Connecticut licensing exam

Connecticut F-1 Unlimited Fire Sprinkler Contractor Exam: Practice Test & Licensing Guide

The PSI trade exam for Connecticut's F-1 unlimited fire sprinkler contractor license: 90 questions covering NFPA fire sprinkler, standpipe, pump and inspection standards. Open book.

Questions
90
Time limit
3 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Fire Sprinkler Systems (13, 13R, 13D)

An ordinary hazard room is 52 ft long, and the maximum allowable spacing between sprinklers along the branch line is 15 ft. With sprinklers evenly spaced and each end sprinkler half a space from its wall, what is the fewest sprinklers that can be used on that branch line?

Requirements at a glance

AgencyConnecticut Department of Consumer Protection (DCP); exams by PSI
ExperienceSatisfactory evidence of education and experience in fire protection sprinkler systems work (CGS 20-334a(c)(1)); age 18
ExamsF-1 fire sprinkler exam: 90 questions, 3 hours, 70%, plus the Business and Law exam
Books allowedNFPA 11, 11A, 12, 13, 13D, 13R, 14, 15, 16, 17, 17A, 20, 22, 24, 25, 45, 96, 101, 170, 230 and 2001, in the editions on the PSI bulletin
Fees$59 per PSI exam portion; DCP $150 application fee (CGS 20-333) and $150 initial license fee (CGS 20-335); renews yearly for $150

Fire sprinkler contractors with the education and experience the Department of Consumer Protection requires for an F-1 license (CGS 20-334a(c)).

How to get licensed, step by step

  1. Confirm you qualify

    Contractor licenses need at least 2 years as a licensed journeyperson (or equivalent experience and training DCP accepts), plus both the Business and Law exam and the trade exam.

    Connecticut DCP: trade license examinations (opens in a new tab)Connecticut General Statutes Chapter 393 (trade licensing) (opens in a new tab)

  2. Apply to DCP

    DCP decides whether you are eligible to test. Once approved, you contact PSI to pay and schedule.

    Connecticut DCP: trade license examinations (opens in a new tab)

  3. Pass both exam portions with PSI

    Both are open book at $59 each. You can test as often as needed for up to one year from your eligibility date. A passing Business and Law score counts for 2 years toward another contractor license.

    Schedule with PSI (Connecticut occupational licenses) (opens in a new tab)

  4. Get licensed

    Send DCP your passing score report or reports with the license fee shown on it.

    Connecticut DCP: trade license examinations (opens in a new tab)

How to prepare

  • Bring the exact editions on PSI's list. You can highlight, underline, annotate and index them with permanent tabs, but you can't write in them during the exam and Post-It notes are not allowed.
  • The PSI fire sprinkler exams are based on the NFPA editions on the bulletin (usually two editions of each standard, such as NFPA 13 2002 or 2013). Study from the edition you will bring, and check the bulletin for your test date.
  • Sprinkler system design and installation (NFPA 13, 13R and 13D) is 35 of 90 questions. Learn hydraulic calculations, hangers, spacing and the 13D and 13R occupancy limits.
  • General knowledge and regulations (NFPA 101 and 170) is 11; wet and dry chemical systems 12; standpipes (14) and inspection, testing and maintenance (25) are 7 each.
  • Fire pumps (NFPA 20), private service mains (24) and tanks (22) add 12 more.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from NFPA 13. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

  • NFPA 13, 13D and 13R: Installation of Sprinkler Systems, 2002 or 2013Essential

    Allowed in the exam room. Over a third of the F-1 and F-2 exams (35 questions).

    NFPA store (opens in a new tab)NFPA free online access (opens in a new tab)

  • NFPA 25: Inspection, Testing and Maintenance of Water-Based Fire Protection Systems, 2002 or 2014

    Allowed in the exam room. Source for the inspection, testing and maintenance questions.

    NFPA store (opens in a new tab)

  • NFPA 14, 20, 22, 24, 96, 101, 170 and 230 and the chemical and foam standards (11, 12, 15, 16, 17, 17A, 45, 2001)

    Allowed in the exam room, in the editions on the PSI bulletin. Standpipes, pumps, tanks, private mains, kitchens, life safety, symbols, storage and special-hazard systems.

    NFPA store (opens in a new tab)

Official reference list (as published by the testing agency)
  • NFPA 13: Installation of Sprinkler Systems, 2002 or 2013 (allowed in the exam room)
  • NFPA 13D (one- and two-family dwellings and manufactured homes) and NFPA 13R (residential occupancies up to four stories), each 2002 or 2013 (allowed in the exam room)
  • NFPA 14: Standpipe, Private Hydrant and Hose Systems, 2003 or 2013 (allowed in the exam room)
  • NFPA 20: Stationary Pumps for Fire Protection, 2002 or 2013; NFPA 22: Water Tanks for Private Fire Protection, 2003 or 2013; NFPA 24: Private Fire Service Mains, 2002 or 2013 (allowed in the exam room)
  • NFPA 25: Inspection, Testing and Maintenance of Water-Based Fire Protection Systems, 2002 or 2014 (allowed in the exam room)
  • NFPA 96: Ventilation Control and Fire Protection of Commercial Cooking Operations, 2001 or 2014 (allowed in the exam room)
  • NFPA 101: Life Safety Code, 2003 or 2012; NFPA 170: Fire Safety Symbols, 2002 or 2012; NFPA 230: Fire Protection of Storage, 1999 or 2003 (allowed in the exam room)
  • NFPA 11 (2002 or 2010), 11A (1999), 12 (2000 or 2011), 15 (2001 or 2012), 16 (2003 or 2011), 17 (2002 or 2013), 17A (2002 or 2013), 45 (2003 or 2011) and 2001 (2004 or 2012) (allowed in the exam room)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
Fire Sprinkler Systems (13, 13R, 13D)35
Fire Sprinkler Wet and Dry Chemical Systems (17, 17a, 11, 11a, 12, 15, 16, 2001)12
Fire Sprinkler Standpipe (14)7
Fire Protection Storage (230)3
Commercial Kitchen Equipment (96)3
Inspection, testing and maintenance (25)7
General Knowledge and Regulations (170, 101)11
Fire Pumps (20)5
Tanks (22)3
Private Service Mains (24)4

Exam day details

  • Administered by PSI Services for the Connecticut Department of Consumer Protection.
  • Fee: $59 to PSI per exam portion. DCP license fees are separate.
  • 90 questions in 3 hours; 70% to pass. Open book.
  • The license covers fire protection sprinkler systems work (CGS 20-330 and 20-334a).
  • Connecticut's PSI fire sprinkler exams are based on the NFPA editions listed in the bulletin (updated 2/4/2026), usually a pair of editions per standard. Check the bulletin for your test date.
  • This exam uses the NFPA editions the bulletin lists, which are older than the editions adopted in the current State Fire Code; study the edition on your bulletin.
  • Open book: bring your own copies of the allowed references. You may highlight, underline, annotate and index them beforehand, but not write in them during the exam. Permanent tabs only; Post-It notes are not allowed.
  • Use a silent, nonprinting, non-programmable calculator. For code questions the exam is based only on the edition of the code book listed in the bulletin.
  • Candidates may test as often as needed for up to one year from the date of eligibility. Contractor exam portions (business and trade) are each valid for 2 years from the date passed.
  • Contractor and dealer licenses need two portions: the Business and Law exam and the trade exam. Journeyperson licenses need only the trade exam.

Frequently asked questions

What's on the Connecticut F-1 exam?

90 questions: sprinkler systems (NFPA 13, 13R, 13D) 35, wet and dry chemical systems 12, general knowledge and regulations 11, standpipes 7 and inspection, testing and maintenance 7, then pumps, private service mains, storage, kitchen equipment and tanks.

Is the F-1 open book?

Yes. You may bring the allowed references listed on the PSI bulletin, tabbed with permanent tabs, and use a silent, non-programmable calculator.

Do I also need the Business and Law exam?

Yes. Contractor licenses need both the Business and Law exam and the F-1 trade exam.

Free questions with answers

Show all 10 free questions and answers
  1. An ordinary hazard room is 52 ft long, and the maximum allowable spacing between sprinklers along the branch line is 15 ft. With sprinklers evenly spaced and each end sprinkler half a space from its wall, what is the fewest sprinklers that can be used on that branch line?

    Answer: 4 sprinklers

    With n evenly spaced sprinklers and half a space at each wall, the spacing is 52 / n. Three sprinklers give 52 / 3 = 17.3 ft, over the 15 ft maximum. Four give 52 / 4 = 13 ft, and each end sprinkler is 6.5 ft from the wall, within the one-half of 15 ft = 7.5 ft limit of 8.6.3.2.1. Seven comes from dividing 52 by the 7.5 ft wall distance.

    Reference: NFPA 13 (2002), 8.6.3.2.1

  2. Under NFPA 17 (2002), what is the maximum force a manual actuator on a dry chemical system may require to operate it?

    Answer: 40 lb

    Section 4.4.2.1 limits manual actuators to a force of no more than 40 lb, and 4.4.2.2 limits their travel to no more than 14 in. Section 4.4.2.3 requires operating instructions on every manual actuator.

    Reference: NFPA 17 (2002), 4.4.2.1; 4.4.2.2

  3. A building has five Class I standpipes and is protected throughout by an approved automatic sprinkler system. What is the maximum total standpipe system flow rate that must be provided, using the 500 gpm plus 250 gpm per additional standpipe rule?

    Answer: 1,000 gpm

    Without a cap: 500 + 4 x 250 = 1,500 gpm. Section 7.10.1.1.3 limits the total to 1,250 gpm, or 1,000 gpm for buildings sprinklered throughout, so 1,000 gpm governs. The 1,250 gpm cap would apply to a building without full sprinkler protection.

    Reference: NFPA 14 (2003), 7.10.1.1.3

  4. Unless another standard or special sprinkler listing requires more, what is the minimum clearance between sprinkler deflectors and the top of storage under NFPA 13 (2002)?

    Answer: 18 in.

    Section 8.5.6.1 requires 18 in. or more between the deflector and top of storage. Where other standards specify greater clearances they govern (8.5.6.2), special sprinklers may use 36 in. (8.5.6.3) and rubber tire storage requires at least 3 ft (8.5.6.5).

    Reference: NFPA 13 (2002), 8.5.6.1

  5. Under NFPA 96, how often must the exhaust system of a high-volume cooking operation (24-hour, charbroiling or wok cooking) be inspected for grease buildup?

    Answer: Quarterly

    The NFPA 96 Schedule of Inspection for Grease Buildup (Table 11.4) sets monthly inspection for systems serving solid fuel cooking, quarterly for high-volume cooking such as 24-hour cooking, charbroiling or wok cooking, semiannually for moderate-volume cooking and annually for low-volume cooking such as churches, day camps, seasonal businesses and senior centers. Later editions keep the same schedule as Table 12.4.

    Reference: NFPA 96 (2017 text), Table 11.4 (Table 12.4 in 2021 and later)

  6. What is the minimum temperature NFPA 20 requires a pump room or pump house to be maintained above, where heat is required?

    Answer: 40 F

    Section 4.13.3.1 requires an approved or listed source of heat to keep a pump room or pump house above 40 F (4 C) where required. NFPA 25 also uses 40 F as the minimum for valve rooms and buildings with wet pipe systems.

    Reference: NFPA 20 (2016 text; bracket 2013), 4.13.3.1

  7. An ordinary hazard sprinkler system is supplied only by a gravity tank. The sprinkler demand is 225 gpm, and the designer applies the lower end of the 60 to 90 minute duration with a central station waterflow alarm. What minimum usable tank volume is required?

    Answer: 13,500 gal

    Where tanks supply sprinklers only, no inside or outside hose allowance is required (11.2.3.1.3), so the demand is just 225 gpm. Volume = 225 gpm x 60 min = 13,500 gal. Adding the 250 gpm hose allowance would give 28,500 gal, using 90 minutes gives 20,250 gal and 30 minutes gives 6,750 gal.

    Reference: NFPA 13 (2002), 11.2.3.1.3; Table 11.2.3.1.1

  8. The local maximum frost penetration depth is 42 in. At what minimum depth below grade must the top of an underground fire service main be buried under NFPA 13 (2002)?

    Answer: 54 in.

    Section 10.4.1 bases cover on the maximum frost penetration, and 10.4.2 requires the top of the pipe to be at least 1 ft below the frost line: 42 + 12 = 54 in. Where frost is not a factor, cover is at least 2-1/2 ft (10.4.3).

    Reference: NFPA 13 (2002), 10.4.1; 10.4.2

  9. How often must valve supervisory switches be tested under NFPA 25 (2002)?

    Answer: Semiannually

    Section 12.3.3.5.1 requires valve supervisory switches to be tested semiannually. The switch must send a distinctive signal within the first two revolutions of a hand wheel or one-fifth of valve stem travel (12.3.3.5.2), and the signal may not restore until the valve is in the normal position (12.3.3.5.3).

    Reference: NFPA 25 (2002), 12.3.3.5.1; 12.3.3.5.2

  10. A building story has a calculated occupant load of 650. What is the minimum number of means of egress NFPA 101 (2003) requires from that story?

    Answer: Three

    Section 7.4.1.2 requires not less than 3 means of egress where the occupant load is more than 500 but not more than 1000, and 4 where it is over 1000. Two is the minimum for any story (7.4.1.1) with a load of 500 or less unless an occupancy chapter permits one.

    Reference: NFPA 101 (2003), 7.4.1.1; 7.4.1.2

Sources

Questions last verified November 16, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.