Iowa licensing exam

Iowa Disconnect/Reconnect A/C and Refrigeration Exam: Practice Test & Licensing Guide

The PSI exam for the Iowa disconnect/reconnect air conditioning and refrigeration electrical license: 50 scored open-book questions in 120 minutes on the 2023 NEC. 70% to pass.

Questions
50
Time limit
2 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Motors and Controls

A single-phase condensing unit has one hermetic compressor with a nameplate rated-load current of 18.4 A and no branch-circuit selection current. What is the minimum ampacity of the branch-circuit conductors under Section 440.32?

Requirements at a glance

AgencyIowa Electrical Examining Board (Dept. of Inspections, Appeals, & Licensing); exam by PSI
ExperienceSpecial electrician Endorsement 2: pass this exam or document two years of disconnecting and reconnecting existing A/C and refrigeration systems (481 IAC 401.2(9))
Exam50 scored questions, 120 minutes, open book; 70% to pass
Books allowedOpen book: NFPA 70 (2023) or NEC Handbook 2023, permanent tabs only; Ugly's not allowed
Fees$87 to PSI per exam (valid 6 months); license fee due after you pass

HVAC and refrigeration workers seeking the Disconnecting and Reconnecting Existing Air Conditioning and Refrigeration Systems endorsement (Endorsement 2) on an Iowa special electrician license. You qualify by passing this exam or by documenting two years of that work (481 IAC 401.2(9)).

How to get licensed, step by step

  1. Apply to the Board

    Send the license application and a Testing Sponsorship Request to the Electrical Examining Board. No license application is needed if you already hold one.

    Iowa Electrical Examining Board (opens in a new tab)

  2. Get your authorization letter

    When the Board approves you it sends an authorization to test, valid for two exam attempts or six months.

    Iowa Electrical Examining Board (opens in a new tab)

  3. Pay and schedule with PSI

    Register with PSI, pay the $87 fee and pick one of the four Iowa centers or any other PSI site. Cancel at least 2 days ahead to keep your fee.

    PSI: Iowa electrical exam registration (opens in a new tab)

  4. Pass and get licensed

    You need 70%. After you pass, contact the Board for instructions and pay the license fee.

    Iowa Electrical Examining Board (opens in a new tab)

How to prepare

  • Iowa adopted the 2023 NEC effective July 1, 2025 (DIAL says unamended). The PSI exam references the 2023 NEC; bring NFPA 70 or the NEC Handbook, 2023. Ugly's is not allowed.
  • The PSI outline covers NEC topics only, with no Iowa-law section, so practice NEC lookups and trade math rather than state statutes.
  • Allowed: highlighting, underlining and permanent tabs. Not allowed: writing in the book, sticky notes or loose papers. PSI also gives you an on-screen calculator.
  • Motors and controls is 30% of the exam. Drill NEC Article 430 and 440 (motor and air-conditioning equipment) sizing, disconnecting means and overload protection, then conductors and raceways.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (NEC), 2023 edition, or the 2023 NEC Handbook (allowed in the exam room; Ugly's is not)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
General Knowledge10
Feeders and Branch Circuits10
Grounding and Bonding10
Raceways and Enclosures14
Conductors18
Motors and Controls30
Special Occupancies8

The outline totals 100; the other items on the 50-question exam are unscored or unassigned.

Exam day details

  • Administered by PSI Services for the Iowa Electrical Examining Board.
  • Fee: $87 to PSI per exam; not refundable or transferable and valid for 6 months. The Board's license application and license fees are separate.
  • 50 scored questions plus 5 unscored items in 120 minutes (plus 15 minutes for the unscored items); 70% correct to pass.
  • Open book: bring your own NFPA 70 (2023) or the 2023 NEC Handbook. Ugly's Electrical References is NOT allowed. You may highlight, underline and index with permanent tabs, but not write in the book; sticky notes are removed.
  • PSI also gives you an on-screen calculator; you may bring a silent, battery-operated, non-programmable calculator with no paper tape.
  • Send the Board your license application and a Testing Sponsorship Request. When it approves you, you get an authorization letter valid for 2 exam attempts or 6 months; then you pay and schedule with PSI. After two failures, contact the Board for a new letter.
  • PSI tests at four Iowa centers and any other PSI site. The license fee is due after you pass.

Frequently asked questions

What's on the Iowa disconnect/reconnect exam?

50 scored questions: motors and controls 30, conductors 18, raceways and enclosures 14, general knowledge, feeders and branch circuits and grounding and bonding 10 each, and special occupancies 8.

Is the exam open book?

Yes, with NFPA 70 (2023) or the 2023 NEC Handbook. Ugly's is not allowed.

How much does the exam cost?

$87 to PSI, valid for six months and not refundable.

Free questions with answers

Show all 10 free questions and answers
  1. A single-phase condensing unit has one hermetic compressor with a nameplate rated-load current of 18.4 A and no branch-circuit selection current. What is the minimum ampacity of the branch-circuit conductors under Section 440.32?

    Answer: 23.0 A

    Section 440.32 requires conductors to carry at least 125 percent of the rated-load current (or branch-circuit selection current, whichever is greater). 18.4 x 1.25 = 23.0 A. 18.4 A omits the 125 percent factor, 21.2 A applies 115 percent (the disconnect factor in 440.12), and 32.2 A applies 175 percent, which is the protective-device limit in 440.22(A), not the conductor rule.

    Reference: NFPA 70, National Electrical Code, 2023 Edition, 440.32

  2. What is the ampacity of 3 AWG copper THWN conductors (75 degrees C column) in a raceway with no more than three current-carrying conductors at 30 degrees C ambient, per Table 310.16?

    Answer: 100 A

    Table 310.16 lists 3 AWG copper at 85 A in the 60 degrees C column, 100 A in the 75 degrees C column (THWN) and 115 A in the 90 degrees C column (THHN, THWN-2). Read the column for the insulation and terminal rating being used; 110 A is the 1 AWG value at 60 degrees C.

    Reference: NFPA 70, National Electrical Code, 2023 Edition, Table 310.16

  3. Five current-carrying 8 AWG THHN copper conductors are installed in a conduit at 30 degrees C and terminate on 75 degrees C rated equipment terminals. The 90 degrees C ampacity of 8 AWG is 55 A and the 75 degrees C ampacity is 50 A. What is the maximum allowable ampacity for the load?

    Answer: 44 A

    Five current-carrying conductors take the 80 percent factor of Table 310.15(C)(1), applied to the 90 degrees C value: 55 x 0.80 = 44 A. The result may not exceed the termination limit (50 A at 75 degrees C), and 44 A is lower, so 44 A governs. 50 A and 55 A ignore the adjustment; 40 A is the 60 degrees C value, which is not required here since the terminals are rated 75 degrees C.

    Reference: NFPA 70, National Electrical Code, 2023 Edition, Table 310.15(C)(1); 110.14(C)(1)

  4. A 1-in. liquidtight flexible metal conduit (LFMC) whip connects a vibrating compressor to a disconnect. Flexibility is necessary after installation. Under Section 350.30, what is the maximum length from the last point where the raceway is securely fastened?

    Answer: 3 ft

    Exception No. 2 to 350.30(A) allows unsupported lengths up to 900 mm (3 ft) for trade sizes 1/2 through 1-1/4 where flexibility is needed after installation, 4 ft for 1-1/2 and 2 in., and 5 ft for 2-1/2 in. and larger. The 12 in. figure is the distance to the box in the general rule.

    Reference: NFPA 70, National Electrical Code, 2023 Edition, 350.30(A), Exception No. 2

  5. A pull box contains a straight pull of 3 AWG conductors in a 2-1/2-in. conduit. Under Section 314.28(A)(1), what is the minimum length of the box?

    Answer: 20 in.

    For straight pulls with conductors 4 AWG or larger, the length of the box must be at least eight times the trade size of the largest raceway: 8 x 2.5 = 20 in. 15 in. is six times 2.5 (the angle-pull factor), 16 in. is eight times a 2-in. conduit, and 12.5 in. is five times the trade size.

    Reference: NFPA 70, National Electrical Code, 2023 Edition, 314.28(A)(1)

  6. What is the minimum size copper equipment grounding conductor for a circuit protected by a 60-A overcurrent device, according to Table 250.122?

    Answer: 10 AWG

    Table 250.122 lists 10 AWG copper for devices rated up to 60 A, 12 AWG for up to 20 A, 8 AWG for up to 100 A and 6 AWG for up to 200 A. Use the rating or setting of the overcurrent device ahead of the equipment, not the conductor ampacity.

    Reference: NFPA 70, National Electrical Code, 2023 Edition, Table 250.122

  7. What is the minimum height of the clear working space in front of electrical equipment that is 4 ft tall, under Section 110.26(A)(3)?

    Answer: 6 1/2 ft

    110.26(A)(3) requires the working space to extend from the floor or platform to a height of 2.0 m (6 1/2 ft) or the height of the equipment, whichever is greater. The equipment here is only 4 ft tall, so 6 1/2 ft governs.

    Reference: NFPA 70, National Electrical Code, 2023 Edition, 110.26(A)(3)

  8. A branch circuit supplies a 24-A noncontinuous load and a 16-A continuous load. What is the minimum branch-circuit conductor ampacity under Section 210.19(A)(1)?

    Answer: 44 A

    210.19(A)(1) requires the noncontinuous load plus 125 percent of the continuous load: 24 + (16 x 1.25) = 24 + 20 = 44 A. 40 A is the straight sum of 24 and 16. 50 A applies 125 percent to both (40 x 1.25 = 50). 46 A applies 125 percent to the noncontinuous load only: (24 x 1.25) + 16 = 46 A.

    Reference: NFPA 70, National Electrical Code, 2023 Edition, 210.19(A)(1)

  9. A Class I location surrounds a commercial garage's fuel-dispensing area. How far does the classified area extend through a solid wall that has no openings, according to Section 511.3?

    Answer: Not beyond the unpierced wall

    511.3 states that a Class I location does not extend beyond an unpierced wall, roof or other solid partition that has no openings. An opening, such as a duct or door, can allow classification to continue through the barrier.

    Reference: NFPA 70, National Electrical Code, 2023 Edition, 511.3

  10. A new air handler and its supply duct are planned directly above an indoor motor control panel in a mechanical room, within 6 ft of the top of the panel. What is the issue under Section 110.26(E)(1)(a)?

    Answer: Ducts are foreign equipment and may not occupy the dedicated space

    110.26(E)(1)(a) reserves a dedicated space the width and depth of the equipment, extending from the floor to 6 ft above the equipment or to the structural ceiling, whichever is lower. Piping, ducts, leak protection apparatus and other foreign equipment may not be in that zone. Foreign systems may be above the zone if protection prevents damage from leaks or condensation (110.26(E)(1)(b)). Insulation or drip pans do not make the zone legal.

    Reference: NFPA 70, National Electrical Code, 2023 Edition, 110.26(E)(1)(a)