Texas licensing exam

Texas Master Electrician Exam: Practice Test & Licensing Guide

TDLR's two-part Master Electrician exam on the 2026 NEC: 75 NEC Knowledge items and 33 calculations, 70% on each.

Questions
108
Time limit
5.333333333333333 hours
Passing score
70% per part

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Service and Transformer Calculations

Using the optional method for a one-family dwelling, find the general load (before adding heating or air-conditioning) for a 2,000 sq ft home with two small-appliance circuits, one laundry circuit, a 12 kW range, a 5 kW dryer, a 4.5 kW water heater and a 1.2 kW dishwasher.

Requirements at a glance

License before thisJourneyman Electrician, held for at least 2 years
Experience12,000 hours of on-the-job training under a Texas master electrician
ExamTwo parts: NEC Knowledge (75 items, 150 min) + Calculations (33 items, 170 min), 70% on each
Code book2026 NEC (soft-bound, publisher tabs only)
Fees$45 TDLR application + $78 PSI exam (both parts)

Journeyman electricians who have held the license for at least two years and have 12,000 hours of on-the-job training under a Texas master electrician.

How to get licensed, step by step

  1. Hold a journeyman license for 2 years

    Journeyman Industrial Electrician time doesn't count toward the master license.

  2. Apply to TDLR

    Mail the Master Electrician application with Experience Verification Forms for 12,000 hours, plus the $45 fee. If you held a municipal master license, you can verify your own hours for those years.

    TDLR: apply for a Master Electrician license (opens in a new tab)

  3. Schedule with PSI

    After TDLR approves you, schedule both parts. You have one year from your application to pass.

    Schedule with PSI (TDLR exams) (opens in a new tab)PSI candidate bulletin (2026 NEC) (opens in a new tab)

  4. Pass both parts

    NEC Knowledge (75 items, 150 minutes) and Calculations (33 items, 170 minutes), 70% on each.

    TDLR: electrician exam information (opens in a new tab)

How to prepare

  • Bring your own soft-bound 2026 NEC. You can highlight and write notes in it beforehand, but only publisher-made permanent tabs are allowed: no homemade tabs, no NEC Handbook, no loose paper.
  • Use the 2026 NEC. The exam switched editions on September 1, 2026, and some articles moved (for example, load calculations are now in Article 120). Study guides written for the 2023 NEC will send you to the wrong place.
  • Practice each part under its own clock. Time doesn't carry over from the NEC Knowledge part to the Calculations part, and you must pass both.
  • Read the bulletin's rules: assume copper conductors and ignore code exceptions and optional calculation methods unless the question tells you to use them.
  • Calculations are where most people fail (19% of attempts passed in fiscal 2025). Service and transformer (8) and motor (6) calculations are almost half of that part: drill Article 120 load calculations, transformer protection in Article 450 and the Article 430 motor tables.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2026 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (NEC), 2026 Edition (bring your own soft-bound copy)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
NEC Knowledge(75 items, 70 scored · 150 min)
Definitions, Theory and Plans7
Services, Service Equipment and Separately Derived Systems11
Feeders4
Branch Circuits and Conductors11
Wiring Methods and Materials7
Equipment and Devices8
Motors and Generators7
Control Devices and Disconnecting Means3
Special Occupancies, Equipment and Conditions8
Renewable Energy (PV and EV Charging)4
Calculations(33 items, 30 scored · 170 min)
Electrical Theory Calculations2
Service and Transformer Calculations8
Feeder Calculations3
Branch Circuit and Conductor Calculations4
Raceway Calculations2
Equipment and Appliance Calculations2
Motor and Generator Calculations6
Disconnecting Means Calculations1
RV, Mobile Home and Marina Calculations1
EV Charging Calculations1

The parts are timed and scored separately, and you must pass each one. Our simulations score each part the same way and give you the combined time (320 minutes).

Exam day details

  • Administered by PSI Services for the Texas Department of Licensing and Regulation (TDLR).
  • Fee: $78 for both parts (PSI), plus TDLR's $45 application fee. Retakes are $78.
  • Since September 1, 2026 the exam is based on the 2026 NEC.
  • Two parts: NEC Knowledge (75 items, 5 unscored, 150 minutes) and Calculations (33 items, 3 unscored, 170 minutes). Unused time doesn't carry over, and you must score 70% on each part.
  • Open book with the same rules as the journeyman exam: your own soft-bound NEC, highlighted or noted beforehand, publisher tabs only, no NEC Handbook.
  • Unless a question says otherwise, all conductors are copper, and you shouldn't apply code exceptions or optional calculation methods.
  • In TDLR's fiscal year 2025, only 22% of NEC Knowledge attempts and 19% of Calculations attempts passed.
  • Journeyman Industrial Electrician experience doesn't count toward the master license.

Frequently asked questions

How many questions are on the Texas Master Electrician exam?

108 items in two parts: NEC Knowledge (75 items, 150 minutes) and Calculations (33 items, 170 minutes), with 8 unscored items in total. You need 70% on each part.

What's the pass rate for the Texas master electrician exam?

Low. In fiscal year 2025, about 22% of NEC Knowledge attempts and 19% of Calculations attempts passed (TDLR statistics). Service, transformer and motor calculations make up most of the Calculations part.

Who can take the Texas master electrician exam?

Journeyman electricians who have held the license for two years and have 12,000 hours of on-the-job training under a Texas master electrician.

Free questions with answers

Show all 10 free questions and answers
  1. Using the optional method for a one-family dwelling, find the general load (before adding heating or air-conditioning) for a 2,000 sq ft home with two small-appliance circuits, one laundry circuit, a 12 kW range, a 5 kW dryer, a 4.5 kW water heater and a 1.2 kW dishwasher.

    Answer: 17,280 VA

    Section 120.82(B): general lighting at 2 VA/sq ft = 4,000 VA; small-appliance and laundry circuits 3 x 1,500 = 4,500 VA; appliances at nameplate: 12,000 + 5,000 + 4,500 + 1,200 = 22,700 VA. Total = 31,200 VA. The 2026 optional method takes the first 8 kVA at 100% and the remainder at 40%: 8,000 + (23,200 x 0.40) = 8,000 + 9,280 = 17,280 VA. 18,480 VA uses the old 10 kVA first step, 19,280 VA uses both the old 10 kVA step and 3 VA/sq ft, and 31,200 VA applies no demand.

    Reference: 2026 National Electrical Code (NFPA 70), 120.82(B)

  2. A 25 hp, 460-volt, 3-phase squirrel-cage motor (not Design B energy-efficient) is protected by an inverse-time circuit breaker. What is the maximum standard breaker rating permitted under 430.52 before you apply any exception for starting current?

    Answer: 90 A

    Use the table FLC, not the nameplate (430.6(A)(1)). Table 430.250 gives 34 A for 25 hp at 460 V. Table 430.52(C)(1) allows an inverse-time breaker at 250%: 34 x 2.5 = 85 A. 85 A is not a standard size, so 430.52(C)(1)(a) lets you use the next higher standard rating, 90 A. 60 A is the dual-element fuse value (175% = 59.5 A, rounded up), and 85 A is the unrounded calculation.

    Reference: 2026 National Electrical Code (NFPA 70), Table 430.250; 430.52(C)(1) and Table 430.52(C)(1)

  3. Nine current-carrying 12 AWG THHN copper conductors run in one raceway through an area with an ambient temperature of 40°C (104°F). What is the adjusted ampacity of each conductor, before any termination or overcurrent limits are applied?

    Answer: 19.1 A

    Start with the 90°C column of Table 310.16: 12 AWG THHN = 30 A. Correction for 36-40°C at 90°C, Table 310.15(B)(1)(1): 0.91. Adjustment for 7-9 current-carrying conductors, Table 310.15(C)(1): 70%. 30 x 0.91 x 0.70 = 19.1 A. 21.0 A applies only the adjustment factor, 27.3 A applies only the temperature correction, and 16.8 A starts from the 75°C value (25 A) with both factors. Section 240.4(D) still limits the overcurrent device on 12 AWG to 20 A.

    Reference: 2026 National Electrical Code (NFPA 70), Table 310.16; Table 310.15(B)(1)(1); Table 310.15(C)(1)

  4. Under the 2026 NEC, where must the service disconnect for a new one-family dwelling be located (when no separate emergency disconnect complying with 225.41 is installed)?

    Answer: In a readily accessible outdoor location, on the dwelling or within sight of it

    The 2026 NEC deleted 230.85 and put a new location rule in 230.70(A)(1). For one- and two-family dwellings, the service disconnect must be in a readily accessible outdoor location, either on the dwelling or within sight of it (visible and not more than 50 ft away per 110.29). The exception applies only if an emergency disconnect is installed under 225.41. 'Nearest point of entrance' is now the rule in 230.70(A)(2) for buildings other than one- and two-family dwellings.

    Reference: 2026 National Electrical Code (NFPA 70), 230.70(A)(1)

  5. At a dwelling, an outdoor outlet supplies a 240-volt, single-phase, 60-ampere branch circuit to a hot-tub disconnect. Under 210.8(F) in the 2026 NEC, does this outlet require GFCI protection?

    Answer: Yes, it covers single-phase outdoor outlets up to 60 A

    The 2026 NEC raised the 210.8(F) threshold for dwelling outdoor outlets from 50 A to 60 A. All outdoor outlets supplied by single-phase branch circuits rated 150 volts or less to ground and 60 A or less need GFCI protection (other than those in 210.8(A) Exception No. 1 and lighting outlets). A 240-volt single-phase circuit is 120 volts to ground. The 50 A answer reflects the 2023 code.

    Reference: 2026 National Electrical Code (NFPA 70), 210.8(F)

  6. Equipment that monitors and controls power within a system to prevent overload of an electrical service, conductor or power distribution equipment is defined in the 2026 NEC as a(n):

    Answer: Power control system (PCS)

    Article 100 (2026) defines a Power Control System (PCS) as equipment that monitors and controls power within a system to prevent overload of a service, conductor, or distribution equipment. It also defines single-source PCS (load management only) and multisource PCS (can also control power production sources). Section 120.7 allows a PCS to be used in load calculations, with the control setting no greater than 80% of the monitored OCPD rating.

    Reference: 2026 National Electrical Code (NFPA 70), Article 100, Power Control System (PCS); 120.7

  7. Under 215.18(A) in the 2026 NEC, a surge-protective device is required on feeders supplying which of the following?

    Answer: Police station areas used only as sleeping quarters

    Section 215.18(A) requires SPDs on feeders that supply dwelling units, dormitories, guest rooms and suites of hotels, motels and dormitories, patient sleeping areas of nursing homes and limited-care facilities, and (new in 2026) areas used exclusively as sleeping quarters in fire, police, ambulance, rescue and ranger stations. Offices, retail spaces and classrooms are not listed.

    Reference: 2026 National Electrical Code (NFPA 70), 215.18(A)

  8. Cable ties are being used as the means of securing and supporting Type MC cable. Under 300.13(E) in the 2026 NEC, which cable tie type designations are evaluated for securement and support?

    Answer: Type 2S or 21S

    New 300.13(E)(1) requires cable ties used for securement and support of cable, flexible conduit, and flexible tubing to be listed and identified for that purpose. Under the Article 100 informational note, Types 1, 11, 2, 21, 2S and 21S are evaluated for cable management (bundling), but only Types 2S and 21S are also evaluated for securing and supporting. Cable tie fixing devices must likewise be listed and identified.

    Reference: 2026 National Electrical Code (NFPA 70), 300.13(E); Article 100, Cable Tie

  9. According to Table 430.52(C)(1), what is the maximum setting of an instantaneous-trip circuit breaker for a Design B energy-efficient (or Design BE) motor, before any exceptions?

    Answer: 1100%

    Table 430.52(C)(1) allows 1100% of FLC for instantaneous-trip breakers on Design B energy-efficient, Design B premium-efficiency, and (new in 2026) Design BE and CE motors. Most other AC motors are limited to 800%. 250% is the inverse-time breaker column, and 1700% is the most that 430.52(C)(3) allows for these motors only when the table setting won't carry the starting current.

    Reference: 2026 National Electrical Code (NFPA 70), Table 430.52(C)(1); 430.52(C)(3)

  10. At a commercial parking lot with permanently connected EVSE, where must the required EVSE emergency disconnect devices be installed under 625.43(D)?

    Answer: 20 ft to 100 ft from the equipment, readily accessible, in sight

    For other than one- and two-family dwellings, 625.43(D)(1) requires one or more clearly identified emergency disconnect devices for permanently connected EVSE and WPTE. They must be readily accessible, not less than 20 ft and not more than 100 ft from the equipment and in sight from it. They must disconnect all EVSE within sight, be manual-reset, open all ungrounded conductors at the same time, and be marked 'EVSE EMERGENCY DISCONNECT' with a warning that vehicles remain energized.

    Reference: 2026 National Electrical Code (NFPA 70), 625.43(D)(1)

Sources

Questions last verified October 7, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.