Metal and Flexible, 3rd edition (2005), SMACNA (allowed in the exam room)
    • ACCA Ductulator (duct slide rule) (allowed in the exam room)

    What's on the exam

    Official content outline from PSI Services (number of questions per topic):

    TopicQuestions
    Electrical Knowledge, Motors, and Controls5
    Air Distribution Systems30
    Safety5

    Exam day details

    • Administered by PSI Services for the Maryland State Board of HVACR Contractors.
    • Fee: $50 to PSI per exam. Board application and license fees are separate.
    • 40 questions in 90 minutes; 28 correct (70%) to pass. The blueprint shown is the master restricted ventilation exam.
    • The journeyman restricted ventilation exam is also 40 questions in 90 minutes: Air Distribution 35 and Safety 5 (no electrical section).
    • The master restricted and journeyman restricted exams in each specialty share one content outline, so this page covers both levels.
    • Master restricted eligibility: licensed by the Board and regularly employed as a journeyman, limited contractor or master restricted contractor (any specialty) for at least 3 years, under a master contractor or a master restricted contractor in the same specialty, with at least 1,875 hours of HVACR work. Others may apply with 6 years of documented HVACR experience.
    • Journeyman restricted eligibility: a Maryland HVACR apprentice license for at least 3 years with at least 1,875 hours of training under a licensed contractor (or a master restricted contractor in the same category), or a Board-approved apprentice program or approved coursework combination. Others may apply to the Board with documented experience.
    • Open book: you may bring only the listed references (none are provided), which you may index, highlight and underline but not write in. Study guides are not allowed.
    • Exam fees are valid for 90 days and for one examination only; they are not refundable or transferable.
    • You may not take an HVACR exam more often than every 30 days.
    • Master, master restricted and limited contractors who own the business or pull permits must carry $300,000 personal liability and $100,000 property damage insurance ($400,000 combined per occurrence).
    • About the practice questions: they are written from the IMC, 29 CFR 1926 and the Maryland HVACR statute and regulations. Modern Refrigeration and Air Conditioning, Manual J, Stoecker, NAIMA and SMACNA are copyrighted, so they are not quoted in the bank; open those books for the matching topics.

    Frequently asked questions

    What's on the Maryland restricted ventilation exam?

    Master restricted: air distribution 30, electrical knowledge, motors and controls 5 and safety 5. Journeyman restricted: air distribution 35 and safety 5.

    Are NAIMA and SMACNA covered in the practice questions?

    No. Those duct standards are not freely available, so the bank draws on IMC chapter 6 and general duct and airflow principles. Bring the NAIMA and SMACNA books to the exam as allowed references.

    Free questions with answers

    Show all 10 free questions and answers
    1. An outdoor air intake for a ventilation system is being placed beside a building's loading dock. With no exception applied, what is the minimum horizontal distance the IMC requires between the intake and the dock?

      Answer: 10 feet

      Section 401.4, Item 2, requires outdoor air intakes to be at least 10 feet horizontally from hazardous or noxious contaminant sources such as vents, streets, alleys, parking lots and loading docks. The 3-foot figure is Item 3's vertical offset (intake at least 3 feet below a contaminant source within 10 feet), not a horizontal separation from a dock.

      Reference: 2018 International Mechanical Code (IMC), Section 401.4

    2. A rooftop intake sits only 6 feet horizontally from a parking lot below. Under what condition may it stay closer than 10 feet horizontally to the lot?

      Answer: The opening is at least 25 feet vertically above the lot

      Section 401.4, Item 2, allows an outdoor air intake closer than 10 feet horizontally to streets, alleys, parking lots and loading docks only where it is at least 25 feet vertically above them. Screens and vehicle counts have no bearing on the separation distance.

      Reference: 2018 International Mechanical Code (IMC), Section 401.4

    3. A plumbing vent terminates 6 feet horizontally from an outdoor air intake. How must the intake opening be located relative to the vent terminal?

      Answer: At least 3 feet below the vent terminal

      Section 401.4, Item 3, requires an intake opening to be at least 3 feet below a contaminant source (vents are named contaminant sources) when that source is within 10 feet of the opening. Locating the intake above the vent would put it in the plume path.

      Reference: 2018 International Mechanical Code (IMC), Section 401.4

    4. An interior storage room of 12 feet by 15 feet has no outdoor openings and is ventilated through an adjoining room. What is the minimum unobstructed opening between the two rooms?

      Answer: 25 square feet

      Section 402.3 requires the opening to be at least 8 percent of the interior room's floor area but not less than 25 square feet. 12 x 15 = 180 sq ft; 180 x 0.08 = 14.4 sq ft, which is below the 25 sq ft floor, so 25 sq ft governs. Twenty square feet is the sunroom exception, which does not apply here.

      Reference: 2018 International Mechanical Code (IMC), Section 402.3

    5. Under 29 CFR 1926.57(b), how must a local exhaust ventilation system used to control construction dusts, fumes and vapors be designed with regard to the employees' work area?

      Answer: So the contaminants are not drawn through the work area of employees

      Section 1926.57(b) requires local exhaust ventilation to prevent dispersion of dusts, fumes, mists, vapors and gases in concentrations causing harmful exposure, and to be designed so these contaminants are not drawn through the work area of employees.

      Reference: 29 CFR Part 1926 (OSHA construction standards), 29 CFR 1926.57(b)

    6. Under 29 CFR 1926.57(g)(3)(ii), what recommended minimum duct velocities apply for exhaust systems serving grinding wheels on floor stands and benches?

      Answer: 4,500 feet per minute in the branch and 3,500 feet per minute in the main

      Section 1926.57(g)(3)(ii) gives not less than the minimum exhaust volumes in Table D-57.1 with a recommended minimum duct velocity of 4,500 feet per minute in the branch and 3,500 feet per minute in the main. The branch, which is closest to the hood, carries the higher velocity.

      Reference: 29 CFR Part 1926 (OSHA construction standards), 29 CFR 1926.57(g)(3)(ii)

    7. Under Table D-2 of 29 CFR 1926.52, what is the permissible sound level for an exposure duration of 4 hours per day?

      Answer: 95 dBA

      Table D-2 gives 90 dBA for 8 hours, 92 for 6 hours, 95 for 4 hours, 97 for 3 hours, 100 for 2 hours, 102 for 1-1/2 hours, 105 for 1 hour, 110 for 1/2 hour and 115 for 1/4 hour or less. When exposure exceeds the table, feasible controls come first, and then ear protection (1926.101).

      Reference: 29 CFR Part 1926 (OSHA construction standards), 29 CFR 1926.52, Table D-2

    8. A 2 hp exhaust fan motor draws 1,865 watts from the line while delivering its rated output. Using 1 hp = 746 W, what is the motor's efficiency?

      Answer: 80 percent

      Efficiency = output / input x 100. Output = 2 hp x 746 W/hp = 1,492 W, and 1,492 / 1,865 = 0.80, or 80 percent. Inverting the ratio gives 125 percent, which is impossible for a motor, and rounding 2 hp to 2,000 W gives 107 percent.

      Reference: DOE Fundamentals Handbook, Electrical Science (DOE-HDBK-1011/3-92), Module 10, AC Generators: Efficiency, Equation (10-3) (hp to watt conversion)

    9. A coil that behaves as a pure inductance of 0.05 henry is connected to a 60-hertz supply. Using X_L = 2 x pi x f x L with pi = 3.14, what is its inductive reactance?

      Answer: About 18.8 ohms

      Equation (8-2): X_L = 2 x 3.14 x 60 x 0.05 = 18.84 ohms. Leaving out the 2 pi gives 3.0 ohms (60 x 0.05), leaving out the 2 gives 9.4 ohms, and using 50 hertz gives 15.7 ohms.

      Reference: DOE Fundamentals Handbook, Electrical Science (DOE-HDBK-1011/3-92), Module 8, AC Reactive Components: Inductive Reactance, Equation (8-2)

    10. Which devices are commonly used as overload devices in magnetic motor controllers?

      Answer: Fuses, thermal overloads and magnetic overloads

      Overload devices in magnetic controllers protect the motor from harmful overcurrent. The text names fuses, thermal overloads and magnetic overloads as the types commonly used in motor-control equipment.

      Reference: DOE Fundamentals Handbook, Electrical Science (DOE-HDBK-1011/3-92), Module 15, Electrical Distribution Systems: Motor Controllers (overload devices)