Iowa Master Electrician Exam: Practice Test & Licensing Guide

The PSI exam for an Iowa master electrician license: 100 scored open-book questions in 240 minutes on the 2023 NEC. 70% to pass.

Questions
100
Time limit
4 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Wiring and Protection

A 3-phase feeder carries 84 A of continuous load and 36 A of noncontinuous load. All terminations are rated 75 degrees C and the conductors are copper with no ampacity adjustment or correction. Using Table 310.16, what is the smallest conductor that may be used?

Requirements at a glance

AgencyIowa Electrical Examining Board (Dept. of Inspections, Appeals, & Licensing); exam by PSI
ExperienceClass A: one year of experience as a licensed journeyman electrician (481 IAC 401.2(3))
Exam100 scored questions, 240 minutes, open book; 70% to pass
Books allowedOpen book: NFPA 70 (2023) or NEC Handbook 2023, permanent tabs only; Ugly's not allowed
Fees$87 to PSI per exam (valid 6 months); license fee due after you pass

Licensed journeyman electricians with at least one year of experience as a journeyman, applying to the Iowa Electrical Examining Board for a class A master license, including those who will qualify an electrical contractor license (481 IAC 401.2(3)).

How to get licensed, step by step

  1. Apply to the Board

    Send the license application and a Testing Sponsorship Request to the Electrical Examining Board. No license application is needed if you already hold one.

    Iowa Electrical Examining Board (opens in a new tab)

  2. Get your authorization letter

    When the Board approves you it sends an authorization to test, valid for two exam attempts or six months.

    Iowa Electrical Examining Board (opens in a new tab)

  3. Pay and schedule with PSI

    Register with PSI, pay the $87 fee and pick one of the four Iowa centers or any other PSI site. Cancel at least 2 days ahead to keep your fee.

    PSI: Iowa electrical exam registration (opens in a new tab)

  4. Pass and get licensed

    You need 70%. After you pass, contact the Board for instructions and pay the license fee.

    Iowa Electrical Examining Board (opens in a new tab)

How to prepare

  • Iowa adopted the 2023 NEC effective July 1, 2025 (DIAL says unamended). The PSI exam references the 2023 NEC; bring NFPA 70 or the NEC Handbook, 2023. Ugly's is not allowed.
  • The PSI outline covers NEC topics only, with no Iowa-law section, so practice NEC lookups and trade math rather than state statutes.
  • Allowed: highlighting, underlining and permanent tabs. Not allowed: writing in the book, sticky notes or loose papers. PSI also gives you an on-screen calculator.
  • The master exam adds a communication systems section (5%). Expect more calculation and service-sizing items than the journeyman exam.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (NEC), 2023 edition, or the 2023 NEC Handbook (allowed in the exam room; Ugly's is not)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
General Electrical Knowledge10
Wiring and Protection25
Wiring Methods and Materials20
Equipment for General Use20
Special Occupancies10
Special Equipment5
Special Conditions5
Communication Systems5

Exam day details

  • Administered by PSI Services for the Iowa Electrical Examining Board.
  • Fee: $87 to PSI per exam; not refundable or transferable and valid for 6 months. The Board's license application and license fees are separate.
  • 100 scored questions plus 10 unscored items in 240 minutes (plus 30 minutes for the unscored items); 70% correct to pass.
  • Open book: bring your own NFPA 70 (2023) or the 2023 NEC Handbook. Ugly's Electrical References is NOT allowed. You may highlight, underline and index with permanent tabs, but not write in the book; sticky notes are removed.
  • PSI also gives you an on-screen calculator; you may bring a silent, battery-operated, non-programmable calculator with no paper tape.
  • Send the Board your license application and a Testing Sponsorship Request. When it approves you, you get an authorization letter valid for 2 exam attempts or 6 months; then you pay and schedule with PSI. After two failures, contact the Board for a new letter.
  • PSI tests at four Iowa centers and any other PSI site. The license fee is due after you pass.

Frequently asked questions

What's on the Iowa master electrician exam?

100 scored questions: wiring and protection 25, wiring methods and materials 20, equipment for general use 20, general electrical knowledge 10, special occupancies 10, special equipment 5, special conditions 5 and communication systems 5.

Is the exam open book?

Yes, with NFPA 70 (2023) or the 2023 NEC Handbook and permanent tabs only. Ugly's is not allowed.

Does Iowa have a separate contractor exam?

No. Electrical contractor licenses require a master license or an employed master electrician; there is no separate contractor trade exam.

Free questions with answers

Show all 10 free questions and answers
  1. A 3-phase feeder carries 84 A of continuous load and 36 A of noncontinuous load. All terminations are rated 75 degrees C and the conductors are copper with no ampacity adjustment or correction. Using Table 310.16, what is the smallest conductor that may be used?

    Answer: 1/0 AWG

    Feeder conductors must carry the noncontinuous load plus 125 percent of the continuous load: 36 + (84 x 1.25) = 36 + 105 = 141 A. In the 75 degree C copper column of Table 310.16, 2 AWG is 115 A and 1 AWG is 130 A, both too small; 1/0 AWG is 150 A. Adding the loads without the 125 percent factor gives 120 A, which tempts you to 1 AWG. 2/0 AWG (175 A) is larger than necessary.

    Reference: NFPA 70, National Electrical Code, 2023, 215.2(A)(1) and Table 310.16

  2. A device box contains three 12-2 NM cables with ground (each enters through an internal cable clamp), one duplex receptacle on a single yoke, and one short 12 AWG pigtail that is spliced to the circuit conductors and does not leave the box. What minimum box volume is required? Use Table 314.16(B)(1).

    Answer: 22.5 cu in.

    Each 12 AWG allowance is 2.25 cu in. Count: six insulated conductors from the three cables = 6; the three equipment grounding conductors together = 1 (up to four share one allowance); the internal clamps = 1 (based on the largest conductor); the receptacle yoke = 2. The pigtail is not counted because no part of it leaves the box. Total 10 x 2.25 = 22.5 cu in. 20.25 omits either the clamp or the double yoke allowance, 24.75 counts the pigtail, and 27.0 counts each grounding conductor separately.

    Reference: NFPA 70, National Electrical Code, 2023, 314.16(B)(1) through (B)(5) and Table 314.16(B)(1)

  3. A straight pull through a junction box is made with a 4 in. conduit carrying 250 kcmil conductors. What is the minimum length of the box?

    Answer: 32 in.

    For conductors 4 AWG and larger, the box length in a straight pull must be at least eight times the trade size of the largest raceway: 8 x 4 = 32 in. Six times (24 in.) is the angle-pull multiplier, and the other values do not follow from the rule.

    Reference: NFPA 70, National Electrical Code, 2023, 314.28(A)(1)

  4. A 25-hp, 460-V, 3-phase squirrel-cage induction motor drives a pump. The branch-circuit conductors are copper, all terminations are rated 75 degrees C, and no correction or adjustment factors apply. What is the smallest conductor permitted?

    Answer: 8 AWG

    Use the full-load current from Table 430.250, not the nameplate: 25 hp at 460 V = 34 A. Branch-circuit conductors for a single continuous-duty motor must carry at least 125 percent of that value: 34 x 1.25 = 42.5 A. In the 75 degree C copper column, 10 AWG is 35 A (too small) and 8 AWG is 50 A. 6 AWG (65 A) is larger than needed.

    Reference: NFPA 70, National Electrical Code, 2023, 430.6(A)(1), 430.22(A), Table 430.250 and Table 310.16

  5. From the closet floor up to a height of 6 ft or the highest clothes-hanging rod, how far horizontally from the side and back walls does the clothes closet storage space extend?

    Answer: 24 in.

    Clothes closet storage space is the volume bounded by the side and back walls and planes extending up from the floor to 6 ft or the highest hanging rod and parallel to the walls at 24 in. horizontal distance. Along the shelf the volume extends 12 in. (or the shelf width, if greater) up to the ceiling. Only certain luminaire types are permitted in a clothes closet and pendants and open-lamp incandescent luminaires are not.

    Reference: NFPA 70, National Electrical Code, 2023, 410.16(A)

  6. Two explosionproof enclosures in a Class I, Division 1 location both require conduit seals and are joined by a conduit nipple. What is the maximum nipple length for which a single seal in the nipple is sufficient?

    Answer: 36 in.

    501.15(A)(3) allows one conduit seal in a nipple or run of conduit not more than 36 in. long connecting two or more explosionproof enclosures that require seals, provided the seal is not more than 18 in. from either enclosure. 18 in. is the seal-to-enclosure distance, not the nipple length. Longer runs need a seal at each enclosure.

    Reference: NFPA 70, National Electrical Code, 2023, 501.15(A)(3)

  7. The required general-purpose receptacle for a permanently installed pool must be located not more than what height above the floor, platform or grade level serving the pool?

    Answer: 6 ft 6 in.

    680.22(A)(1) requires at least one 125-V, 15- or 20-A general-purpose receptacle located not less than 6 ft and not more than 20 ft from the inside wall of the pool, and not more than 6 ft 6 in. above the floor, platform or grade level serving the pool. 6 ft is the minimum horizontal distance from the pool wall, not a height limit.

    Reference: NFPA 70, National Electrical Code, 2023, 680.22(A)(1)

  8. Storage batteries supply the emergency illumination in an office building. For at least how long must they maintain the total load without the voltage at the load falling below 87-1/2 percent of nominal?

    Answer: 1-1/2 hours

    700.12(C)(4) requires storage batteries and UPS that supply emergency illumination to carry the total load for at least 1-1/2 hours without the load voltage dropping below 87-1/2 percent of nominal; automotive-type batteries are not allowed and an automatic charger is required. 2 hours is the general minimum supply duration of 700.12(C) and the on-site fuel requirement for generators, which does not apply to battery-supplied emergency illumination. 1 hour is too short.

    Reference: NFPA 70, National Electrical Code, 2023, 700.12(C)(4)

  9. What is the smallest bonding conductor or grounding electrode conductor permitted for a communications primary protector?

    Answer: 14 AWG

    800.100(A)(3) requires the protector bonding conductor or grounding electrode conductor to be not smaller than 14 AWG, with a current-carrying capacity at least equal to the cable sheath, strength members and protected conductors. It is not required to exceed 6 AWG, so 6 AWG is the upper limit of what can be required, not the minimum. 12 AWG and 10 AWG are not values in the rule.

    Reference: NFPA 70, National Electrical Code, 2023, 800.100(A)(3)

  10. A 120-V branch circuit uses 12 AWG solid uncoated copper (1.93 ohms per 1000 ft at 75 degrees C, Chapter 9 Table 8) for a 100 ft one-way run and carries 16 A. What is the approximate voltage drop?

    Answer: 6.2 V

    The current travels out and back, so the circuit length is 200 ft. R = 1.93 x 200 / 1000 = 0.386 ohm and VD = 16 x 0.386 = 6.2 V, about 5.1 percent of 120 V, more than the 3 percent suggested for branch circuits. 3.1 V uses only the one-way length, and 12.4 V counts the round trip twice.

    Reference: NFPA 70, National Electrical Code, 2023, Chapter 9, Table 8 and 210.19 Informational Note