Minnesota Power Limited Technician Exam: Practice Test & Licensing Guide

The Minnesota DLI power limited technician exam: 80 questions on the 2026 NEC and technology circuits, open book with DLI-supplied references, 5.5 hours, 70% to pass.

Questions
80
Time limit
5.5 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Electrical Theory and Calculations

Three resistors of 6, 12 and 18 ohms are connected in series across a 72-volt supply. What is the voltage drop across the 12-ohm resistor?

Requirements at a glance

AgencyMinnesota Department of Labor and Industry (DLI); Board of Electricity sets the rules
ExperienceA 4-year electrical degree, or 36 months (6,000 hours) of power limited experience with at least 12 months installing; DLI-approved training can earn up to 12 months of credit
Exam80 questions, 5.5 hours, 70% to pass
Books allowedNone of your own: DLI supplies the 2026 NEC (without tabs), the laws-and-rules booklet and a calculator
Fees$50 per personal-license exam (Minn. Stat. 326B.092), plus application and license fees

Technicians who install and supervise Class 2, 3 and 4 technology systems (alarm, signaling, audio, communications and control) for a licensed technology system or electrical contractor.

How to get licensed, step by step

  1. Apply to DLI

    Send DLI your power limited technician application and proof of experience or education with the exam fee (believed $50; confirm with DLI). The license is held through a licensed technology system or electrical contractor.

    Minnesota Department of Labor and Industry (DLI) (opens in a new tab)DLI: electrical license basics (opens in a new tab)

  2. Schedule your exam

    After DLI approves your application, you schedule the exam in DLI's iMS system. DLI gives exams at its St. Paul office (Tuesday to Thursday) and at outstate sites including Duluth, Mankato, Rochester and St. Cloud.

    DLI: license exam schedule (opens in a new tab)

  3. Take the exam

    You have 5.5 hours and need 70%. The exam is open book with DLI-supplied references; no personal books, notes or electronic devices.

    DLI: electrical license basics (opens in a new tab)DLI Electrical License Examination Guide (PDF) (opens in a new tab)

  4. Results and retakes

    DLI mails results in about 2 weeks. If you fail, wait 30 days after receiving results before reapplying.

    DLI: license exam schedule (opens in a new tab)

How to prepare

  • Study the DLI Electrical License Examination Guide: it marks the NEC knowledge areas for the power limited technician (grounding and bonding, wiring methods, Class 1, 2 and 3 circuits, fire alarm, communications, theory and troubleshooting).
  • The 2026 NEC reorganized limited-energy work in Chapter 7, so confirm article numbers in the DLI-supplied code book. Our questions on those articles are concept level; Minnesota Statutes 326B.31 to 326B.399 and Rules 3800 are cited exactly.
  • Every DLI exam is open book, but with DLI-supplied references only: a code book without tabs, the DLI laws-and-rules booklet and a desk calculator. You cannot bring your own books, so practice finding answers fast rather than relying on tabs.
  • DLI publishes no topic weights, so our topic split is an estimate. Several versions of each exam are in use, and some questions ask for more than one answer or the choice that does not apply.
  • Drill Class 2 and 3 circuit rules, separation of power-limited and non-power-limited wiring, listing, grounding and bonding, and Minnesota licensing law (a power limited technician must work for a licensed contractor).
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (NEC), 2026 edition (Minnesota exams are based on the 2026 NEC from September 8, 2026; DLI supplies the code book)
  • Minnesota Statutes 326B.31 to 326B.399 and Minnesota Rules chapters 3800 and 3801 (in the DLI laws-and-rules booklet)

What's on the exam

Estimated topic weighting. No official breakdown is published:

TopicQuestions
Electrical Theory and Calculations8
General Requirements, Definitions and Working Space (NEC Articles 90 to 110)10
Overcurrent Protection and Grounding and Bonding (NEC Chapter 2)10
Wiring Methods and Materials (NEC Chapter 3)18
Equipment, Flexible Cords and Low-Voltage Lighting (NEC Chapter 4)6
Hazardous (Classified) Locations and Special Occupancies (NEC Chapter 5)6
Emergency Systems, Fire Alarm and Special Conditions (NEC Chapter 7)10
Class 1, 2 and 3 Remote-Control, Signaling and Power-Limited Circuits14
Communications, Antenna and Broadband Systems (NEC Chapter 8)8
Minnesota Statutes 326B and Rules 380010

Exam day details

  • Administered by the Minnesota Department of Labor and Industry (DLI), which gives its own exams.
  • Fee: $50 per personal-license exam (Minn. Stat. 326B.092). Application and license fees are separate.
  • 80 questions in 5.5 hours, open book with DLI-supplied references; 70% to pass (DLI Electrical License Examination Guide). DLI publishes no topic weights.
  • A power limited technician installs and supervises technology circuits and systems: Class 2, 3 and 4 circuits for control, signaling, alarm and audio, antenna and communication circuits, and low-voltage lighting on a Class 2 or 3 supply.
  • The license is not stand-alone: the holder must work for a licensed technology system or electrical contractor (or a registered employer on its own property). Unlicensed individuals may work under a power limited technician's supervision.
  • The 2026 NEC reorganized limited-energy work in Chapter 7; confirm article numbers in the code book DLI provides. Our questions are concept level for those articles.
  • Open book with DLI-supplied references: you get the code book (without tabs), the DLI laws-and-rules booklet and a desk calculator. You cannot bring your own books, notes or electronic devices.
  • DLI gives the exam at its St. Paul office and outstate sites, scheduled after DLI approves your application. The time limit is 5.5 hours; the passing score is 70%.
  • Results are mailed in about 2 weeks. If you fail, wait 30 days after receiving results before reapplying.
  • Some questions ask you to pick more than one answer (the question says how many) or the one choice that does not apply. Several versions of each exam are in use.

Note: DLI's Electrical License Examination Guide gives the question count (80) and marks the knowledge areas for the power limited technician but publishes no weights, so our topic split is an estimate. We could not read the 2026 NEC limited-energy articles (they were reorganized), so questions stay at concept level and cite Minnesota Statutes 326B and Rules 3800 for law.

Frequently asked questions

How many questions are on the Minnesota power limited technician exam?

80 questions in 5.5 hours, open book with DLI-supplied references. You need 70% to pass.

What experience do I need?

A 4-year electrical degree, or 36 months (6,000 hours) of power limited experience with at least 12 months installing. DLI-approved training can earn up to 12 months of credit (Minn. Stat. 326B.33, Rules 3800.3520).

Can I work on my own with this license?

No. The holder must be an employee, partner or officer of a licensed technology system or electrical contractor, or work for a registered employer on its own property.

Free questions with answers

Show all 10 free questions and answers
  1. Three resistors of 6, 12 and 18 ohms are connected in series across a 72-volt supply. What is the voltage drop across the 12-ohm resistor?

    Answer: 24 V

    Series resistance = 6 + 12 + 18 = 36 ohms. Current = 72 / 36 = 2 A, the same everywhere in a series circuit. Drop across the 12-ohm resistor = 2 A x 12 ohms = 24 V. 12 V results from using the 6-ohm value, 36 V assumes the drop splits evenly, and 48 V is the drop across the other two resistors combined.

    Reference: Basic electrical theory (Ohm's law and power formulas), Series circuit: E = I x R

  2. An Informational Note after a section recommends following an industry workmanship standard. How does the NEC treat that note?

    Answer: Informational only; it is not an enforceable requirement of the Code

    Article 90 says explanatory material, such as informational notes, is informational only and is not an enforceable requirement of the Code (Section 90.5(C) in the NEC 2023 text). Being printed inside a section does not make a note mandatory, and the Code does not limit or extend that rule by occupancy or by the wording of the note.

    Reference: NEC 2026, Introduction article (Article 90 in the NEC 2023 text), Explanatory material (Section 90.5(C)) in the NEC 2023 text

  3. A service uses 350 kcmil copper conductors, and the grounding electrode conductor runs only to two ground rods. What is the smallest copper grounding electrode conductor the NEC permits for that run?

    Answer: 6 AWG

    The GEC sizing table (Table 250.66 in the NEC 2023 text) would require 2 AWG copper for 350 kcmil service conductors, but a conductor that runs only to rod, pipe or plate electrodes need not be larger than 6 AWG copper (Section 250.66(A)). 4 AWG is the limit for a conductor to a concrete-encased electrode, and 8 AWG is smaller than the 6 AWG the rod rule allows.

    Reference: NEC 2026, Grounding and Bonding article (Article 250 in the NEC 2023 text), Grounding electrode conductor size, rod connections (Section 250.66(A) and Table 250.66) in the NEC 2023 text

  4. Type NM cable is run through bored holes in wood studs. What is the minimum distance from the edge of the hole to the edge of the stud if no steel plate is used?

    Answer: 1-1/4 in. (32 mm)

    Section 300.4(A)(1): holes must be bored so the edge of the hole is not less than 1-1/4 in. from the nearest edge of the wood member. Where that distance cannot be kept, the cable must be protected from nails and screws with a steel plate or bushing.

    Reference: NEC 2026, General Requirements for Wiring Methods and Materials article (Article 300 in the NEC 2023 text), Protection against physical damage, bored holes in wood members (Section 300.4(A)(1)) in the NEC 2023 text

  5. A low-voltage landscape luminaire system is installed on an outdoor patio (not near a pool, spa or fountain) where wet contact is likely. What is the highest ac operating voltage allowed for the system and its associated components under the low-voltage lighting rules?

    Answer: 15 volts ac

    The Low-Voltage Lighting article allows 30 volts ac (60 volts dc) in ordinary locations but reduces the limit to 15 volts ac (30 volts dc) where wet contact is likely (Section 411.3 in the NEC 2023 text). 30 volts ac is the ordinary-location limit; 24 V and 12 V are common product voltages, not the code limit. Pools, spas and fountains fall under Article 680 instead.

    Reference: NEC 2026, Low-Voltage Lighting article (Article 411 in the NEC 2023 text), Voltage limitations (Section 411.3 in the NEC 2023 text)

  6. Which type of material is the Class III classification of a hazardous (classified) location based on?

    Answer: Easily ignitible fibers and flyings

    Section 500.5(D): Class III locations are hazardous because of easily ignitible fibers or flyings, such as in textile mills and woodworking plants, but those fibers are not likely to be suspended in the air in ignitible quantities. Class I is gases and vapors, and Class II is combustible dust.

    Reference: NEC 2026, Hazardous (Classified) Locations article (Article 500 in the NEC 2023 text), Class III locations (Section 500.5(D)) in the NEC 2023 text

  7. What is the maximum output voltage permitted from the power source of a non-power-limited fire alarm (NPLFA) circuit?

    Answer: 600 volts, nominal

    For NPLFA circuits the power source must comply with Chapters 1 through 4 and have an output voltage of not more than 600 volts, nominal. Power-limited fire alarm circuits instead use sources limited by the power-limited fire alarm tables in Chapter 9.

    Reference: NEC 2026, Fire Alarm Systems article (Article 760 in the NEC 2023 text), NPLFA circuit power source requirements (Section 760.41(A) in 2023)

  8. A Class 1 power-limited circuit must be supplied from a source with a rated output of not more than what?

    Answer: 30 volts and 1000 volt-amperes

    The Class 1 power-limited rule caps the source rating at 30 volts and 1000 VA. The 100 VA values belong to Class 2 and Class 3 sources, and Class 3 allows up to 150 volts.

    Reference: NEC 2026, Class 1 Power-Limited Circuits article (Article 724 in the NEC 2023 text), Class 1 circuits, power source limit (Section 724.40 in the NEC 2023 text)

  9. Antenna lead-in conductors are attached to the outside of a building, not in a raceway or metal cable armor. What minimum clearance must they keep from any conductor forming part of a lightning protection system?

    Answer: 6 ft (1.8 m)

    Section 810.18(A): lead-in conductors must be installed so they cannot swing closer than 6 ft to any conductor that is part of a lightning protection system. The 2 ft figure applies to power circuits of 250 volts or less, and 10 ft applies to circuits over 250 volts.

    Reference: NEC 2026, Antenna Systems (Article 810 in the NEC 2023 text), Clearances, receiving stations, outside of buildings (Section 810.18(A) in the NEC 2023 text)

  10. Under Minnesota Statutes 326B.31, which of these is within the definition of technology circuits or systems?

    Answer: Class 2 alarm and signaling circuits isolated from other circuits by a demarcation

    Section 326B.31, subd. 29 defines technology circuits or systems as class 2, 3 or 4 circuits for remote control, signaling, control, alarm and audio, isolated from other circuits by a demarcation, plus antenna and communication circuits and low-voltage lighting limited to a class 2 or 3 supply. Process control circuits are expressly excluded.

    Reference: Minnesota Statutes 326B.31, Subd. 29 (technology circuits or systems)