Requirements at a glance
| Agency | Hawaii Board of Electricians and Plumbers (DCCA PVL); exams by PSI |
|---|---|
| Experience | Registered as a journey worker electrician for at least 4 years, or equivalent experience in the trade (HRS 448E-5(b)) |
| Exam | Supervising electrician: 70 questions, 3 hours, 70% |
| Books allowed | None; the 2020 NEC is provided in the exam center |
| Fee | $95 to PSI, plus the Board's application and license fees |
Journey worker electricians applying for a Hawaii supervising electrician license, which lets you direct and supervise electrical work.
Official links
How to get licensed, step by step
Apply to the Board
Send the Board of Electricians and Plumbers your application with proof of your experience. You can't register with PSI until it approves you.
Board of Electricians and Plumbers (opens in a new tab)Hawaii Revised Statutes chapter 448E (electricians and plumbers) (opens in a new tab)Hawaii Administrative Rules 16-80 (electricians and plumbers) (opens in a new tab)
Schedule the supervising electrician exam with PSI
Register online or call PSI at 833-333-4754. Your approval is good for 2 years and you can test as often as you like in that time.
Get licensed
PSI reports your result to the Board; follow the Board's instructions for the license fee and any remaining requirements.
How to prepare
- Hawaii's trade exams are PSI exams on specific editions: the 2020 NEC, the 2018 UPC, IMC, IFGC and IBC. Hawaii's state electrical code is older than the 2020 NEC, so study to the editions on PSI's bulletin, and check the bulletin again before test day.
- Contractor exams are closed book except C-13, where PSI provides the NEC. Electrician exams provide the NEC too. Plumber and other contractor exams allow no reference books.
- Motors (6), overcurrent protection (4) and illuminated signs (2) have their own sections: Articles 430, 240 and 600.
- Grounding and bonding and service, feeders and branch circuits are 10 questions each.
- Start with the free questions above to find your weak topics, then drill those first.
- Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
- Read every explanation, including for questions you got right, and look the section up in your own book.
Books for this exam
This is an open-book exam: you can bring the references below, and most questions come from the 2020 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.
2020 National Electrical Code (NEC), NFPA 70Essential
Provided in the exam center, so you can't bring your own. Practice finding answers fast.
Official reference list (as published by the testing agency)
- NFPA 70: National Electrical Code, 2020 edition (provided in the exam center)
What's on the exam
Official content outline from PSI Services (number of questions per topic):
| Topic | Questions | |
|---|---|---|
| General Electrical Knowledge | 6 | |
| Service, Feeders, and Branch Circuits | 10 | |
| Grounding and Bonding | 10 | |
| Conductors and Cables | 8 | |
| Raceways and Boxes | 4 | |
| Special Occupancies, Conditions, and Equipment | 4 | |
| Electrical Power | 6 | |
| Motors | 6 | |
| Low Voltage and Communication Circuits | 2 | |
| Lighting | 4 | |
| Illuminated Signs | 2 | |
| Safety Information | 4 | |
| Overcurrent Protection | 4 |
Exam day details
- Administered by PSI Services for the Hawaii Board of Electricians and Plumbers.
- Fee: $95 to PSI. Board application and license fees are separate.
- 70 scored questions in 3 hours; 49 correct (70%) to pass.
- The Board must approve your application before you can register with PSI. Your eligibility lasts 2 years, and you can test as often as you like within it.
- PSI may add up to 10 unscored pretest questions; they do not count against your time.
- PSI provides an online calculator, or you can bring a silent, non-programmable one.
Frequently asked questions
What's on the Hawaii supervising electrician exam?
70 scored questions: service, feeders and branch circuits 10, grounding and bonding 10, conductors and cables 8, general electrical knowledge 6, electrical power 6, motors 6, raceways and boxes 4, special occupancies 4, lighting 4, safety 4, overcurrent protection 4, low voltage and communication 2 and illuminated signs 2.
Which NEC edition is used?
The 2020 NEC, provided in the exam center.
How is it different from the journey worker exam?
Same length and time, but it adds separate overcurrent protection, motors and illuminated signs sections and has fewer general and conductor questions.
Free questions with answers
Show all 10 free questions and answers
A 480Y/277-volt switchboard has exposed live parts on one side of the aisle and a grounded concrete wall on the other side (Condition 2). What minimum depth of working space is required in front of the switchboard?
Answer: 3 1/2 feet
Table 110.26(A)(1) gives 3 ft for Condition 1, 3 1/2 ft for Condition 2 and 4 ft for Condition 3 at 151 to 600 volts to ground. Exposed live parts on one side and grounded parts on the other is Condition 2. 4 feet applies only when live parts are on both sides.
Reference: 2020 National Electrical Code (NFPA 70), Table 110.26(A)(1)
Under Article 100, which description fits a qualified person?
Answer: One trained in the equipment and its hazards
The Article 100 definition ties a qualified person to skills and knowledge of the construction and operation of the equipment, plus safety training to recognize and avoid the associated hazards. Years of service or an official title alone do not qualify someone.
Reference: 2020 National Electrical Code (NFPA 70), Article 100, Qualified Person
A 3-phase feeder supplies 120 amperes of continuous load and 80 amperes of noncontinuous load. The terminals are rated 75 C and the conductors are THHN copper in conduit with no adjustment or correction factors. What is the smallest conductor size permitted?
Answer: 4/0 AWG
215.2(A)(1) requires an ampacity of the noncontinuous load plus 125 percent of the continuous load: 80 + (1.25 x 120) = 230 A. In the 75 C column of Table 310.16, 3/0 = 200 A (too small) and 4/0 = 230 A. 250 kcmil results from applying 125 percent to the whole 200 A; 3/0 results from ignoring the continuous-load factor.
Reference: 2020 National Electrical Code (NFPA 70), 215.2(A)(1); Table 310.16
A feeder is protected by a 400-ampere circuit breaker, and the copper conductors run in rigid metal conduit. Using Table 250.122, what is the minimum copper equipment grounding conductor?
Answer: 3 AWG
Table 250.122 is entered with the rating of the overcurrent device ahead of the equipment: 400 A requires 3 AWG copper (300 A = 4 AWG, 500 A = 2 AWG, 600 A = 1 AWG). The feeder conductor size is not used to enter the table, except for the increase rule in 250.122(B).
Reference: 2020 National Electrical Code (NFPA 70), Table 250.122
Nine current-carrying 8 AWG THHN copper conductors are installed in one conduit at a 30 C ambient. Table 310.16 lists 8 AWG THHN at 55 amperes in the 90 C column. What is the adjusted allowable ampacity?
Answer: 38.5 amperes
Table 310.15(C)(1) (2020 numbering; Table 310.15(B)(3)(a) in 2017) requires a 70 percent adjustment for 7 through 9 current-carrying conductors: 55 x 0.70 = 38.5 A. 44.0 A uses the 80 percent factor for 4-6 conductors; 27.5 A uses 50 percent, which is for 10-20 conductors; 55 A takes no adjustment. The 90 C column is used as the starting point since THHN is a 90 C conductor.
Reference: 2020 National Electrical Code (NFPA 70), Table 310.15(C)(1); Table 310.16
A box contains six 12 AWG insulated conductors from three cables, three 12 AWG equipment grounding conductors, internal cable clamps, and one duplex receptacle on a single yoke. Using 2.25 cubic inches per 12 AWG conductor, what is the minimum box volume?
Answer: 22.5 cubic inches
Count volume allowances: six conductors = 6; all equipment grounding conductors together = 1 (314.16(B)(5)); internal clamps = 1 (314.16(B)(2)); one yoke with a device = 2 (314.16(B)(4)). Total 10 x 2.25 = 22.5 in3. 20.25 in3 omits the clamp allowance (9 allowances); 18.0 in3 omits the yoke (8); 24.75 in3 adds one allowance too many (11).
Reference: 2020 National Electrical Code (NFPA 70), 314.16(B); Table 314.16(B)
A PV source circuit from a module string has a short-circuit current (Isc) of 9.5 amperes. Under 690.8(A)(1), what is the maximum circuit current, and what must the conductor and overcurrent device be rated for after the second multiplier in 690.8(B)?
Answer: 11.9 amperes; at least 14.8 amperes
Maximum circuit current = Isc x 1.25 = 9.5 x 1.25 = 11.875 A (690.8(A)(1)). The overcurrent device and conductor ampacity must be at least 125 percent of that: 11.875 x 1.25 = 14.84 A (690.8(B)). The first factor accounts for high irradiance; the second applies the continuous-load rule.
Reference: 2020 National Electrical Code (NFPA 70), 690.8(A)(1); 690.8(B)
A 3-phase, 480-volt primary, 75-kVA transformer has only primary overcurrent protection and no secondary protection. Under 450.3(B), what is the maximum rating of the primary overcurrent device?
Answer: 125 amperes
Primary full-load current = 75,000 / (1.732 x 480) = 90.2 A. For a current of 9 A or more, the primary protection may be sized at 125 percent: 90.2 x 1.25 = 112.8 A. Since this is not a standard rating, the next higher standard size, 125 A, is permitted. 100 A is the next lower size; 90 A is the unprotected current; 150 A is too large.
Reference: 2020 National Electrical Code (NFPA 70), Table 450.3(B); 240.6(A)
A 25-hp, 460-volt, 3-phase squirrel-cage induction motor has a Table 430.250 full-load current of 34 amperes. The motor is continuous duty on a branch circuit of its own. What is the minimum ampacity of the branch-circuit conductors?
Answer: 42.5 amperes
430.22(A) requires branch-circuit conductors for a single continuous-duty motor to be at least 125 percent of the full-load current from Table 430.250: 34 x 1.25 = 42.5 A. 34 A omits the 125 percent; 39.1 A is 115 percent; 85 A is the 250 percent value used for inverse-time breaker sizing, not for conductors.
Reference: 2020 National Electrical Code (NFPA 70), 430.22(A); Table 430.250
A luminaire will be installed within the zone above a bathtub, within 3 feet horizontally and 8 feet vertically from the top of the tub rim. What must the luminaire be listed for?
Answer: Damp, or wet where exposed to shower spray
410.10(D) requires luminaires in the bathtub or shower zone (3 ft horizontal, 8 ft vertical from the tub rim or shower threshold) to be listed for damp locations, or listed for wet locations where subject to shower spray. A dry-location luminaire is not acceptable.
Reference: 2020 National Electrical Code (NFPA 70), 410.10(D)
Sources
- PSI: Hawaii Electricians Candidate Information Bulletin (3/22/2024) (opens in a new tab)
- Hawaii DCCA Professional and Vocational Licensing (opens in a new tab)
- Hawaii Revised Statutes chapter 448E (electricians and plumbers) (opens in a new tab)
Questions last verified November 16, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.