Requirements at a glance
| Agency | Alaska Division of Corporations, Business and Professional Licensing (CBPL); exam by PSI |
|---|---|
| Experience | Set by 12 AAC 39.332; the license covers warm air systems up to 240,000 Btu/h input in single-family and duplex dwellings up to three stories |
| Exam | 65 questions, 2 hours, 70% |
| Books allowed | IMC 2012, NFPA 54 (2018) and the Alaska mechanical statutes and regulations |
| Fee | $150 to PSI per registration, plus the CBPL application and license fees |
HVAC installers seeking a mechanical administrator license in the residential HVAC category (single-family and duplex dwellings up to three stories, warm air systems up to 240,000 Btu/h input).
Official links
How to get licensed, step by step
Apply to the CBPL
Send the Division your application, fee and supporting documents. When it approves you, it mails an eligibility letter with your state ID number.
Alaska Division of Corporations, Business and Professional Licensing (CBPL) (opens in a new tab)
Schedule the residential HVAC exam with PSI
Register online or call PSI at 855-746-8173. Your eligibility letter is valid for one year and you can retake as often as you like in that year, paying each time.
Schedule with PSI (mechanical administrators) (opens in a new tab)
Pass the exam
You need 70%. Scores are valid for 12 months toward the license.
Schedule with PSI (mechanical administrators) (opens in a new tab)
Get licensed
Send the Division your results and the license fee. Administrator licenses run 2 years and expire December 31 of odd-numbered years.
Alaska Division of Corporations, Business and Professional Licensing (CBPL) (opens in a new tab)
How to prepare
- Bring the exact editions on PSI's outline: the 2020 NEC, 2018 UPC, 2012 IMC, 2018 NFPA 54 and 2018 IRC. Code questions are based only on the listed edition.
- Tab your books before exam day with permanent tabs only. You can highlight and underline, but you can't write in them or bring loose papers; sticky notes are removed.
- Every administrator exam has an Alaska statutes and regulations section drawn from the Division's PDFs (AS 08.18, AS 08.40, 12 AAC 21, 32 and 39). Tab those too.
- Alaska statutes and regulations are 12 of 65 questions, more than any other section: study them first.
- Start with the free questions above to find your weak topics, then drill those first.
- Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
- Read every explanation, including for questions you got right, and look the section up in your own book.
Books for this exam
This is an open-book exam: you can bring the references below. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.
Official reference list (as published by the testing agency)
- International Mechanical Code (IMC), 2012 edition
- NFPA 54 National Fuel Gas Code, 2018 edition
- Alaska Mechanical Administrator Statutes and Regulations (AS 08.40; 12 AAC 39)
- Alaska Centralized Regulations and Statutes
What's on the exam
Official content outline from PSI Services (number of questions per topic):
| Topic | Questions | |
|---|---|---|
| AK Statutes | 12 | |
| Burners | 8 | |
| Controls | 8 | |
| Air Conditioning | 8 | |
| Fuel Piping | 7 | |
| Chimneys, Flues, Vents | 7 | |
| Sheet Metal and Duct | 8 | |
| Testing and Inspections | 4 | |
| Evaporative Cooling | 3 |
Exam day details
- Administered by PSI Services for the Alaska Division of Corporations, Business and Professional Licensing (CBPL).
- Fee: $150 to PSI per exam registration (not refundable or transferable). CBPL application and license fees are separate.
- 65 scored questions in 2 hours; 46 correct (70%) to pass. Plus up to 10 unscored experimental items.
- Scope (12 AAC 39.332): fuel piping and warm air heating not exceeding 240,000 Btu/h input in a single-family or duplex dwelling up to three stories.
- Open book: bring your own copies of the allowed references. You may highlight and add permanent tabs beforehand, but not write in them; sticky notes are removed. A silent, non-printing, non-programmable calculator is allowed.
- PSI may add 1 to 10 unscored experimental items, which count against your time.
- The CBPL approves your application first and sends an eligibility letter; the letter is valid for one year, and you may retake as many times as you like in that year (a new fee each time). If you do not pass within the year, you must reapply.
- Since 10/20/2026 the electrical and mechanical administrator exams can be taken remotely or at a PSI test site.
Frequently asked questions
What is on the Alaska residential HVAC exam?
65 questions: Alaska statutes 12, burners 8, controls 8, air conditioning 8, sheet metal and duct 8, fuel piping 7, chimneys, flues and vents 7, testing and inspections 4 and evaporative cooling 3.
How long is it?
Two hours (120 minutes), 70% to pass.
Free questions with answers
Show all 10 free questions and answers
Under 12 AAC 39.332(b), what is the largest warm air heating system, by input, that falls within the residential HVAC mechanical administrator license?
Answer: 240,000 Btu/h input
12 AAC 39.332(b)(2) lists warm air heating systems not exceeding 240,000 B.T.U./hour input. The limit is stated as input rating, not output, so a furnace with a larger input is outside the category even if its output is lower.
Reference: Alaska Mechanical Administrator Statutes and Regulations, 12 AAC 39.332(b)(2)
A residential HVAC administrator is supervising replacement of an oil-fired furnace in a duplex, including the new oil line from the outside tank to the furnace. Is the oil piping within the category scope?
Answer: Yes, fuel tank and fuel oil piping integral to work on the HVAC system in a duplex of up to three stories is included
12 AAC 39.332(b)(1) covers fuel gas piping downstream of the gas meter and the fuel tank and fuel oil piping that is integral to work on an HVAC system for a single-family or duplex dwelling not exceeding three stories. A duplex qualifies, and the oil line is integral to the furnace.
Reference: Alaska Mechanical Administrator Statutes and Regulations, 12 AAC 39.332(b)(1)
Under Section 301.7, how must appliances regulated by the mechanical code be furnished for the application in which they are installed?
Answer: Listed and labeled for that application
Section 301.7 requires appliances to be listed and labeled for the application in which they are installed and used, unless otherwise approved by the code official under Section 105. Listing and labeling of refrigeration equipment is handled in Section 1101.2.
Reference: 2012 International Mechanical Code (Alaska Mechanical Code 2012), 301.7
A water-level detection device is used to protect against condensate overflow from a cooling coil. To what standard does Section 307.2.3 require the device to conform?
Answer: UL 508
Section 307.2.3 requires the water-level detection device to conform to UL 508 and to shut off the equipment served before the auxiliary pan or primary drain overflows. UL 17 covers vent dampers, UL 181 covers ducts and UL 1995 covers heating and cooling equipment.
Reference: 2012 International Mechanical Code (Alaska Mechanical Code 2012), 307.2.3
A furnace and cooling coil are installed over an auxiliary drain pan. Part of the insulation would be damaged if the pan fills with water. What does Section 307.2.3.2 require?
Answer: That part of the insulation and equipment sits above the pan rim
Section 307.2.3.2 requires that portion of any appliance, equipment or insulation subject to water damage when auxiliary pans fill to be installed above the rim of the pan, and any supports inside the pan to be water resistant and approved.
Reference: 2012 International Mechanical Code (Alaska Mechanical Code 2012), 307.2.3.2
What does UPC Section 1211.3 say about using gas piping for electrical grounding?
Answer: Gas piping may not be used as a grounding conductor or electrode
Section 1211.3 prohibits using gas piping as a grounding conductor or electrode. Gas piping is bonded to the grounding system for safety under 1211.1 and 1211.2, which is different from using it as the ground.
Reference: 2018 Uniform Plumbing Code (Alaska adoption), Chapter 12 Fuel Gas Piping, 1211.3
What is the minimum thickness of a galvanized steel vent connector under Section 803.8?
Answer: 0.0136 inch (No. 28 gage)
Section 803.8 sets the minimum vent connector thickness at 0.0136 inch (No. 28 gage) for galvanized steel, 0.022 inch for copper and 0.020 inch for aluminum. The 0.0575-inch figure is for medium- and high-heat chimney connectors in Table 803.9(2).
Reference: 2012 International Mechanical Code (Alaska Mechanical Code 2012), 803.8
Using Table 603.4 for ducts in a single dwelling unit, what is the minimum galvanized thickness for an exposed rectangular duct over 14 inches in size?
Answer: 0.0187 inch (No. 26 gage)
Table 603.4 lists 0.0157 inch (28 gage) for exposed rectangular ducts of 14 inches or less and 0.0187 inch (26 gage) for exposed rectangular ducts over 14 inches. The 0.0236 inch figure applies to round or enclosed ducts of 20 inches and over.
Reference: 2012 International Mechanical Code (Alaska Mechanical Code 2012), Table 603.4
An evaporative cooler is connected to the potable water supply. What does IMC Section 928.1 require?
Answer: Backflow protection per Section 608 of the Plumbing Code
Section 928.1 requires evaporative cooling equipment to be provided with potable water backflow protection in accordance with Section 608 of the Plumbing Code as adopted by 8 AAC 63.010. It also calls for manufacturer's instructions, level platforms per Section 304.10, flashed openings, and intake locations per Section 401.4.
Reference: 2012 International Mechanical Code (Alaska Mechanical Code 2012), 928.1
A short branch is added to existing gas piping after the pressure test, a minor addition. What does UPC Section 1213.1.2 allow?
Answer: No pressure test if inspected and the joints are leak tested
Section 1213.1.2 says repairs or additions after the pressure test require testing of the affected piping, but minor repairs and additions need not be pressure tested if the work is inspected and connections are tested with noncorrosive leak-detecting fluid or another method approved by the authority having jurisdiction.
Reference: 2018 Uniform Plumbing Code (Alaska adoption), Chapter 12 Fuel Gas Piping, 1213.1.2
Sources
- PSI: Alaska Mechanical Administrators Examination Candidate Information Bulletin (updated 10/15/2026) (opens in a new tab)
- Alaska Division of Corporations, Business and Professional Licensing (opens in a new tab)
Questions last verified November 16, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.