New Hampshire licensing exam

New Hampshire Master Electrician Exam: Practice Test & Licensing Guide

The Prov exam for New Hampshire's master electrician license: 126 open-book questions in 5 hours, with a heavy section on the state's laws and rules plus NEC, motors, services and wiring methods. 70% to pass.

Questions
126
Time limit
5 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Administrative

According to Elec 305.01(d), which publication is the basis for the practical electrical installation questions on the examination?

Requirements at a glance

AgencyNew Hampshire Electricians' Board (OPLC); exam by Prov
Exam126 questions, 5 hours, open book, 70% to pass
Experience8,000 hours as an apprentice electrician and 600 hours of education (RSA 319-C:7)
Books allowed2020 NEC; Ugly's Electrical References (2020); NH Laws and Rules Elec 100-400 / RSA 319-C; American Electrician's Handbook 17th ed.; HB85 Ch. 157
Fees$90 to Prov; board application and license fees are separate

Electricians applying to the New Hampshire Electricians' Board for a master license. State law (RSA 319-C:7) calls for 8,000 hours as an apprentice electrician, at least 600 hours of education and a passing exam score.

How to get licensed, step by step

  1. Meet the apprenticeship and education requirements

    RSA 319-C:7 calls for 8,000 hours as a registered apprentice electrician and at least 600 hours of education that meet the board's criteria. The board can credit approved school courses or military experience.

    New Hampshire Electricians' Board (OPLC) (opens in a new tab)RSA 319-C (electricians) (opens in a new tab)

  2. Apply to the Electricians' Board

    Send the application and fee to the board (OPLC, Concord). Check the board's page for the current forms.

    New Hampshire Electricians' Board (OPLC) (opens in a new tab)

  3. Register and schedule with Prov

    Register at provexam.com/scheduler and choose "NH - New Hampshire Electrician Board" (4 New Hampshire centers, or remote through Examroom). If you fail, wait 30 days; there is no attempt limit. You can reschedule free up to 3 days ahead.

    Schedule with Prov (opens in a new tab)Prov: New Hampshire Electrician Board Candidate Information Bulletin (opens in a new tab)

  4. Get licensed

    Prov grades the exam immediately and sends your result to the board, which issues the license.

    New Hampshire Electricians' Board (OPLC) (opens in a new tab)

How to prepare

  • Administrative questions (25 of 126) come from the state's laws and rules; tab Elec 100-400 and RSA 319-C.
  • Motors and generators (19) and general electrical knowledge (21) are the next-largest sections.
  • New Hampshire's building code now adopts the 2023 NEC (concurrency period to Dec. 31, 2026), but the Prov bulletin lists only the 2020 NEC for the master exam. Confirm the edition before you buy a book.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2020 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

  • 2020 National Electrical Code (NEC), NFPA 70Essential

    Allowed in the exam room. Most of the electrician exam comes from it.

    NFPA (opens in a new tab)

  • Ugly's Electrical References, 2020

    Allowed in the exam room. Quick tables and formulas.

  • American Electrician's Handbook, 17th Edition

    Allowed in the exam room. Tables, formulas and theory for the electrician exams.

    McGraw Hill (opens in a new tab)

Official reference list (as published by the testing agency)
  • NFPA 70 National Electrical Code, 2020 (open book)
  • Ugly's Electrical References, 2020 (open book)
  • New Hampshire Laws and Rules Elec 100-400 and RSA 319-C (open book; printed copies allowed)
  • American Electrician's Handbook, 17th Edition, McGraw Hill (open book)
  • HB85 Chapter 157, New Hampshire amendment to the 2017 NEC (open book)

What's on the exam

Official content outline from Prov, Inc. (number of questions per topic):

TopicQuestions
General Electrical Knowledge21
Equipment for General Use9
Motors and Generators19
Control Devices5
Special Conditions2
Special Equipment2
Special Occupancies3
Services and Service Equipment12
Branch Circuits and Conductors6
Feeders8
Wiring Methods & Materials14
Administrative25

Exam day details

  • Administered by Prov, Inc. for the New Hampshire Office of Professional Licensure and Certification.
  • Fee: $90 to Prov. Board application and license fees are separate.
  • 126 questions in 5 hours; 89 correct (70%) to pass.
  • Open book: the references above are permitted in the exam room.
  • Register directly with Prov (choose "NH - New Hampshire Electrician Board"), then schedule at one of 4 New Hampshire test centers or remotely through Examroom.
  • If you fail, wait 30 days to retake. There is no limit on attempts. You can reschedule free up to 3 days before your appointment.

Note: New Hampshire's building code (RSA 155-A:1) now adopts the 2023 NEC, with a concurrency period to December 31, 2026, but the Prov bulletin (effective October 31, 2026) still lists the 2020 NEC for this exam. We follow the printed bulletin. Check the current bulletin before your test date.

Frequently asked questions

What's on the New Hampshire master electrician exam?

126 questions: administrative 25, general electrical knowledge 21, motors and generators 19, wiring methods and materials 14, services and service equipment 12, equipment for general use 9, feeders 8, branch circuits and conductors 6, control devices 5, special occupancies 3, and special conditions and special equipment 2 each.

How is it different from the journeyman exam?

It has 25 administrative questions on the state's laws and rules, against 9 on the journeyman exam, and runs 126 questions in 5 hours.

Which NEC edition is on the exam?

Prov's bulletin lists the 2020 NEC, even though the state building code now adopts the 2023 NEC. Check the current bulletin before you buy a book.

Free questions with answers

Show all 10 free questions and answers
  1. According to Elec 305.01(d), which publication is the basis for the practical electrical installation questions on the examination?

    Answer: The American Electricians Handbook published by McGraw-Hill, current edition

    Elec 305.01(d) says practical questions shall be based upon the American Electricians Handbook published by McGraw-Hill, in its current edition. NEC questions are drawn from the edition adopted under RSA 155-A:1, IV (Elec 305.01(a)), not from a handbook.

    Reference: New Hampshire Administrative Rules, Elec 100-400, Elec 305.01(a) and (d)

  2. Overhead service conductors attach to the side of a building. Regardless of other clearances, what is the lowest height above finished grade permitted for the point of attachment under 230.26?

    Answer: 10 ft

    230.26 requires the point of attachment to provide the clearances of 230.9 and 230.24, and in no case to be less than 3.0 m (10 ft) above finished grade. Higher attachment points may be needed so the drop meets 230.24(B), such as 12 ft over residential driveways or 18 ft over streets subject to truck traffic, but 10 ft is the absolute floor.

    Reference: NFPA 70, National Electrical Code (NEC), 2020 edition, 230.26; 230.24(B)

  3. A built-in trash compactor in a New Hampshire dwelling is cord-and-plug connected under NEC 422.16(B)(2). What cord length, measured from the face of the attachment plug to the plane of the rear of the appliance, is allowed for a trash compactor?

    Answer: 3 ft to 4 ft

    422.16(B)(2) allows a trash compactor cord of 0.9 m to 1.2 m (3 ft to 4 ft) measured to the plane of the rear of the appliance, with the receptacle in the space occupied by the appliance or adjacent to it. A built-in dishwasher is permitted a longer cord, 3 ft to 6.5 ft, and its receptacle goes in the adjacent space.

    Reference: New Hampshire 2020 NEC Amendments (OPLC Electricians' Board bulletin; NFPA 70, 2020 edition, as amended, eff. July 1, 2022), Amend Section 422.16(B)(2) (EL-20-16-21)

  4. A New Hampshire building has a 208Y/120-volt system and a 480Y/277-volt system, and branch circuits are supplied from both. Under the amended NEC 210.5(C)(1), how must the method used to identify ungrounded conductors be documented at each branch-circuit panelboard?

    Answer: Documented in a readily available way, or posted on a durable label that is not handwritten

    Amended 210.5(C)(1) (EL-20-01-21) applies when branch circuits come from more than one nominal voltage system; New Hampshire strikes the words 'phase or line and' so each ungrounded conductor is identified by system at all termination, connection and splice points. Under (C)(1)(b), unchanged, the method for conductors originating in a panelboard must be documented in a readily available manner or permanently posted at the panelboard, and the label must be durable and not handwritten.

    Reference: New Hampshire 2020 NEC Amendments (OPLC Electricians' Board bulletin; NFPA 70, 2020 edition, as amended, eff. July 1, 2022), Amend Section 210.5(C)(1) (EL-20-01-21)

  5. Under amended NEC 334.10(3) in New Hampshire, how must Type NM cable generally be concealed in a nondwelling structure permitted to be of Type III, IV or V construction?

    Answer: Behind a thermal barrier with at least a 15-minute finish rating

    EL-20-13-21 revises 334.10(3): in other structures permitted to be of Types III, IV and V construction, NM cable must, except as permitted by 334.10(6), be concealed within walls, floors or ceilings that provide a thermal barrier of material with at least a 15-minute finish rating as identified in listings of fire-rated assemblies. Exposed runs are allowed only in the places listed in amended 334.10(6), such as accessible attics or unfinished basements. Multifamily dwellings fall under 334.10(2), which carries no such concealment condition.

    Reference: New Hampshire 2020 NEC Amendments (OPLC Electricians' Board bulletin; NFPA 70, 2020 edition, as amended, eff. July 1, 2022), Amend Section 334.10(3) (EL-20-13-21)

  6. A 20-hp, 460-volt, three-phase squirrel-cage motor has a Table 430.250 full-load current of 27 amperes. What is the minimum ampacity of the branch-circuit conductors for this continuous-duty motor?

    Answer: 33.75 amperes

    430.22(A) requires conductors for a single motor to have an ampacity of at least 125 percent of the full-load current from the table: 27 x 1.25 = 33.75 A. Using the table value alone (27 A) leaves out the factor, 31.05 A uses 115 percent (the disconnect rule), and 40.5 A uses 150 percent.

    Reference: NFPA 70, National Electrical Code (NEC), 2020 edition, 430.22(A); Table 430.250

  7. Under 430.75(A), what must be true when the disconnecting means for a motor controller is in the open position?

    Answer: The motor control circuit is disconnected from all sources of supply

    430.75(A) requires motor control circuits to be arranged so they are disconnected from all sources of supply when the disconnecting means is in the open position. The disconnect may be two or more devices, one for the motor and controller and one for the control circuit, as long as they are immediately adjacent to each other.

    Reference: NFPA 70, National Electrical Code (NEC), 2020 edition, 430.75(A)

  8. A feeder will carry 80 amperes of continuous load and 70 amperes of noncontinuous load. The overcurrent device is not listed for operation at 100 percent of its rating and all terminations are rated 75 degrees C. What is the smallest copper THWN conductor, using Table 310.16?

    Answer: 2/0 AWG

    215.2(A)(1) requires an ampacity of at least the noncontinuous load plus 125 percent of the continuous load: 70 + (80 x 1.25) = 170 A. In the 75 degrees C copper column, 1/0 AWG is 150 A (too small) and 2/0 AWG is 175 A. 3/0 AWG (200 A) comes from 125 percent of the whole 150 A (187.5 A).

    Reference: NFPA 70, National Electrical Code (NEC), 2020 edition, 215.2(A)(1); Table 310.16

  9. Which wiring method does Article 501 permit for general use in a Class I, Division 1 location?

    Answer: Threaded rigid metal conduit or threaded intermediate metal conduit

    501.10(A)(1) permits threaded rigid metal conduit or threaded intermediate metal conduit, Type MI cable with approved fittings, and certain listed cable types such as MC-HL. EMT, NM cable and nonmetallic flexible conduit are not on the Division 1 list.

    Reference: NFPA 70, National Electrical Code (NEC), 2020 edition, 501.10(A)(1)

  10. A 480-volt resistance heating element draws 24 amperes. What is its resistance?

    Answer: 20 ohms

    Ohm's law gives R = E / I = 480 / 24 = 20 ohms. 0.05 ohm is I / E inverted, 11,520 ohms multiplies voltage and current (which is watts), and 10 ohms is the result of using 240 volts.

    Reference: General electrical theory, Ohm's law, R = E / I

Sources

Questions last verified November 17, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.