Maryland licensing exam

Maryland Journey Natural Gas Fitter Exam: Practice Test & Licensing Guide

The PSI exam for the Maryland journey natural gas fitter license: 40 questions on gas piping, pipe sizing math, chimneys and flues, combustion and appliances. Open book, 70% to pass.

Questions
40
Time limit
90 min
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10General Piping

Which plastic piping material may be used for underground fuel gas piping outdoors?

Requirements at a glance

AgencyMaryland State Board of Plumbing; exam by PSI
Experience3,750 natural gas fitter working hours as an apprentice over at least 2 years, plus an approved course of study.
Exam40 questions, 90 minutes, 70% to pass
Books allowed2018 IFGC, Mathematics for Plumbers and Pipefitters (8th edition) and Frankland's Pipe Fitters and Pipe Welders Handbook (1984)
Fees$25 to PSI, plus Board application and license fees

Gas fitters applying for a Maryland journey natural gas fitter license from the State Board of Plumbing, after 3,750 working hours as a natural gas fitter apprentice over at least 2 years and an approved course of study.

How to get licensed, step by step

  1. Confirm you qualify

    3,750 natural gas fitter working hours as an apprentice over at least 2 years, plus an approved course of study.

    Maryland Department of Labor: Occupational and Professional Licensing (opens in a new tab)Maryland Code (General Assembly) (opens in a new tab)

  2. Apply through PSI

    Submit the exam application online at the PSI site below (mailed or faxed applications are returned). PSI and the Board review your documents, then email you how to pay and schedule.

    Schedule with PSI (plumbers and gas fitters) (opens in a new tab)

  3. Pass the open-book exam

    Exam fees are non-refundable and non-transferable. The bulletin lists no waiting period between attempts; confirm with PSI.

    Schedule with PSI (plumbers and gas fitters) (opens in a new tab)

  4. Apply for the license

    After you pass, the Board sends you the license application. Pay the license fee and file any required insurance.

    Maryland Department of Labor: Occupational and Professional Licensing (opens in a new tab)

How to prepare

  • Tab your books before exam day: permanent plastic tabs (Avery Swift or Redi-Tag), highlighting and underlining are allowed; Post-It flags and writing in the book are not.
  • Only 40 questions, so every section counts: general piping (15) and pipe sizing math (10) are 25 of them. Tab the IFGC pipe sizing tables and practice sizing by hand.
  • Chimney and flues, combustion and appliances are 5 questions each; tab IFGC Chapters 3, 5 and 6 and the appliance chapters.
  • The Lee Smith math book or Frankland's handbook can serve for the math items; know where the offset and volume formulas are.
  • The bulletin lists the 2018 IFGC while the state code is now the 2024 edition; check the current bulletin before buying books.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2018 IFGC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

  • 2018 International Fuel Gas Code (IFGC)Essential

    Allowed in the exam room. Gas appliances and piping are 40 of the 100 plumber questions.

    ICC store: 2018 IFGC (opens in a new tab)

  • Mathematics for Plumbers and Pipefitters, Lee Smith, 8th Edition (2013)

    Allowed in the exam room. Offsets, pipe sizing and volume math for the 7 math questions.

Official reference list (as published by the testing agency)
  • International Fuel Gas Code (IFGC), 2018 edition (allowed in the exam room)
  • Mathematics for Plumbers and Pipefitters, Lee Smith, 8th Edition, 2013 (allowed in the exam room)
  • The Pipe Fitters and Pipe Welders Handbook, Revised Edition, Thomas Frankland, 1984 (allowed in the exam room)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
General Piping15
Pipe Sizing/Math10
Chimney and Flues5
Combustion5
Appliances5

Exam day details

  • Administered by PSI Services for the Maryland State Board of Plumbing.
  • Fee: $25 to PSI. Board application and license fees are separate.
  • 40 questions in 90 minutes; 28 correct (70%) to pass. The outline and references match the master natural gas fitter exam.
  • Eligibility: 3,750 natural gas fitter working hours as an apprentice over at least 2 years, plus an approved course of study.
  • Open book: you may bring only the listed references (none are provided), which you may index, highlight and underline but not write in. Study guides are not allowed.
  • The Pipe Fitters and Pipe Welders Handbook (Frankland, 1984) or the Lee Smith math book can be used as the general reference for math items.
  • Apply to PSI online first; once approved you receive an email on how to pay and schedule. Upload your experience documentation with the application.
  • If a code and a trade reference disagree, the code, law or regulation overrides the other sources. State-specific law overrides national law.

Frequently asked questions

What's on the Maryland journey natural gas fitter exam?

40 questions: general piping 15, pipe sizing and math 10, chimney and flues 5, combustion 5 and appliances 5.

How much does the exam cost?

$25 to PSI. Board application and license fees are separate.

Which books can I bring?

The 2018 IFGC, Mathematics for Plumbers and Pipefitters (8th edition) and The Pipe Fitters and Pipe Welders Handbook (Frankland, 1984).

Free questions with answers

Show all 10 free questions and answers
  1. Which plastic piping material may be used for underground fuel gas piping outdoors?

    Answer: Polyethylene pipe marked "Gas" and "ASTM D2513"

    Section 403.6 allows polyethylene pipe, tubing and fittings that conform to ASTM D2513 and are marked "Gas" and "ASTM D2513" (polyamide to ASTM F2945 is also allowed). The same section prohibits PVC and CPVC for fuel gas supply, so a pressure rating on the PVC does not make it acceptable. ABS is not listed as a fuel gas material at all.

    Reference: 2018 International Fuel Gas Code, Section 403.6

  2. Which of the following pipe materials is not permitted for a fuel gas piping system?

    Answer: Cast-iron pipe

    Section 403.4.1 states flatly that cast-iron pipe shall not be used. Steel pipe (403.4.2, ASTM A53), stainless steel tubing (403.5.2, ASTM A268 or A269) and listed CSST (403.5.5) are all recognized materials.

    Reference: 2018 International Fuel Gas Code, Section 403.4.1

  3. A gas supplier reports that the gas in a system contains an average of 0.4 grains of hydrogen sulfide per 100 standard cubic feet. Which piping or tubing material may NOT be used on this system?

    Answer: Type L copper tubing conforming to ASTM B88

    Sections 403.4.3 and 403.5.3 prohibit copper and copper alloy pipe or tubing where the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 standard cubic feet. At 0.4 grains the limit is exceeded, so copper is out. Steel and stainless steel are not restricted by this rule.

    Reference: 2018 International Fuel Gas Code, Section 403.5.3

  4. A building has an 80,000 Btu/h furnace, a 40,000 Btu/h water heater and a 65,000 Btu/h range, all on natural gas rated at 1,000 Btu per cubic foot. What is the total gas demand in cubic feet per hour (cfh)?

    Answer: 185 cfh

    Section 402.2 bases sizing on the sum of the maximum input of the appliances served. 80,000 + 40,000 + 65,000 = 185,000 Btu/h, and 185,000 Btu/h / 1,000 Btu per cubic foot = 185 cfh. 120 cfh leaves out the range; the other values misplace the decimal.

    Reference: 2018 International Fuel Gas Code, Section 402.2

  5. A propane-fired heater is rated at 100,000 Btu/h. If the propane heating value is taken as 2,500 Btu per cubic foot, what is its fuel use at full input?

    Answer: 40 cfh

    cfh = Btu/h / Btu per cubic foot = 100,000 / 2,500 = 40 cfh. Propane carries about two and a half times the heat of natural gas per cubic foot, so the flow is less than the 100 cfh a natural gas unit of the same input would use at 1,000 Btu/ft3.

    Reference: 2018 International Fuel Gas Code, Section 402.2

  6. Which type of venting system does the code require for a Category IV appliance?

    Answer: The system specified or furnished by the appliance manufacturer

    Table 503.4 says Category II, III and IV appliances use the venting system specified or furnished by the manufacturer of the listed appliance (Sections 503.4.1 and 503.4.2). Category I appliances are the ones that may use Type B vent, chimneys or single-wall pipe. Condensate must also be collected and disposed of under 503.9.

    Reference: 2018 International Fuel Gas Code, Table 503.4; Section 503.9

  7. A single-wall vent connector serves a draft hood appliance and connects to a gas vent that is 12 feet tall. What is the maximum horizontal length of the connector, assuming no engineered system?

    Answer: 9 feet

    Section 503.10.8 limits the horizontal length of a single-wall connector to 75 percent of the height of the vent: 0.75 x 12 = 9 feet. A Type B double-wall connector is allowed 100 percent (12 feet in this case), so 12 feet is a mix-up of the two rules.

    Reference: 2018 International Fuel Gas Code, Section 503.10.8

  8. Rooms communicate with an appliance space to supply indoor combustion air. The appliances total 150,000 Btu/h. What is the minimum free area of each of the two permanent openings between spaces on the same story?

    Answer: 150 square inches

    Section 304.5.3.1 requires each opening to have 1 square inch of free area per 1,000 Btu/h of total input, but not less than 100 square inches. 150,000 / 1,000 = 150 square inches. One opening must start within 12 inches of the top and the other within 12 inches of the bottom of the enclosure.

    Reference: 2018 International Fuel Gas Code, Section 304.5.3.1

  9. A combustion air opening needs 36 square inches of net free area. The opening will be covered with a wood louver whose free area is not known. What minimum louver size must be provided?

    Answer: 144 square inches

    Section 304.10 says the opening is sized on net free area, and where the louver's free area is unknown, wood louvers are assumed to have 25 percent free area and metal louvers or grilles 75 percent. 36 / 0.25 = 144 square inches. A metal louver would need 36 / 0.75 = 48 square inches.

    Reference: 2018 International Fuel Gas Code, Section 304.10

  10. What is the minimum size of the level service space required at the front or service side of a gas appliance located in an attic, and the minimum solid flooring width of the passageway?

    Answer: 30 inches deep by 30 inches wide; 24 inches of flooring

    Section 306.3 requires a level service space at least 30 inches deep and 30 inches wide at the front or service side of the appliance, and continuous solid flooring at least 24 inches wide in the passageway. The passageway must be at least 30 inches high, 22 inches wide and not more than 20 feet long (50 feet if 6 feet high for its entire length).

    Reference: 2018 International Fuel Gas Code, Section 306.3

Sources

Questions last verified November 16, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.