Idaho licensing exam

Idaho Limited Electrical Refrigeration, Heating and Air Conditioning Installer Exam: Practice Test & Licensing Guide

Idaho's limited electrical refrigeration, heating and air conditioning (RHA) installer exam, given by PSI: 45 NEC questions, mostly equipment for general use and wiring and protection. Open book, 2 hours, 70% to pass.

Questions
45
Time limit
2 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10NEC Article 90: Introduction

Under Article 90, a Code rule that uses the term 'shall' or 'shall not' is a:

Requirements at a glance

AgencyIdaho Division of Occupational and Professional Licenses (DOPL); exam by PSI
Exam45 questions, 2 hours, 70% to pass
Books allowed2020 or 2023 NEC (or NEC Handbook) and Ugly's Electrical References (any edition)
Fees$75 per exam to PSI, plus DOPL license application fees

Installers applying to Idaho DOPL for a limited electrical installer license in refrigeration, heating and air conditioning work.

How to get licensed, step by step

  1. Check your experience

    Make sure you meet DOPL's requirements for the Limited Electrical Refrigeration, Heating and Air Conditioning Installer license before you test; you prove them when you apply.

    DOPL: electrical program information and exams (opens in a new tab)

  2. Register and pay with PSI

    Create a PSI account, pick the Idaho Limited Electrical Refrigeration, Heating and Air Conditioning Installer exam and pay the $75 fee, then schedule a seat at a PSI center. The fee is good for one year.

    Schedule with PSI (Idaho contractor and trade exams) (opens in a new tab)

  3. Pass the exam

    Bring your tabbed references and score 70% or higher.

    Schedule with PSI (Idaho contractor and trade exams) (opens in a new tab)

  4. Apply to DOPL

    After you pass, apply through eDOPL for the Limited Electrical Refrigeration, Heating and Air Conditioning Installer license.

    DOPL online license application (eDOPL) (opens in a new tab)

How to prepare

  • Bring your own 2020 or 2023 NEC (or NEC Handbook) and Ugly's (any edition). The PSI outline is labeled by 2017 NEC chapter, so focus on rules that read the same in each edition.
  • Tab your books before exam day with permanent tabs. You can highlight and underline, but not write in them; sticky notes are removed.
  • Chapter 4 equipment for general use is 16 of 45 questions: tab Article 440 (air-conditioning and refrigerating equipment), 430 (motors) and 422 and 424 (appliances and space heating).
  • Chapter 2 wiring and protection is 10, and Chapter 7 special conditions (including Class 1, 2 and 3 control circuits) is 7.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (NEC) or NEC Handbook, 2020 or 2023 Edition
  • Ugly's Electrical References (any edition)
  • Optional: Ferm's Fast Finder Index or Tom Henry's Key Word Index (2020 and 2023 editions)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
NEC Article 90: Introduction2
NEC Chapter 1: General3
NEC Chapter 2: Wiring and Protection10
NEC Chapter 3: Wiring Methods and Materials6
NEC Chapter 4: Equipment for General Use16
NEC Chapter 7: Special Conditions7
NEC Calculations1

Exam day details

  • Administered by PSI Services for the Idaho Division of Occupational and Professional Licenses (DOPL).
  • Fee: $75 per exam, paid to PSI when you schedule. The fee is good for one year, isn't refundable, and each retake costs it again. DOPL license application fees are separate.
  • 45 questions in 2 hours; 70% to pass.
  • Open book: bring your own 2020 or 2023 NEC (or NEC Handbook) and Ugly's Electrical References (any edition). The PSI outline lists its topics by 2017 NEC chapter; the chapters are the same in the 2020 and 2023 editions, though some articles and section numbers changed.
  • Pass the exam with PSI first, then apply to DOPL for the limited license. Book online at PSI; no DOPL approval is needed to sit.
  • You may highlight, underline and add permanent tabs to your references, but not write in them. Sticky notes and loose papers aren't allowed.
  • Your score shows on screen when you finish.
  • Cancel or reschedule at least 2 days before your appointment to keep your fee.

Frequently asked questions

What's on the Idaho RHA installer exam?

Per DOPL's December 2025 PSI bulletin, 45 NEC questions: Chapter 4 equipment for general use 16, Chapter 2 wiring and protection 10, Chapter 7 special conditions 7, Chapter 3 wiring methods 6, Chapter 1 3, the introduction (Article 90) 2 and 1 calculation.

Which NEC edition do I bring?

DOPL's December 2025 PSI bulletin allows the 2020 or 2023 NEC (or the NEC Handbook) plus Ugly's Electrical References (any edition). The outline itself is labeled by 2017 NEC chapter, so focus on rules that read the same in every edition.

Free questions with answers

Show all 10 free questions and answers
  1. Under Article 90, a Code rule that uses the term 'shall' or 'shall not' is a:

    Answer: Mandatory rule

    90.5(A) says mandatory rules identify actions that are specifically required or prohibited and are characterized by 'shall' or 'shall not'. Permissive rules (90.5(B)) use 'shall be permitted' or 'shall not be required', and informational notes (90.5(C)) are not enforceable. Same in 2017, 2020 and 2023.

    Reference: NFPA 70, National Electrical Code, 2023, 90.5(A)

  2. A 120/240-volt single-phase panelboard feeding a furnace and air handler is mounted facing a grounded concrete wall. What is the minimum depth of working space in front of it?

    Answer: 3 ft

    The panel's voltage to ground is 120 V, so the 0-150 V row of Table 110.26(A)(1) applies, which requires 900 mm (3 ft) for Conditions 1, 2 and 3. The 3 1/2 ft value is Condition 2 for 151-600 V to ground (such as 277 V). Same values in 2017, 2020 and 2023.

    Reference: NFPA 70, National Electrical Code, 2023, Table 110.26(A)(1)

  3. To save a run, an installer proposes feeding the HVAC service receptacle from the load side of the condensing unit's disconnect. Under 210.63, this is:

    Answer: Not permitted

    210.63 states that the HVAC service receptacle outlet shall not be connected to the load side of the equipment's branch-circuit disconnecting means; otherwise the receptacle would be dead whenever the technician opens the disconnect to work. GFCI protection or fusing does not change this. The rule is in 210.63 (2017) and 210.63(A) (2020/2023).

    Reference: NFPA 70, National Electrical Code, 2023, 210.63(A)

  4. In a standard load calculation under Article 220, Part III, fixed electric space-heating loads are calculated at what percentage of the total connected load?

    Answer: 100%

    220.51 requires fixed electric space-heating loads to be calculated at 100% of the total connected load. The 125% factor for heating in 424.4(B) applies to sizing the branch-circuit conductors and overcurrent devices, not to the feeder or service load calculation. Same in 2017, 2020 and 2023.

    Reference: NFPA 70, National Electrical Code, 2023, 220.51

  5. An installer wants to tie-wrap the furnace's Class 2 thermostat cable to the outside of the EMT that carries the furnace's 120-volt supply. Under 300.11, this is:

    Answer: Permitted because the cable controls that equipment

    300.11 (Raceways Used as Means of Support) generally prohibits using raceways to support other raceways, cables or equipment, but allows a raceway containing the power supply conductors for electrically controlled equipment to support Class 2 circuit conductors or cables used solely to connect to that equipment's control circuits. Unrelated low-voltage cables may not be supported this way. Same in 2017, 2020 and 2023.

    Reference: NFPA 70, National Electrical Code, 2023, 300.11

  6. NM cable run along the joists to a furnace must be secured within what distance of each box and at what maximum interval?

    Answer: Within 12 in. and every 4 1/2 ft

    334.30 requires Type NM cable to be supported and secured at intervals not exceeding 1.4 m (4 1/2 ft) and within 300 mm (12 in.) of every cable entry into enclosures such as boxes and cabinets. 3 ft and 10 ft are the EMT values. Same in 2017, 2020 and 2023.

    Reference: NFPA 70, National Electrical Code, 2023, 334.30

  7. Branch-circuit conductors supplying a single motor-compressor must have an ampacity of at least:

    Answer: 125% of the larger of the RLC or the branch-circuit selection current

    440.32 requires conductors for a single motor-compressor to have an ampacity of not less than 125% of the motor-compressor rated-load current or the branch-circuit selection current, whichever is greater. 175% is the short-circuit protection limit in 440.22(A), and 115% is the disconnect rating in 440.12. Same in 2017, 2020 and 2023.

    Reference: NFPA 70, National Electrical Code, 2023, 440.32

  8. An HVAC control transformer will supply a 24-volt ac Class 2 thermostat circuit. Per Chapter 9, Table 11(A), what is the maximum nameplate rating for a Class 2 power source in this voltage range?

    Answer: 100 VA

    Chapter 9, Table 11(A) limits ac Class 2 power sources operating over 20 V through 30 V to a maximum nameplate rating of 100 VA. Common 40 VA and 75 VA control transformers fall within that limit, but 75 VA is not the ceiling, and 150 VA exceeds it. Same table in 2017, 2020 and 2023.

    Reference: NFPA 70, National Electrical Code, 2023, Chapter 9, Table 11(A)

  9. An installer wants to pull Class 2 thermostat cable into the same conduit as the 240-volt supply conductors for a condensing unit. There is no barrier and the Class 2 circuit is not being reclassified. Under 725.136, this is:

    Answer: Not permitted

    725.136(A) prohibits Class 2 and Class 3 circuit conductors from being placed in any raceway, cable, enclosure or similar fitting with conductors of electric light, power, Class 1 or non-power-limited fire alarm circuits, except as specifically permitted (barriers, limited separation inside equipment, etc.). Serving the same unit is not one of those permissions for a shared raceway. 725.136 remained in Article 725 in the 2017, 2020 and 2023 NEC.

    Reference: NFPA 70, National Electrical Code, 2023, 725.136(A)

  10. A single hermetic motor-compressor is marked with a rated-load current of 18.6 A and a branch-circuit selection current of 20.1 A. What is the minimum ampacity of its branch-circuit conductors?

    Answer: 25.1 A

    440.32 uses 125% of the rated-load current or the branch-circuit selection current, whichever is greater. 20.1 A is greater, so 1.25 x 20.1 = 25.1 A. 23.3 A uses the RLC (1.25 x 18.6), 20.1 A omits the 125% factor, and 35.2 A is the 175% protection value. Same in 2017, 2020 and 2023.

    Reference: NFPA 70, National Electrical Code, 2023, 440.32

Sources

Questions last verified October 27, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.