Montana licensing exam

Montana Journeyman Electrician Exam: Practice Test & Licensing Guide

The PSI exam for a Montana journeyman electrician license: 60 questions on the National Electrical Code and general trade knowledge and theory. Open book, 70% to pass.

Questions
60
Time limit
3 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10National Electrical Code

Under the Article 100 definition, what makes a load a continuous load when sizing a branch circuit for a heated stock-water trough?

Requirements at a glance

AgencyMontana State Electrical Board (Department of Labor and Industry); exams by PSI
ExperienceDocumented on your Board application. See the Board site for the hours required for this license.
Exam60 questions, 3 hours, 70%
Books allowedNEC (tabs and indexes), Montana Building Codes Amendments and a non-programmable calculator
Fees$75 to PSI (non-refundable, valid one year), plus Board application and license fees

Electricians applying to the Montana State Electrical Board for a journeyman license after documenting their experience.

How to get licensed, step by step

  1. Apply to the Board

    Send the Montana State Electrical Board your application and documentation of your experience.

    Montana State Electrical Board (opens in a new tab)

  2. Wait for your admission letter

    When the Board approves you, it mails or e-mails an admission letter. You can't schedule before then.

    Montana State Electrical Board (opens in a new tab)

  3. Pay and schedule with PSI

    Register at PSI online or call 855-746-8173. If you fail once you can retest right away; after a second failure you need an 8-hour Board-approved code seminar before a third try.

    Schedule with PSI (Montana electrical) (opens in a new tab)PSI: Montana electrical exam bulletin (opens in a new tab)

  4. Pass and get licensed

    Send the Board your results and fees to receive your license.

    Montana State Electrical Board (opens in a new tab)

How to prepare

  • Check the NEC edition on the current PSI bulletin before you buy a book. The bulletin lists the 2020 NEC, while Montana's code list shows the 2023 NEC effective September 26, 2026.
  • Bring the Montana Building Codes Amendments with your NEC. Tabs and indexes are allowed, and highlights and notes made before the exam are fine; writing in your books during the exam is not.
  • A silent, non-programmable calculator is allowed. Calculators built for electrical estimating are not.
  • The exam has two areas: the NEC and general trade knowledge and theory. Tab Articles 100, 110, 210, 220, 230, 240, 250, 310, 314 and 430 and Chapter 9 tables.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the NEC and the Montana amendments. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • National Electrical Code (NFPA 70), 2020 edition per the PSI bulletin; tabs and indexes allowed (see the edition note in the details)
  • Montana Building Codes Amendments (ARM Title 24, Chapter 301)
  • Printreading by David L. Hittinger, based on the 2020 NEC (listed in the bulletin)
  • A silent, non-printing, non-programmable calculator (not an electrical-estimating calculator)

What's on the exam

Estimated topic weighting. No official breakdown is published:

TopicQuestions
National Electrical Code1
General Trade Knowledge & Theory1

Exam day details

  • Administered by PSI Services for the Montana State Electrical Board.
  • Fee: $75 to PSI, non-refundable and valid for one year. Board application and license fees are separate.
  • 60 questions plus a few unscored experimental items in 3 hours (180 minutes); 70% correct to pass.
  • The PSI bulletin (page dated 1/23/2026) lists the 2020 NEC and the Montana Building Codes Amendments, and titles the exams '2020'. DLI's code list shows the 2023 NEC taking effect in Montana on September 26, 2026. Check the current PSI bulletin for the edition on your test date.
  • Open book: bring your own NEC (tabs and indexes allowed), the Montana Building Codes Amendments and a silent, non-programmable calculator. Highlighting and notes in approved material before the exam are allowed; writing in your books during the exam is not.
  • PSI adds a small number of unscored experimental questions to each exam.
  • The Board approves your application first and mails or e-mails an admission letter; then you pay and schedule with PSI. Exam fees are non-refundable, non-transferable and valid for one year.
  • After a first failure you may reschedule with no waiting period. After a second failure you must show proof of an 8-hour Board-approved electrical code seminar before a third attempt.

Note: PSI does not publish a topic breakdown for this exam, so the topic split in our practice tests is an estimate.

Frequently asked questions

What's on the Montana journeyman electrician exam?

60 questions in two areas: the National Electrical Code, and general trade knowledge and theory. PSI does not publish how many questions come from each area.

Which NEC edition is on the Montana electrician exams?

The PSI bulletin lists the 2020 NEC. Montana's code list shows the 2023 NEC effective September 26, 2026, so confirm the edition in the current PSI bulletin before you buy a book.

Can I use a calculator?

Yes, a silent, non-printing, non-programmable calculator. Calculators designed for preprogrammed electrical calculations, such as the Electrical Estimate Pal, are not allowed.

Free questions with answers

Show all 10 free questions and answers
  1. Under the Article 100 definition, what makes a load a continuous load when sizing a branch circuit for a heated stock-water trough?

    Answer: The maximum current is expected to continue for 3 hours or more

    Article 100 defines a continuous load as one where the maximum current is expected to continue for 3 hours or more. Stock-tank heaters in a Montana winter easily qualify. The 1-hour and 6-hour figures are not in the definition, and a dedicated circuit does not by itself make a load continuous.

    Reference: NFPA 70 National Electrical Code (2020 and 2023 editions), Article 100, Definitions: Continuous Load

  2. A branch circuit in a stock-watering shed carries 24 A of continuous heater load plus 10 A of noncontinuous load. The breaker is not listed for 100% continuous operation. What is the minimum overcurrent device rating?

    Answer: 40 A

    Size the device at 125% of the continuous load plus 100% of the noncontinuous load: 24 x 1.25 = 30 A, plus 10 A = 40 A, and 40 A is a standard rating. 34 A is the plain sum with no 125% factor. 30 A leaves out the noncontinuous load. 45 A wrongly applies 125% to everything (34 x 1.25 = 42.5, rounded up).

    Reference: NFPA 70 National Electrical Code (2020 and 2023 editions), 210.20(A) (branch circuits); 215.3 (feeders)

  3. A 240-volt feeder to a machine shed panel carries a noncontinuous 80-ampere load. All terminations are rated 75 degrees C. Using THWN copper and Table 310.16, what is the smallest conductor?

    Answer: 4 AWG

    In the 75 degrees C copper column of Table 310.16, 4 AWG is rated 85 A, which covers the 80 A load. 6 AWG is only 65 A and 8 AWG only 50 A. 3 AWG (100 A) would work but is not the smallest.

    Reference: NFPA 70 National Electrical Code (2020 and 2023 editions), Table 310.16, 75 degrees C copper column

  4. A 50-ampere circuit is run with 90 degrees C THHN copper to a 60-ampere disconnect. Its terminals carry no marking above 60 degrees C. What is the smallest copper conductor permitted?

    Answer: 6 AWG

    Equipment rated 100 A or less with no higher marking limits the conductor to the 60 degrees C column (110.14(C)(1)). In that column 8 AWG carries only 40 A and 10 AWG 30 A, while 6 AWG carries 55 A and covers the 50 A load. 8 AWG is the trap: it is 55 A in the 90 degrees C column, but that column can't be used at the terminals.

    Reference: NFPA 70 National Electrical Code (2020 and 2023 editions), 110.14(C)(1); Table 310.16

  5. Eight current-carrying 10 AWG THHN copper conductors are run in one EMT raceway at 30 degrees C ambient. The 90 degrees C ampacity of 10 AWG is 40 A. What is the adjusted ampacity?

    Answer: 28 A

    Seven to nine current-carrying conductors require an adjustment factor of 70%, so 40 x 0.70 = 28 A. 32 A uses the 80% factor for 4 to 6 conductors and 20 A uses the 50% factor for 10 to 20 conductors. 40 A ignores the adjustment entirely.

    Reference: NFPA 70 National Electrical Code (2020 and 2023 editions), Table 310.15(C)(1)

  6. A 4,500-watt, 240-volt single-phase electric water heater in a ranch house is operating normally. How much current does it draw?

    Answer: 18.75 A

    Current equals power divided by voltage: 4,500 / 240 = 18.75 A. 37.5 A divides by 120 V, 10.8 A wrongly applies the three-phase factor (4,500 / (240 x 1.732)), and 21.6 A uses 208 V.

    Reference: Standard electrical theory (Ohm's law and power relationships), Ohm's law power formula I = P / E

  7. A 4,500-watt, 240-volt resistance heating element is connected to a 208-volt supply at a Montana school. Assuming the resistance stays constant, what power does it produce?

    Answer: 3,380 W

    Resistance R = E squared / P = 240 x 240 / 4,500 = 12.8 ohms. At 208 V, P = 208 x 208 / 12.8 = 3,380 W. Power varies with the square of voltage, so the linear estimate of 3,900 W (4,500 x 208/240) is wrong. 4,500 W ignores the voltage drop, and 4,160 W is 208 x 20.

    Reference: Standard electrical theory (Ohm's law and power relationships), Resistance and power formulas P = E squared / R

  8. An 8-ohm resistor is in series with a parallel pair of 12 ohms and 6 ohms, across a 120-volt source. What is the voltage across the parallel pair?

    Answer: 40 V

    The 12 ohm and 6 ohm resistors in parallel equal (12 x 6) / 18 = 4 ohms. Total resistance is 8 + 4 = 12 ohms, so I = 120 / 12 = 10 A. The parallel pair drops 10 x 4 = 40 V, and the 8 ohm resistor drops 80 V. Choosing 80 V picks the wrong part of the circuit.

    Reference: Standard electrical theory (Ohm's law and power relationships), Series-parallel circuit analysis

  9. A 5-horsepower motor is 85% efficient. At full load, approximately how many watts of electrical input does it need? (1 hp = 746 W)

    Answer: 4,388 W

    Output power is 5 x 746 = 3,730 W. Input = output / efficiency = 3,730 / 0.85 = 4,388 W. 3,730 W is the output, with no losses. 3,171 W multiplies by 0.85 instead of dividing, and 4,290 W adds 15% instead of dividing by 0.85.

    Reference: Standard electrical theory (Ohm's law and power relationships), Motor efficiency and horsepower conversion

  10. A balanced three-phase, 480-volt electric heater is rated 25 kW. What is the line current?

    Answer: 30.1 A

    For a three-phase load, I = P / (1.732 x E) = 25,000 / (1.732 x 480) = 30.1 A. 52.1 A forgets the 1.732 factor. 17.4 A divides by 1.732 a second time. 90.3 A divides by 277 volts (line-to-neutral) and also ignores the three-phase factor.

    Reference: Standard electrical theory (Ohm's law and power relationships), Three-phase power I = P / (1.732 x E)

Sources

Questions last verified October 27, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.