Hawaii licensing exam

Hawaii C-13 Electrical Contractor Exam: Practice Test & Licensing Guide

The PSI trade exam for Hawaii's C-13 electrical contractor classification: 40 questions on the 2020 NEC, including photovoltaics. The NEC is provided; no notes.

Questions
40
Time limit
2 hours
Passing score
75%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10General Electrical Knowledge

An 80-ampere noncontinuous load will be served through a standard 90-ampere circuit breaker whose terminals carry no temperature marking, using THHN copper conductors. What is the smallest copper conductor that may be used, applying the termination temperature rule?

Requirements at a glance

AgencyHawaii Contractors License Board (DCCA PVL); exams by PSI
ExperienceAt least 4 years of supervisory experience (foreman, supervising employee or contractor) in the classification within the past 10 years (HAR 16-77-18); the Board may accept equivalent training or experience
ExamsC-13 Electrical Contractor: 40 questions, 2 hours, 75%, plus the Business and Law exam for new applicants
Books allowedNone; the 2020 NEC is provided in the exam center (no notes)
Fees$80 to PSI per exam ($85 for B and A), plus the Board's application and license fees and required insurance

Qualifiers for a Hawaii C-13 electrical contractor license from the Contractors License Board, in addition to the Business and Law exam. C-13 also covers the work of C-15 and C-60.

How to get licensed, step by step

  1. Apply to the Board

    Send the Contractors License Board your application. You can't register with PSI until the Board approves it and sends a letter of approval.

    Contractors License Board (opens in a new tab)Hawaii Administrative Rules 16-77 (contractors) (opens in a new tab)

  2. Schedule Business and Law and the C-13 exam with PSI

    Register online or call PSI at 833-333-4754. Your approval is good for 6 months and you can test as often as you like in that time. After 6 months you need a new application.

    Schedule with PSI (Hawaii trade exams) (opens in a new tab)

  3. Pass both exams

    Each exam needs 75%. If you already hold a Hawaii license and add a classification, you take only the new trade exam.

    Schedule with PSI (Hawaii trade exams) (opens in a new tab)

  4. Get licensed

    Send the Board your results and proof of the insurance (workers' compensation and liability) the license requires.

    Contractors License Board (opens in a new tab)Hawaii Revised Statutes chapter 444 (contractors) (opens in a new tab)

How to prepare

  • Hawaii's trade exams are PSI exams on specific editions: the 2020 NEC, the 2018 UPC, IMC, IFGC and IBC. Hawaii's state electrical code is older than the 2020 NEC, so study to the editions on PSI's bulletin, and check the bulletin again before test day.
  • Contractor exams are closed book except C-13, where PSI provides the NEC. Electrician exams provide the NEC too. Plumber and other contractor exams allow no reference books.
  • Service, feeders, branch circuits and electrical power (7) and grounding and bonding (6) are 13 of the 40 questions.
  • Photovoltaics (2) comes from NEC Article 690.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2020 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

  • 2020 National Electrical Code (NEC), NFPA 70Essential

    Provided in the exam center, so you can't bring your own. Practice finding answers fast.

    NFPA store (opens in a new tab)

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code, 2020 edition (provided in the exam center; no highlighting or notes)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
General Electrical Knowledge3
Service, Feeders, Branch Circuits, and Electrical Power7
Grounding and Bonding6
Conductors and Cables3
Raceways, Conduits, and Boxes3
Special Occupancies, Conditions, and Equipment3
Motors3
Low Voltage and Controls3
Lighting2
Safety Information2
Overcurrent Protection3
Photovoltaics2

Exam day details

  • Administered by PSI Services for the Hawaii Contractors License Board.
  • Fee: $80 to PSI. The Contractors License Board's application and license fees are separate.
  • 40 scored questions in 2 hours; 30 correct (75%) to pass.
  • The 2020 NEC is provided at the test center. You cannot mark it during the exam.
  • The Board must approve your application before you can register with PSI. Your eligibility lasts 6 months, and you can test as often as you like within it.
  • PSI may add up to 10 unscored pretest questions; they do not count against your time.
  • Closed-book and open-book rules are on each exam page. PSI provides an online calculator, or you can bring a silent, non-programmable one.

Frequently asked questions

What's on the Hawaii C-13 exam?

40 scored questions: service, feeders, branch circuits and electrical power 7, grounding and bonding 6, general electrical knowledge 3, conductors and cables 3, raceways, conduits and boxes 3, special occupancies 3, motors 3, low voltage and controls 3, overcurrent protection 3, lighting 2, safety 2 and photovoltaics 2.

Do I also take Business and Law?

Yes, if you are a new applicant. Business and Law is a separate 80-question exam.

Does C-13 cover solar?

PSI's classification description says C-13 includes the work of the C-15 electronic systems contractor and the C-60 solar power systems contractor.

Free questions with answers

Show all 10 free questions and answers
  1. An 80-ampere noncontinuous load will be served through a standard 90-ampere circuit breaker whose terminals carry no temperature marking, using THHN copper conductors. What is the smallest copper conductor that may be used, applying the termination temperature rule?

    Answer: 3 AWG

    For circuits rated 100 A or less with unmarked terminals, 110.14(C)(1)(a) limits the conductor ampacity to the 60 C column of Table 310.16 even when the insulation is rated 90 C. In the 60 C column 4 AWG is 70 A (too small) and 3 AWG is 85 A, which carries the 80 A load; 85 A is not a standard rating, so 240.4(B) lets the 90 A breaker protect it. Using the 90 C value of 4 AWG (95 A) would overheat the terminal.

    Reference: 2020 National Electrical Code (NFPA 70), 110.14(C)(1)(a) and Table 310.16

  2. Overhead service conductors cross a paved commercial parking lot that is subject to truck traffic. What is the minimum clearance from final grade?

    Answer: 18 ft

    230.24(B) sets 10 ft at the building entrance and pedestrian-only areas, 12 ft over residential property and driveways and commercial areas not subject to truck traffic, 15 ft for the intermediate case, and 18 ft over public streets, alleys, roads, and parking areas subject to truck traffic.

    Reference: 2020 National Electrical Code (NFPA 70), 230.24(B)(4)

  3. What minimum length of a rod electrode must be in contact with the soil?

    Answer: 8 feet

    250.53(G) in the 2020 edition requires at least 8 ft of rod or pipe electrode in contact with the soil, driven to a depth of at least 8 ft. Rods are manufactured in 8 ft and 10 ft lengths for this reason.

    Reference: 2020 National Electrical Code (NFPA 70), 250.52(A)(5) and 250.53(G)

  4. A 1/0 AWG copper THHN conductor (170 amperes at 90 C) is in a 40 C ambient with a correction factor of 0.91. What is its corrected ampacity?

    Answer: About 155 amperes

    Table 310.16 gives 170 A at 90 C. The 2020 NEC moved the ambient correction table to Table 310.15(B)(1) (it was 310.15(B)(2)(a) in 2017); its factor for 40 C in the 90 C column is 0.91: 170 x 0.91 = 154.7 A, or about 155 A. Dividing by 0.91 gives 187 A, which is a common mistake.

    Reference: 2020 National Electrical Code (NFPA 70), Table 310.16 and Table 310.15(B)(1)

  5. Conductors in a 3-inch conduit make a straight pull through a pull box. What is the minimum length of the box, measured in the direction of the conductors?

    Answer: 24 inches

    314.28(A)(1) requires a straight-pull box to be not less than 8 times the trade diameter of the largest raceway: 8 x 3 in = 24 in. The 6 times multiplier is used for angle pulls, which would give 18 in.

    Reference: 2020 National Electrical Code (NFPA 70), 314.28(A)(1)

  6. A feeder of 1 AWG copper THWN (130 amperes at 75 C) feeds a panel with no receptacle loads, and the calculated load is 125 amperes. What is the maximum standard overcurrent device permitted by the next-size-up rule?

    Answer: 150 amperes

    240.4(B) permits the next higher standard rating above the conductor ampacity (130 A) when the circuit is not a multioutlet branch circuit for receptacles and the rating is not over 800 A. The next standard size above 130 A is 150 A (240.6(A)). A 125 A breaker would also be allowed, but the question asks for the maximum.

    Reference: 2020 National Electrical Code (NFPA 70), 240.4(B) and 240.6(A)

  7. In a Class I, Division 1 location, a conduit enters an explosionproof enclosure that contains switches or breakers that may produce arcs in normal operation. Where is the conduit seal located?

    Answer: Within 18 inches of the enclosure

    501.15(A)(1) requires a seal in each conduit entering an explosionproof enclosure with arcing apparatus, and the seal must be placed within 18 in of the enclosure. No union, coupling or fitting other than a listed explosionproof reducer may be between the seal and the enclosure.

    Reference: 2020 National Electrical Code (NFPA 70), 501.15(A)(1)

  8. A 10-horsepower, 460-volt, 3-phase induction motor has a full-load current of 14 amperes in Table 430.250. What is the minimum ampacity of the branch-circuit conductors?

    Answer: 17.5 amperes

    430.22 requires conductors for a single continuous-duty motor to have an ampacity of at least 125 percent of the table full-load current: 14 x 1.25 = 17.5 A. 35 A is the maximum inverse-time breaker size (250 percent), which is a different calculation.

    Reference: 2020 National Electrical Code (NFPA 70), 430.22 and Table 430.250

  9. What is the minimum size of the copper grounding conductor for a TV or radio receiving antenna mast?

    Answer: 10 AWG

    810.21(H) requires the bonding or grounding electrode conductor for an antenna mast or antenna discharge unit to be not smaller than 10 AWG copper, 8 AWG aluminum, or 17 AWG copper-clad steel or bronze. The 14 AWG minimum applies to communications and CATV bonding under 800.100(A)(3), not to Article 810 antennas.

    Reference: 2020 National Electrical Code (NFPA 70), 810.21(H)

  10. A bedroom in a new dwelling has no ceiling light. Which arrangement satisfies the Code's requirement for lighting in this habitable room?

    Answer: A receptacle controlled by a wall switch near the entrance

    210.70(A)(1) requires a wall-switch-controlled lighting outlet in every habitable room, and in rooms other than kitchens and bathrooms, one or more switched receptacles may be used in its place. A lamp on an unswitched receptacle does not meet the rule.

    Reference: 2020 National Electrical Code (NFPA 70), 210.70(A)(1)

Sources

Questions last verified November 16, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.