Kansas Master Electrician Exam (ICC KGD): Practice Test & Licensing Guide

The ICC Kansas Standard Master Electrician exam (KGD): 100 open-book questions on the 2017 NEC, accepted by Wichita, Sedgwick County, Johnson County and other Kansas jurisdictions. 75% to pass.

Questions
100
Time limit
5 hours
Passing score
75%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10General Knowledge

A balanced 45 kW resistive load is served at 480 volts, 3-phase. What is the line current?

Requirements at a glance

AgencyYour Kansas city or county licenses you; the International Code Council (ICC) gives the exam through Pearson VUE. There is no statewide license
ExperienceSet by your city or county. Sedgwick County/Wichita: electrical master is journeyman plus 2 years; mechanical and plumbing master is 2 years as a journeyman or 4 years in the field
ExamKGD: 100 questions, 5 hours, 75%
Books allowed2017 NEC and Ugly's Electrical References (any edition)
Fees$115 per ICC exam (national T-series exams are $120), plus your city or county's certificate or license fees

Electricians applying for a master certificate or electrical contractor license from a Kansas city or county that accepts the ICC standard exam, such as Sedgwick County/Wichita (journeyman plus 2 years) or Johnson County.

How to get licensed, step by step

  1. Ask your city or county which exam it accepts

    Kansas law lets each jurisdiction name the standard examinations it accepts as proof of competency. Confirm the exam and the experience rules before you pay.

    Sedgwick County MABCD: master and journeyman trade certificates (opens in a new tab)Johnson County Contractor Licensing: exam information (opens in a new tab)Kansas statute K.S.A. 12-1525 (standard examinations) (opens in a new tab)

  2. Register for the master electrician exam (KGD) with ICC and Pearson VUE

    Create an ICC account, pick the Kansas standard exam from the Exam Catalog and schedule a Pearson VUE appointment. If you fail, wait 10 days to retake.

    Schedule with Pearson VUE (ICC exams) (opens in a new tab)ICC: State of Kansas exam bulletin (PDF) (opens in a new tab)

  3. Pass at 75% with your books

    The exam is open book with four-option multiple choice and no penalty for guessing. Bring only the approved references.

    ICC: State of Kansas exam bulletin (PDF) (opens in a new tab)

  4. Apply to your city or county

    Send your passing score and proof of experience to the jurisdiction, with its fee. It issues the certificate or license and sets renewal rules.

    Sedgwick County MABCD: master and journeyman trade certificates (opens in a new tab)Johnson County Contractor Licensing: exam information (opens in a new tab)

How to prepare

  • Study the edition the exam is built on: the 2017 NEC for electrical and the 2018 IPC, IMC and IFGC for plumbing and mechanical. Your city's adopted code can be newer.
  • The exam is open book, but there is not time to look up every answer. Tab your books by chapter and table before exam day.
  • The 2014 NEC / 2015 I-Code Kansas exams end December 1, 2026. If your jurisdiction wants a 2021-based exam, ask about the national ICC T-series instead.
  • The master exam has the same weights as the journeyman exam with more questions: wiring methods and materials (26%) and branch circuits and conductors (19%) lead.
  • Services (11%) and special occupancies (11%) reward good tabbing of Articles 230, 250 and Chapters 5 through 7.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2017 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

  • NFPA 70: National Electrical Code (NEC), 2017 EditionEssential

    Allowed in the exam room. The Kansas standard electrician exams are built on the 2017 edition, not the newer NEC your city may enforce.

    NFPA store (opens in a new tab)

  • Ugly's Electrical References (any edition)

    Allowed in the exam room. Formulas for voltage drop, power, motors and load calculations.

Official reference list (as published by the testing agency)
  • 2017 National Electrical Code (NEC) (allowed in the exam room)
  • Ugly's Electrical References (any edition) (allowed in the exam room)

What's on the exam

Official content outline from International Code Council (ICC), delivered by Pearson VUE, (number of questions per topic):

TopicQuestions
General Knowledge6
Services and Service Equipment11
Feeders4
Branch Circuits and Conductors19
Wiring Methods and Materials26
Equipment and Devices13
Control Devices4
Motors and Generators6
Special Occupancies, Equipment, and Conditions11

Exam day details

  • Administered by International Code Council (ICC), delivered by Pearson VUE, for Kansas cities and counties.
  • Fee: $115 to ICC through Pearson VUE per exam. Your city or county's license fees are separate.
  • 100 multiple-choice questions in 5 hours; 75 correct (75%) to pass.
  • Open book: bring the approved references. Questions are four-option multiple choice with no penalty for guessing; 75% to pass.
  • Kansas has no statewide electrician, plumber or mechanical license. ICC only tests; the city or county where you want to work sponsors you and issues the license.
  • If you fail, wait 10 days to retake.
  • The 2014 NEC / 2015 I-Code exams stop being offered December 1, 2026. These Kansas standard exams are based on the 2017 NEC and 2018 I-Codes; the national T-series exams cover the 2020 NEC and 2021 I-Codes.

Frequently asked questions

What's on the Kansas master electrician exam?

100 questions by weight: wiring methods and materials 26%, branch circuits and conductors 19%, equipment and devices 13%, services and service equipment 11%, special occupancies 11%, general knowledge 6%, motors and generators 6%, feeders 4% and control devices 4%.

Is the master exam different from the journeyman exam?

The ICC outline and weights are the same; the master exam is longer (100 questions in 5 hours) and the license requires more experience from the city or county.

Which code book does the Kansas exam use?

The 2017 NEC, plus Ugly's Electrical References (any edition).

Free questions with answers

Show all 10 free questions and answers
  1. A balanced 45 kW resistive load is served at 480 volts, 3-phase. What is the line current?

    Answer: 54.1 A

    For a balanced three-phase load, I = P / (E x 1.732) = 45,000 / (480 x 1.732) = 45,000 / 831.4 = 54.1 A. 93.8 A divides by 480 alone (single-phase formula), 31.3 A divides by 480 x 3, and 108.3 A uses 240 V instead of 480 V.

    Reference: NFPA 70, National Electrical Code, 2017, Three-phase power formula (Ugly's Electrical References, electrical formulas)

  2. A new 480Y/277-volt, 3-phase, solidly grounded wye service has a 2,000 A service disconnect. Under 230.95, what is the maximum setting allowed for the required ground-fault protection of equipment?

    Answer: 1,200 A

    Section 230.95 requires ground-fault protection of equipment for solidly grounded wye services of more than 150 volts to ground with a service disconnect rated 1,000 A or more. Section 230.95(A) limits the maximum setting to 1,200 A, with a maximum time delay of 1 second for ground-fault currents of 3,000 A or more. 1,000 A is the disconnect rating that triggers the requirement, 2,000 A is this disconnect's rating, and 3,000 A is the current at which the time limit is checked.

    Reference: NFPA 70, National Electrical Code, 2017, 230.95(A)

  3. A 3-phase, 4-wire feeder has a calculated maximum unbalanced neutral load of 450 A. None of the load is electric-discharge lighting or other nonlinear load. What is the neutral load after the allowed demand factor under 220.61(B)?

    Answer: 375 A

    Section 220.61(B)(2) permits a demand factor of 70 percent for the portion of the unbalanced neutral load over 200 A: 200 + 0.70 x (450 - 200) = 200 + 175 = 375 A. 315 A applies 70 percent to the whole 450 A, 450 A ignores the reduction, and 325 A uses 50 percent for the portion over 200 A.

    Reference: NFPA 70, National Electrical Code, 2017, 220.61(B)(2)

  4. Table 310.106(A) lists the minimum size of copper conductors for general wiring at 2,000 volts or less. What is that smallest size?

    Answer: 14 AWG

    Section 310.106(A) and its table set 14 AWG as the smallest copper conductor for general branch-circuit and feeder wiring (12 AWG for aluminum or copper-clad aluminum). Smaller 16 and 18 AWG conductors are used only for specific purposes such as fixture wires, control and Class 2 circuits, covered by their own articles.

    Reference: NFPA 70, National Electrical Code, 2017, 310.106(A), Table 310.106(A)

  5. Where must the means to disconnect all ungrounded conductors of a multiwire branch circuit simultaneously be provided under 210.4(B)?

    Answer: At the point where the branch circuit originates

    Section 210.4(B) requires each multiwire branch circuit to have a means that simultaneously disconnects all ungrounded conductors at the point where the circuit originates, such as a multipole breaker or handle-tied single-pole breakers. This protects workers who might open only one leg and still find the shared neutral energized.

    Reference: NFPA 70, National Electrical Code, 2017, 210.4(B)

  6. A metal outlet box contains two 12-2 with ground nonmetallic-sheathed cables (four insulated 12 AWG circuit conductors plus two bare grounds), one single-gang switch and no clamps or fittings. Using 2.25 cubic inches per 12 AWG, what is the minimum box volume required?

    Answer: 15.75 cubic inches

    Under 314.16(B) count each insulated conductor (4), the device yoke as two conductors (2) and all equipment grounding conductors together as one (1): 4 + 2 + 1 = 7 allowances. 7 x 2.25 = 15.75 in3. 13.5 omits the grounds, 18.0 counts each ground separately (8 allowances), and 11.25 omits the switch allowance.

    Reference: NFPA 70, National Electrical Code, 2017, 314.16(B); Table 314.16(B)

  7. A 3-phase, 45 kVA transformer has a 208Y/120-volt secondary. What is the full-load secondary line current?

    Answer: 124.9 A

    Three-phase current = kVA x 1,000 / (E x 1.732) = 45,000 / (208 x 1.732) = 45,000 / 360.3 = 124.9 A. 216.3 A divides by 208 only (single-phase formula), 72.1 A divides by 208 x 3, and 187.5 A is 45,000 divided by 240 V.

    Reference: NFPA 70, National Electrical Code, 2017, Three-phase transformer current formula (Ugly's); Table 450.3(B) application

  8. A 3-way snap switch is installed for a luminaire fed by a grounded system. In which conductor must the switching be done under 404.2(A)?

    Answer: The ungrounded (hot) conductor only

    Section 404.2(A) requires 3-way and 4-way switches to be wired so that all switching is done only in the ungrounded circuit conductor, except where the Code expressly permits otherwise. Switching the neutral leaves the luminaire energized when the switch is off, a shock hazard to anyone servicing it.

    Reference: NFPA 70, National Electrical Code, 2017, 404.2(A)

  9. A single 40 hp, 460-volt, 3-phase continuous-duty induction motor has a Table 430.250 full-load current of 52 A. Under 430.22, what is the minimum ampacity of the branch-circuit conductors?

    Answer: 65 A

    Section 430.22 requires branch-circuit conductors for a single continuous-duty motor to have an ampacity of at least 125 percent of the motor full-load current from the table: 52 x 1.25 = 65 A. 52 A omits the factor, 78 A applies 150 percent, and 57 A applies only 110 percent. Overload relays are sized from the nameplate, not this value.

    Reference: NFPA 70, National Electrical Code, 2017, 430.22; Table 430.250

  10. In a Class I, Division 1 location, a conduit enters an enclosure that contains arcing devices. How close to the enclosure must the conduit seal be installed under 501.15(A)(1)?

    Answer: Within 18 in

    Section 501.15(A)(1) requires a seal in each conduit entry into an enclosure that contains arcing or high-temperature devices, located as close as practicable and not more than 18 in from the enclosure. 10 ft is the distance allowed for a boundary seal where a conduit run leaves the classified location under 501.15(A)(4).

    Reference: NFPA 70, National Electrical Code, 2017, 501.15(A)(1)