Philadelphia Journeyman Plumber Exam (ICC 250): Practice Test & Licensing Guide

ICC exam 250, Pennsylvania (Philadelphia) Journeyman Plumber: 75 closed-book questions on the Philadelphia Plumbing Code 2018 in 3 hours, with 25% on plan reading and analysis.

Questions
75
Time limit
3 hours
Passing score
70%
Books
Closed book
What to study ↓

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Plumbing Fixtures and Terminology

A cast-iron water closet floor flange is being installed. What minimum flange thickness and caulking depth does the code require?

Requirements at a glance

AgencyCity of Philadelphia Department of Licenses and Inspections; exam by ICC, delivered by Pearson VUE
ExamICC 250 Journeyman Plumber: 75 questions, 3 hours, CLOSED book
Experience4 years as a registered apprentice
Books allowedNone. The exam is closed book
Fees$115 to Pearson VUE; Philadelphia Journeyman license $126 (L&I pages, check current fees)

Plumbers applying for a Philadelphia Journeyman Plumber license, which requires a 4-year registered apprenticeship.

How to get licensed, step by step

  1. Check you qualify

    You need to have completed a 4-year registered apprenticeship.

    City of Philadelphia: Licenses and Inspections (opens in a new tab)

  2. Schedule exam 250 with Pearson VUE

    Book through Pearson VUE ($115). If you fail, wait 10 days to retake.

    Schedule with Pearson VUE (ICC exams) (opens in a new tab)ICC: Philadelphia Contractor/Trades Examination Information Bulletin (opens in a new tab)

  3. Pass and apply to L&I

    Send your results with your application and fee to Licenses and Inspections.

    City of Philadelphia: Licenses and Inspections (opens in a new tab)

How to prepare

  • Closed book: memorize the common fixture unit values, drain and vent sizes and trap rules.
  • Plan reading and analysis (25%), drainage (15%) and venting (15%) are over half of the exam.
  • The bulletin lists the Philadelphia Plumbing Code 2018. Philadelphia has adopted the 2021 I-Codes, so check the current bulletin before you test.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

What to study

This is a closed-book exam, so nothing comes into the exam room. Study from these:

  • Philadelphia Plumbing Code 2018 (2018 IPC with Philadelphia amendments)Essential

    NOT allowed in the exam room (closed book). Study it, because the whole exam comes from it.

    ICC store (opens in a new tab)

Official reference list (as published by the testing agency)
  • Philadelphia Plumbing Code 2018 (the exam is closed book; no references are allowed in the room)

What's on the exam

Official content outline from International Code Council (ICC), delivered by Pearson VUE (number of questions per topic):

TopicQuestions
Plumbing Fixtures and Terminology12
Plumbing Fundamentals and Administrative13
Traps, Interceptors, and Cleanouts5
Special Requirements4
Drainage Requirements15
Venting Requirements15
Water Distribution11
Plan Reading and Analysis25

The outline totals 100; the other items on the 75-question exam are unscored or unassigned.

Exam day details

  • Administered by International Code Council (ICC), delivered by Pearson VUE for the City of Philadelphia Department of Licenses and Inspections.
  • Fee: $115 to Pearson VUE. City of Philadelphia license fees are separate.
  • 75 questions in 3 hours. This is a CLOSED-book exam, so you must know the code without looking it up.
  • The bulletin lists the Philadelphia Plumbing Code 2018 (the 2018 IPC with Philadelphia amendments). Philadelphia adopted the 2021 I-Codes in 2025, but the March 2026 exam bulletin still names the 2018 code. TODO(verify): check the current ICC bulletin for a change before your test date.
  • Plan reading and analysis is 25% of the exam, with drainage and venting another 30%.
  • ICC writes the exam and Pearson VUE delivers it. Every question is four-option multiple choice with one correct answer.
  • If you fail, you must wait 10 days before you retake the exam.
  • The ICC Philadelphia bulletin does not print a passing score. TODO(verify): confirm the passing score with ICC before you sit.
  • Philadelphia's published exam results are valid for 12 months for applying, unless the code edition has changed.

Frequently asked questions

Is the Philadelphia journeyman plumber exam open book?

No. ICC lists exams 249 and 250 as closed book.

How many questions are on it?

75 questions in 3 hours.

What's on the exam?

Plan reading and analysis 25%, drainage 15%, venting 15%, plumbing fundamentals and administrative 13%, plumbing fixtures and terminology 12%, water distribution 11%, traps, interceptors and cleanouts 5% and special requirements 4%.

Free questions with answers

Show all 10 free questions and answers
  1. A cast-iron water closet floor flange is being installed. What minimum flange thickness and caulking depth does the code require?

    Answer: 0.25 inch thick with at least 2 inches of caulking depth

    Section 405.4.1 requires cast-iron or galvanized malleable iron floor flanges to be at least 0.25 inch thick with not less than a 2-inch caulking depth. Copper-alloy flanges may be 0.125 inch thick and plastic flanges must be 0.25 inch thick.

    Reference: Philadelphia Plumbing Code 2018 (IPC 2018 with Philadelphia amendments), 405.4.1

  2. A pipe passes through a foundation wall. What does the code require?

    Answer: A relieving arch or a sleeve two pipe sizes larger than the pipe

    Section 305.3 requires a pipe passing through a foundation wall to have a relieving arch or a pipe sleeve built into the wall, and the sleeve must be two pipe sizes greater than the pipe passing through.

    Reference: Philadelphia Plumbing Code 2018 (IPC 2018 with Philadelphia amendments), 305.3

  3. Which of the following traps is prohibited by the code for a new installation?

    Answer: An S trap

    Section P-1002.3 prohibits traps that depend on moving parts, bell traps, crown-vented traps, partition-type traps (with limited exceptions), S traps and drum traps. Philadelphia permits an S trap only as a direct replacement for a previously installed S trap.

    Reference: Philadelphia Plumbing Code 2018 (IPC 2018 with Philadelphia amendments), P-1002.3

  4. Under the Philadelphia amendment, what must be done before corrosive liquid waste enters the plumbing system when treatment is required?

    Answer: It must be thoroughly neutralized or treated before discharge

    Section P-803.1 notes that discharges to public sewers are regulated by the Philadelphia Water Department, which prohibits corrosive liquids that damage drains, sewers or sewage treatment. Where treatment is required, liquids may not enter the plumbing system without being thoroughly neutralized or treated.

    Reference: Philadelphia Plumbing Code 2018 (IPC 2018 with Philadelphia amendments), P-803.1

  5. What is the minimum slope for a horizontal drainage pipe that is 2 1/2 inches in diameter?

    Answer: 1/4 inch per foot

    Table P-704.1 requires 1/4 inch per foot for pipe 3 inches and smaller, 1/8 inch per foot for 4 through 6 inches, and 1/16 inch per foot for 8 inches and larger.

    Reference: Philadelphia Plumbing Code 2018 (IPC 2018 with Philadelphia amendments), Table P-704.1

  6. A 4-inch horizontal drain 40 feet long is laid at the minimum code slope. What is the minimum total fall over its length?

    Answer: 5 inches

    Table P-704.1 gives 1/8 inch per foot for 4- to 6-inch pipe: 40 ft x 1/8 in/ft = 5 inches. Using 1/4 inch per foot would give 10 inches, which is the slope for 3-inch and smaller pipe.

    Reference: Philadelphia Plumbing Code 2018 (IPC 2018 with Philadelphia amendments), Table P-704.1

  7. The vent system must protect fixture trap seals from a pressure differential greater than what?

    Answer: 1 inch of water column

    Section 901.2 requires the vent system to admit or release air so the seal of any fixture trap is not subjected to a pressure differential of more than 1 inch of water column.

    Reference: Philadelphia Plumbing Code 2018 (IPC 2018 with Philadelphia amendments), 901.2

  8. At what static pressure inside a building is a water pressure-reducing valve required?

    Answer: Above 80 psi

    Section P-604.8 requires an approved pressure-reducing valve with strainer where building water pressure exceeds 80 psi static, reducing it to not more than 80 psi. Service lines to sill cocks and outside hydrants are excepted.

    Reference: Philadelphia Plumbing Code 2018 (IPC 2018 with Philadelphia amendments), P-604.8

  9. A plan shows a 6-inch building drain running 80 feet at the minimum slope. What total fall is required?

    Answer: 10 inches

    Table P-704.1 gives 1/8 inch per foot for 4- to 6-inch drains: 80 ft x 1/8 in/ft = 10 inches. Using 1/4 inch per foot gives 20 inches, and 1/16 inch per foot (5 inches) applies to 8-inch and larger pipe.

    Reference: Philadelphia Plumbing Code 2018 (IPC 2018 with Philadelphia amendments), Table P-704.1

  10. A house plan shows two bathroom groups (1.6 gpf water closets), one kitchen sink with a dishwasher, and one residential clothes washer on the same building drain. Using Table 709.1, what is the total drainage fixture unit load?

    Answer: 14 dfu

    Table 709.1 rates a bathroom group at 5 dfu with a 1.6 gpf closet, a kitchen sink with dishwasher at 2 dfu and a residential clothes washer at 2 dfu: 5 + 5 + 2 + 2 = 14 dfu. 16 results from counting the dishwasher separately, and 10 leaves out the kitchen sink and washer.

    Reference: Philadelphia Plumbing Code 2018 (IPC 2018 with Philadelphia amendments), Table 709.1