Idaho licensing exam

Idaho Limited Electrical Photovoltaic Installer Exam: Practice Test & Licensing Guide

Idaho's limited electrical photovoltaic installer exam, given by PSI: 60 NEC questions across Chapters 1 to 7 and 9, with special equipment (where solar PV lives) the biggest share. Open book, 3 hours, 70% to pass.

Questions
60
Time limit
3 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10NEC Article 90: Introduction

A homeowner asks whether a PV system installed in full compliance with the NEC is guaranteed to have room for a future battery addition. Under Article 90, a Code-compliant, properly maintained installation is:

Requirements at a glance

AgencyIdaho Division of Occupational and Professional Licenses (DOPL); exam by PSI
Exam60 questions, 3 hours, 70% to pass
Books allowed2020 or 2023 NEC (or NEC Handbook) and Ugly's Electrical References (any edition)
Fees$75 per exam to PSI, plus DOPL license application fees

Installers applying to Idaho DOPL for a limited electrical installer license in solar photovoltaic work.

How to get licensed, step by step

  1. Check your experience

    Make sure you meet DOPL's requirements for the Limited Electrical Photovoltaic Installer license before you test; you prove them when you apply.

    DOPL: electrical program information and exams (opens in a new tab)

  2. Register and pay with PSI

    Create a PSI account, pick the Idaho Limited Electrical Photovoltaic Installer exam and pay the $75 fee, then schedule a seat at a PSI center. The fee is good for one year.

    Schedule with PSI (Idaho contractor and trade exams) (opens in a new tab)

  3. Pass the exam

    Bring your tabbed references and score 70% or higher.

    Schedule with PSI (Idaho contractor and trade exams) (opens in a new tab)

  4. Apply to DOPL

    After you pass, apply through eDOPL for the Limited Electrical Photovoltaic Installer license.

    DOPL online license application (eDOPL) (opens in a new tab)

How to prepare

  • Bring your own 2020 or 2023 NEC (or NEC Handbook) and Ugly's (any edition). The PSI outline is labeled by 2017 NEC chapter, so focus on rules that read the same in each edition.
  • Tab your books before exam day with permanent tabs. You can highlight and underline, but not write in them; sticky notes are removed.
  • Chapter 6 special equipment is the biggest section (10); tab Article 690 and Article 705 (interconnected power sources).
  • The other 50 questions cover Article 90 and Chapters 1 to 5, 7 and 9, plus 5 calculations using Chapters 4 and 9.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (NEC) or NEC Handbook, 2020 or 2023 Edition
  • Ugly's Electrical References (any edition)
  • Optional: Ferm's Fast Finder Index or Tom Henry's Key Word Index (2020 and 2023 editions)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
NEC Article 90: Introduction5
NEC Chapter 1: General7
NEC Chapter 2: Wiring and Protection7
NEC Chapter 3: Wiring Methods and Materials6
NEC Chapter 4: Equipment for General Use6
NEC Chapter 5: Special Occupancies6
NEC Chapter 6: Special Equipment10
NEC Chapter 7: Special Conditions5
NEC Chapter 9: Tables3
NEC Calculations5

Exam day details

  • Administered by PSI Services for the Idaho Division of Occupational and Professional Licenses (DOPL).
  • Fee: $75 per exam, paid to PSI when you schedule. The fee is good for one year, isn't refundable, and each retake costs it again. DOPL license application fees are separate.
  • 60 questions in 3 hours; 70% to pass. 5 questions are calculations using Chapters 4 and 9.
  • Open book: bring your own 2020 or 2023 NEC (or NEC Handbook) and Ugly's Electrical References (any edition). The PSI outline lists its topics by 2017 NEC chapter; the chapters are the same in the 2020 and 2023 editions, though some articles and section numbers changed.
  • Pass the exam with PSI first, then apply to DOPL for the limited license. Book online at PSI; no DOPL approval is needed to sit.
  • You may highlight, underline and add permanent tabs to your references, but not write in them. Sticky notes and loose papers aren't allowed.
  • Your score shows on screen when you finish.
  • Cancel or reschedule at least 2 days before your appointment to keep your fee.

Frequently asked questions

What's on the Idaho PV installer exam?

Per DOPL's December 2025 PSI bulletin, 60 NEC questions: Chapter 6 special equipment 10, Chapter 1 7, Chapter 2 7, Chapters 3, 4 and 5 6 each, the introduction (Article 90) 5, Chapter 7 5, Chapter 9 tables 3, and 5 calculations from Chapters 4 and 9.

Which NEC edition do I bring?

DOPL's December 2025 PSI bulletin allows the 2020 or 2023 NEC (or the NEC Handbook) plus Ugly's Electrical References (any edition). The outline itself is labeled by 2017 NEC chapter, so focus on rules that read the same in every edition.

Is it only solar questions?

No. Chapter 6 (which includes Article 690 for PV systems) is the biggest section at 10 questions, but the other 50 cover general NEC rules from wiring and protection to special occupancies and conditions.

Free questions with answers

Show all 10 free questions and answers
  1. A homeowner asks whether a PV system installed in full compliance with the NEC is guaranteed to have room for a future battery addition. Under Article 90, a Code-compliant, properly maintained installation is:

    Answer: Essentially free from hazard, but not necessarily adequate for expansion

    90.1(B) says compliance with the Code plus proper maintenance results in an installation that is essentially free from hazard but not necessarily efficient, convenient, or adequate for good service or future expansion. Planning spare capacity is a design decision, not a Code guarantee. Same text in the 2017, 2020 and 2023 NEC.

    Reference: NFPA 70, National Electrical Code, 2023, 90.1(B)

  2. As defined in Article 100, equipment that is 'approved' is equipment that is:

    Answer: Acceptable to the authority having jurisdiction

    Article 100 defines Approved as acceptable to the authority having jurisdiction. Listed and Labeled are separate Article 100 definitions involving a product evaluation organization; listing helps the AHJ approve equipment but is not itself approval. The definition is unchanged in the 2017, 2020 and 2023 NEC.

    Reference: NFPA 70, National Electrical Code, 2023, Article 100, Approved

  3. A PV inverter's AC output circuit is protected by a 60-ampere circuit breaker. Using Table 250.122, what is the minimum size copper equipment grounding conductor?

    Answer: 10 AWG

    Table 250.122 sizes the equipment grounding conductor by the rating of the overcurrent device ahead of the circuit: 60 A requires 10 AWG copper. 12 AWG is for 20 A, and 8 AWG is the 100 A row. The table values are the same in the 2017, 2020 and 2023 NEC.

    Reference: NFPA 70, National Electrical Code, 2023, Table 250.122

  4. A long straight run of PVC conduit is installed on a sunny roof between securely mounted boxes. Expansion fittings are required when the expected length change in that run, per Table 352.44, is at least:

    Answer: 1/4 in.

    352.44 requires expansion fittings for PVC conduit where the length change calculated from Table 352.44 is expected to be 6 mm (1/4 in.) or greater in a straight run between securely mounted items such as boxes or cabinets. Rooftop runs see large temperature swings, so this often applies. Same in 2017, 2020 and 2023.

    Reference: NFPA 70, National Electrical Code, 2023, 352.44

  5. A continuous-duty motor for a solar tracker has a marked service factor of 1.15. A separate overload device must be sized at no more than what percentage of the motor nameplate full-load current?

    Answer: 125%

    430.32(A)(1) sets the separate overload device at not more than 125% of the nameplate full-load current for motors with a marked service factor of 1.15 or greater (also for temperature rise of 40°C or less); all other motors are 115%. 130% and 140% are the maximum settings allowed by 430.32(C) only when the first device trips. Same in 2017, 2020 and 2023.

    Reference: NFPA 70, National Electrical Code, 2023, 430.32(A)(1)

  6. A grain-handling building where combustible dust may be present in the air is classified as which type of hazardous location?

    Answer: Class II

    500.5(C) defines Class II locations as those that are hazardous because of the presence of combustible dust. Class I (500.5(B)) is flammable gases, vapors or liquids, and Class III (500.5(D)) is ignitible fibers or flyings. Zone 1 is a Class I zone classification under Article 505. Same in 2017, 2020 and 2023.

    Reference: NFPA 70, National Electrical Code, 2023, 500.5(C)

  7. Using the module-rating method in Article 690, the maximum current of a PV source circuit (one series string) is calculated as:

    Answer: 125% of the module rated short-circuit current (Isc)

    690.8(A)(1) sets the maximum current of a PV source circuit as the sum of the parallel-connected module rated short-circuit currents multiplied by 125% to allow for irradiance above standard test conditions. Imp is lower than Isc and is not the basis. 2020 and 2023 restructured the list as 690.8(A)(1)(a)(1), but the 125% x Isc method is unchanged from 2017.

    Reference: NFPA 70, National Electrical Code, 2023, 690.8(A)(1)

  8. According to Chapter 9, Table 1, what is the maximum percent fill of a conduit's cross-sectional area for three or more conductors?

    Answer: 40%

    Chapter 9, Table 1 limits fill to 53% for one conductor, 31% for two conductors and 40% for over two conductors. 60% applies only to nipples 24 in. or shorter (Note 4). Same in 2017, 2020 and 2023.

    Reference: NFPA 70, National Electrical Code, 2023, Chapter 9, Table 1

  9. Two current-carrying 10 AWG copper THWN-2 conductors (90°C) of an inverter circuit run in conduit through a mechanical room with a 45°C ambient temperature. What is the corrected ampacity (before considering termination limits)?

    Answer: 34.8 A

    Table 310.16 gives 10 AWG copper 40 A in the 90°C column. The ambient correction factor for 90°C conductors at 41-45°C is 0.87, so 40 x 0.87 = 34.8 A. 32.8 A uses the 75°C factor (0.82) and 30.5 A starts from the 75°C ampacity (35 x 0.87). The correction table is Table 310.15(B)(1)(1) in 2023, Table 310.15(B)(1) in 2020 and Table 310.15(B)(2)(a) in 2017; the 2017 ampacity table is Table 310.15(B)(16). Values are identical in all three.

    Reference: NFPA 70, National Electrical Code, 2023, Table 310.16 and Table 310.15(B)(1)(1)

  10. A PV breaker is backfed at the opposite end of a busbar using the 120% option. What permanent warning must be applied next to that breaker?

    Answer: 'POWER SOURCE OUTPUT CONNECTION - DO NOT RELOCATE THIS OVERCURRENT DEVICE'

    The 120% option requires a permanent warning label on the distribution equipment adjacent to the backfed breaker reading 'WARNING: POWER SOURCE OUTPUT CONNECTION - DO NOT RELOCATE THIS OVERCURRENT DEVICE' (or equivalent), because the rule depends on the breaker staying at the far end. 705.12(B)(2) in 2023, 705.12(B)(3)(2) in 2020, 705.12(B)(2)(3)(b) in 2017.

    Reference: NFPA 70, National Electrical Code, 2023, 705.12(B)(2)

Sources

Questions last verified October 27, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.