Iowa Master Hydronics Exam: Practice Test & Licensing Guide

The Kirkwood exam for an Iowa master hydronics license with gas: 100 open-book questions in 4 hours on boilers, fuels, piping and controls. 75% to pass.

Questions
100
Time limit
4 hours
Passing score
75%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Piping, Pumps, Valving

A radiant floor system design calls for each tubing circuit to be 250 feet long. Under Section 1209.6, which installed circuit length falls outside the allowed variance?

Requirements at a glance

AgencyIowa Plumbing and Mechanical Systems Board (PMSB); exam by Kirkwood Community College
ExperienceA prior journeyperson license plus 2 years in the discipline, or a master license from another state
Exam100 questions, 4 hours, open book; 75% to pass
Books allowed2024 IMC, 2024 NFPA 54, Boiler Operator's Guide (4th ed.) and Steam Plant Operation (8th ed.)
Fees$119 to Kirkwood plus a $35 PMSB exam-candidate application per exam

Candidates with a prior journeyperson license plus 2 years in the discipline (or a master license elsewhere) applying to the Plumbing and Mechanical Systems Board.

How to get licensed, step by step

  1. Apply to the PMSB

    Submit the exam-candidate application and fee to the Plumbing and Mechanical Systems Board for approval.

    Iowa DIAL: plumbing and mechanical examination (opens in a new tab)

  2. Register with Kirkwood

    Register and pay Kirkwood for your exam, then test at one of about 16 Iowa community-college centers. Fees are non-refundable and non-transferable.

    Kirkwood: Iowa state discipline exams (opens in a new tab)

  3. Take the exam

    Bring your approved references and a battery-operated, non-programmable calculator. You need 75% to pass.

    Kirkwood: Iowa state discipline exams (opens in a new tab)

  4. Apply for your license

    After you pass, send the Board a post-examination licensure application. If you fail, register and pay for a new exam (Kirkwood, 319-398-1022).

    Iowa DIAL: plumbing and mechanical examination (opens in a new tab)

How to prepare

  • Kirkwood's outlines say questions are based on the listed edition, but you may bring any edition. Iowa adopted the 2024 UPC and 2024 IMC with amendments effective March 26, 2025.
  • Code books may be bound or loose-leaf. Photocopies, handwritten notes and sticky notes are not allowed; highlighting and permanent tabs are.
  • The exam is open book, so tab each chapter and practice finding answers fast.
  • Controls and control systems and maintenance and repairs are 15% each. The master exam adds startup and shutdown (6%) and turbines (5%) sections.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2024 IMC and NFPA 54 and the Boiler Operator's Guide and Steam Plant Operation. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • 2024 International Mechanical Code (IMC), ICC, with Iowa amendments (481 IAC 426)
  • 2024 NFPA 54 National Fuel Gas Code
  • Boiler Operator's Guide, 4th edition
  • Steam Plant Operation, 8th edition

What's on the exam

Official content outline from Kirkwood Community College (number of questions per topic):

TopicQuestions
Water Treatment and Feed6
Fuels and Firing Methods14
General Code10
Startup and Shutdown6
Piping, Pumps, Valving10
Controls and Control Systems15
Maintenance and Repairs15
Tests and Inspections9
Refrigeration10
Turbines5

Exam day details

  • Administered by Kirkwood Community College for the Iowa Plumbing and Mechanical Systems Board (PMSB).
  • Fee: $119 to Kirkwood per exam, plus a $35 PMSB exam-candidate application per exam. Exam fees are non-refundable and non-transferable.
  • 100 questions in 4 hours (Master Hydronics with Gas); 75% to pass.
  • Iowa adopted the 2024 IMC with amendments (481 IAC 426), effective March 26, 2025; fuel gas references are NFPA 54 and NFPA 58 (current edition).
  • Open book: bring the references listed. Code books may be bound or loose-leaf; photocopies are not allowed. You may highlight and add permanent tabs before the exam, but handwritten notes in the books are not allowed and sticky notes are not accepted.
  • Exam questions are based on the listed edition, but the books you bring may be any edition.
  • You may bring an architect's scale or rule and a battery-operated, non-programmable calculator with no printing capability.
  • Kirkwood tests at about 16 Iowa community-college centers. Pass with 75%; then send the PMSB a post-examination licensure application. If you fail you must register and pay for a new exam.

Frequently asked questions

What's on the Iowa master hydronics exam?

100 questions: controls and control systems 15%, maintenance and repairs 15%, fuels and firing methods 14%, general code 10%, piping, pumps and valving 10%, refrigeration 10%, tests and inspections 9%, water treatment and feed 6%, startup and shutdown 6% and turbines 5%.

Which books are allowed?

The 2024 IMC, 2024 NFPA 54, Boiler Operator's Guide (4th edition) and Steam Plant Operation (8th edition).

Who can take the master exam?

Candidates with a prior journeyperson license plus 2 years in the discipline, or a master license from another state.

Free questions with answers

Show all 10 free questions and answers
  1. A radiant floor system design calls for each tubing circuit to be 250 feet long. Under Section 1209.6, which installed circuit length falls outside the allowed variance?

    Answer: 279 feet

    Section 1209.6 allows individual radiant tubing circuits to vary from the design length by no more than plus or minus 10 percent. 10 percent of 250 ft is 25 ft, so the allowed range is 250 - 25 = 225 ft to 250 + 25 = 275 ft. 279 ft is 4 ft over the limit; 228, 262 and 274 ft all fall inside the range.

    Reference: 2024 International Mechanical Code, Section 1209.6

  2. A steam boiler has a primary low-water cutoff and a second, auxiliary low-water cutoff with a manual reset set slightly lower. What happens if the water level falls to the auxiliary cutoff's setting?

    Answer: The burner shuts down and stays locked out until manually reset

    The auxiliary low-water cutoff is a backup in case the primary cutoff fails. Because water has fallen below the primary's setting, it shuts the burner off and locks out, so an operator must find the cause and reset it by hand before firing again. An automatic restart would hide the failed primary control, and the safety valve responds to pressure, not water level.

    Reference: Boiler Operator's Guide, 4th Edition, Concept: boiler connections, appurtenances and controls, primary and auxiliary low-water cutoffs

  3. Only one new branch is added to an existing gas piping system to serve a new boiler. What does NFPA 54 require for testing?

    Answer: Pressure test the new branch only and leak test its connection to the existing piping

    NFPA 54 8.1.1.5 requires only the newly installed branches to be pressure tested, and 8.1.1.6 requires the connections between the new piping and the existing piping to be tested with a noncorrosive leak-detecting fluid or other approved methods. The whole existing system need not be retested.

    Reference: NFPA 54 (2024), Sections 8.1.1.5 and 8.1.1.6

  4. A machinery room is 40 feet by 30 feet and is occupied by 3 workers. Using the larger of the two normal-ventilation quantities in Section 1105.6.3.1 (0.5 cfm per square foot or 20 cfm per person), what is the minimum normal exhaust rate, ignoring the temperature-rise option?

    Answer: 600 cfm

    Section 1105.6.3.1 requires the larger of 0.5 cfm per square foot of room area or 20 cfm per person. Area: 40 x 30 = 1,200 sq ft, and 0.5 x 1,200 = 600 cfm. People: 3 x 20 = 60 cfm. The larger value, 600 cfm, governs; 1,200 cfm would result from using 1 cfm per square foot.

    Reference: 2024 International Mechanical Code, Section 1105.6.3.1

  5. Appliances with a combined input of 600,000 Btu/h get all combustion air through two permanent openings that connect directly to the outdoors. What is the minimum free area of each opening?

    Answer: 150 square inches

    For two permanent openings communicating directly with the outdoors, or through vertical ducts, each opening must have at least 1 square inch per 4,000 Btu/h of total input. Calculation: 600,000 / 4,000 = 150 square inches each. With horizontal ducts the ratio is 1 in 2,000 and each opening would be 300.

    Reference: NFPA 54 (2024), Section 9.3.3.1

  6. A steam boiler produces 10,000 lb/h of steam. Feedwater has 100 ppm total dissolved solids, and the boiler water must stay at or below 2,000 ppm. Using blowdown = steam x feed TDS / (boiler TDS - feed TDS), what blowdown rate is required?

    Answer: About 526 lb/h

    Blowdown = 10,000 x 100 / (2,000 - 100) = 1,000,000 / 1,900 = 526 lb/h. Taking 5 percent of steam gives 500 lb/h, which ignores that blowdown also leaves the feed stream. Doubling the ratio or confusing ppm with percent gives the larger values.

    Reference: Boiler Operator's Guide, 4th Edition, Concept: boiler blowdown, cycles of concentration and total dissolved solids

  7. When filling and starting a cold steam boiler, what should the operator confirm in the gauge glass before the burner is fired?

    Answer: The water level is at the normal operating level and visible in the glass

    Before firing, the operator confirms that the water level in the gauge glass is at the normal operating level, with the column blown down so the glass reads true. Firing with the level too low risks overheating the tubes, and a flooded boiler may carry water into the steam line.

    Reference: Steam Plant Operation, 8th Edition, Concept: preparing a steam boiler for firing

  8. What is the primary job of the governor on a steam turbine?

    Answer: To hold the turbine at the required speed by regulating steam flow

    The governor senses turbine speed and adjusts the steam admission valve to keep speed at the setting despite changes in load. A separate overspeed trip is a safety device, not the governor, and shuts off steam if speed rises dangerously.

    Reference: Steam Plant Operation, 8th Edition, Concept: steam turbine governor and speed control

  9. Which condition must a refrigeration system be kept free of under Section 1101.6?

    Answer: Accumulations of oil, dirt, waste, excessive corrosion, debris and leaks

    Section 1101.6 requires refrigeration systems to be maintained in proper operating condition, free from accumulations of oil, dirt, waste, excessive corrosion and other debris, and free from leaks. It places the duty on keeping the existing system sound, not on equipment age.

    Reference: 2024 International Mechanical Code, Section 1101.6

  10. Which pressure vessel is outside the scope of IMC Chapter 10 under Section 1001.1?

    Answer: An unfired vessel of 4 cubic feet operating at 200 psi in a Group B building

    Section 1001.1 excepts unfired pressure vessels of 5 cubic feet or less operating at no more than 250 psi located in occupancy Groups B, F, H, M, R, S and U. The 8 cubic foot vessel is too large, and the 300 psi vessel exceeds the pressure limit. Directly fired vessels fall under Section 1004.

    Reference: 2024 International Mechanical Code, Section 1001.1, Exceptions