Iowa licensing exam

Iowa Master Mechanical Exam: Practice Test & Licensing Guide

The Kirkwood exam for an Iowa master mechanical license with gas: 100 open-book questions in 4 hours on the 2024 IMC and 2024 NFPA 54. 75% to pass.

Questions
100
Time limit
4 hours
Passing score
75%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10General Requirements, Definitions, Testing

A building owner asks who is responsible for keeping an existing mechanical system in safe operating condition, and which edition governs the safeguards that were originally installed. Which answer matches Section 102.3?

Requirements at a glance

AgencyIowa Plumbing and Mechanical Systems Board (PMSB); exam by Kirkwood Community College
ExperienceA prior journeyperson license plus 2 years in the discipline, or a master license from another state
Exam100 questions, 4 hours, open book; 75% to pass
Books allowed2024 International Mechanical Code and 2024 NFPA 54 National Fuel Gas Code
Fees$119 to Kirkwood plus a $35 PMSB exam-candidate application per exam

Candidates with a prior journeyperson license plus 2 years in the discipline (or a master license elsewhere) applying to the Plumbing and Mechanical Systems Board.

How to get licensed, step by step

  1. Apply to the PMSB

    Submit the exam-candidate application and fee to the Plumbing and Mechanical Systems Board for approval.

    Iowa DIAL: plumbing and mechanical examination (opens in a new tab)

  2. Register with Kirkwood

    Register and pay Kirkwood for your exam, then test at one of about 16 Iowa community-college centers. Fees are non-refundable and non-transferable.

    Kirkwood: Iowa state discipline exams (opens in a new tab)

  3. Take the exam

    Bring your approved references and a battery-operated, non-programmable calculator. You need 75% to pass.

    Kirkwood: Iowa state discipline exams (opens in a new tab)

  4. Apply for your license

    After you pass, send the Board a post-examination licensure application. If you fail, register and pay for a new exam (Kirkwood, 319-398-1022).

    Iowa DIAL: plumbing and mechanical examination (opens in a new tab)

How to prepare

  • Kirkwood's outlines say questions are based on the listed edition, but you may bring any edition. Iowa adopted the 2024 UPC and 2024 IMC with amendments effective March 26, 2025.
  • Code books may be bound or loose-leaf. Photocopies, handwritten notes and sticky notes are not allowed; highlighting and permanent tabs are.
  • The exam is open book, so tab each chapter and practice finding answers fast.
  • The outline matches the journeyperson exam with 100 questions. Drill duct, combustion air, chimney and vent sizing and the NFPA 54 fuel gas tables.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2024 IMC and NFPA 54. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • 2024 International Mechanical Code (IMC), ICC, with Iowa amendments (481 IAC 426)
  • 2024 NFPA 54 National Fuel Gas Code

What's on the exam

Official content outline from Kirkwood Community College (number of questions per topic):

TopicQuestions
General Requirements, Definitions, Testing22
Heating, Refrigeration, and Hydronic Systems20
Exhaust and Ventilation Systems15
Duct Systems12
Combustion Air7
Chimneys and Vents14
Fuel Supply System10

Exam day details

  • Administered by Kirkwood Community College for the Iowa Plumbing and Mechanical Systems Board (PMSB).
  • Fee: $119 to Kirkwood per exam, plus a $35 PMSB exam-candidate application per exam. Exam fees are non-refundable and non-transferable.
  • 100 questions in 4 hours (Master Mechanical with Gas); 75% to pass. The topic mix is the same as the journeyperson exam.
  • Iowa adopted the 2024 IMC with amendments (481 IAC 426), effective March 26, 2025. For fuel gas the Iowa amendments refer to NFPA 54 and NFPA 58 (current edition) in place of the IFGC.
  • Open book: bring the references listed. Code books may be bound or loose-leaf; photocopies are not allowed. You may highlight and add permanent tabs before the exam, but handwritten notes in the books are not allowed and sticky notes are not accepted.
  • Exam questions are based on the listed edition, but the books you bring may be any edition.
  • You may bring an architect's scale or rule and a battery-operated, non-programmable calculator with no printing capability.
  • Kirkwood tests at about 16 Iowa community-college centers. Pass with 75%; then send the PMSB a post-examination licensure application. If you fail you must register and pay for a new exam.

Frequently asked questions

What's on the Iowa master mechanical exam?

100 questions: general requirements, definitions and testing 22%, heating, refrigeration and hydronic systems 20%, exhaust and ventilation 15%, chimneys and vents 14%, duct systems 12%, fuel supply 10% and combustion air 7%.

Which books are allowed?

The 2024 International Mechanical Code and the 2024 NFPA 54 National Fuel Gas Code. Any edition may be brought, but questions follow the 2024 editions.

Who can take the master exam?

Candidates with a prior journeyperson license plus 2 years in the discipline, or a master license from another state.

Free questions with answers

Show all 10 free questions and answers
  1. A building owner asks who is responsible for keeping an existing mechanical system in safe operating condition, and which edition governs the safeguards that were originally installed. Which answer matches Section 102.3?

    Answer: The owner or owner's agent maintains the system, and required devices and safeguards are kept in compliance with the edition under which they were installed

    Section 102.3 puts maintenance on the owner or the owner's authorized agent and says devices or safeguards required by the code are maintained in compliance with the edition under which they were installed. The code official may require a reinspection, and HVAC inspection for maintenance follows ASHRAE/ACCA/ANSI Standard 180.

    Reference: 2024 International Mechanical Code, Section 102.3

  2. A high-pressure steam boiler produces 7,500 pounds of steam per hour. Using Table 1004.3.1, what is the minimum clearance from the top of the boiler to the ceiling or other overhead obstruction?

    Answer: 7 feet

    Table 1004.3.1 sets 3 feet for high-pressure steam boilers with capacity up to 5,000 pounds per hour and 7 feet for those exceeding 5,000 pounds per hour. At 7,500 pounds per hour the 7-foot row governs, and it is greater than the 2- and 3-foot general rows.

    Reference: 2024 International Mechanical Code, Table 1004.3.1

  3. The design length of a radiant tubing circuit is 280 feet and the manufacturer lists no maximum. Under Section 1209.6, what is the allowable range of installed circuit length?

    Answer: 252 feet to 308 feet, a variance of not more than plus or minus 10 percent from the design

    Section 1209.6 says individual tubing circuit lengths are installed with a variance of not more than plus or minus 10 percent from the design. 0.10 x 280 = 28 ft, so the range is 280 - 28 = 252 ft to 280 + 28 = 308 ft. The 5 and 20 percent figures are not in the code.

    Reference: 2024 International Mechanical Code, Section 1209.6

  4. A 300 square foot interior room has no openings to the outdoors and is naturally ventilated through an adjoining room. What is the minimum unobstructed opening between the two rooms under Section 402.3?

    Answer: 25 square feet

    Section 402.3 sets the opening to the adjoining room at not less than 8 percent of the interior room's floor area but not less than 25 square feet. 0.08 x 300 = 24 sq ft, which is less than the 25 sq ft floor, so 25 square feet governs. 12 sq ft is 4 percent (the outdoor openable area rule in Section 402.2) and 20 sq ft is the sunroom exception minimum.

    Reference: 2024 International Mechanical Code, Section 402.3

  5. A room that requires mechanical exhaust is in an office suite (not Group R-3 or a Group R-2 dwelling unit). Which pressure condition does Section 501.4 require for that room?

    Answer: A neutral or negative pressure relative to adjoining spaces

    Section 501.4 requires a space that has mechanical exhaust required, other than Group R-3 and dwelling units in Group R-2, to be maintained at neutral or negative pressure, and requires adequate means to be provided where supply exceeds exhaust. The code gives no 0.10 inch w.c. figure.

    Reference: 2024 International Mechanical Code, Section 501.4

  6. A duct runs through the wall between an attached garage and a dwelling. What does Section 603.7 require?

    Answer: Continuous duct of sheet steel at least 0.0187 inch (No. 26 gage) with no openings into the garage

    Section 603.7 requires ducts in a private garage that penetrate a wall or ceiling separating a dwelling from the garage to be continuous, made of sheet steel not less than 0.0187 inch (No. 26 gage) and with no openings into the garage; fire and smoke dampers are not required in such ducts.

    Reference: 2024 International Mechanical Code, Section 603.7

  7. At what point must a connector enter a chimney flue under Section 801.12?

    Answer: Not less than 12 inches above the lowest portion of the interior of the flue

    Section 801.12 requires connectors to connect to a chimney flue at a point not less than 12 inches (305 mm) above the lowest portion of the interior of the chimney flue. This keeps the entrance above the debris and soot that collects at the base.

    Reference: 2024 International Mechanical Code, Section 801.12

  8. A mechanical draft system is to be added to a manually fired wood stove. Which combination does Section 804.3.8 require?

    Answer: A UL 378 draft device, a visible and audible failure warning, and a smoke detector in the room

    Section 804.3.8 permits mechanical draft on manually fired appliances and fireplaces if the draft device is listed to UL 378 and installed per its instructions, a device gives a visible and audible warning when the draft device fails or power is lost while it is on, and a smoke detector is installed in the room. The warning device and smoke detector each need battery backup if powered from building wiring.

    Reference: 2024 International Mechanical Code, Section 804.3.8

  9. Two spaces on different stories will share combustion air for appliances totaling 85,000 Btu/h. What total minimum free area of permanent openings in doors or floors connecting the two spaces is required?

    Answer: 170 square inches

    For spaces in different stories, the volumes are considered communicating where the permanent openings in doors or floors have a total minimum free area of 2 square inches per 1,000 Btu/h of total input: 2 x 85 = 170 sq in. 100 sq in is the same-story minimum (1 sq in per 1,000 Btu/h, at least 100 sq in each opening), and 85 sq in is the same-story rate without the 100 sq in minimum.

    Reference: NFPA 54 (2024), 9.3.2.3

  10. An outdoor purge discharge point is being selected for a gas main with a design operating pressure above 2 psig. Which minimum distances must be met under Section 8.3.1.3?

    Answer: 10 feet from ignition sources, 10 feet from building openings, and 25 feet from mechanical air intake openings

    Section 8.3.1.3 requires the point of discharge to be controlled with a shutoff valve and located at least 10 feet from sources of ignition, at least 10 feet from building openings and at least 25 feet from mechanical air intake openings.

    Reference: NFPA 54 (2024), 8.3.1.3

Sources

Questions last verified November 10, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.