Requirements at a glance
| Agency | Georgia Construction Industry Licensing Board (Division of Electrical Contractors); exams by PSI |
|---|---|
| Experience | Age 21; 4 years of primary electrical experience (up to 1 year of secondary experience or education may count); at least one of the 3 references from a licensed electrical contractor. The license is restricted to single-phase work of 200 amps or less at the service. |
| Exam | 140 questions, 8 hours in two 4-hour parts, open book, 70 to pass |
| Books allowed | 2023 NEC (or NEC Handbook) with Georgia amendments, American Electricians' Handbook 17th Edition, the NASCLA Georgia guide, IRS Circular E, 29 CFR 1926 and Ugly's 2023 |
| Fees | $40 application fee ($30 plus a $10 processing fee) per the Secretary of State form. The PSI exam fee and license fee are not published in the candidate bulletin; confirm them with PSI and the Board. |
Qualifying agents for a restricted Georgia electrical contractor license from the Construction Industry Licensing Board. Class I is limited to single-phase work with a service of 200 amps or less.
Official links
How to get licensed, step by step
Apply to the Board
Submit the application, three references on the Board's form and the $40 fee to the Construction Industry Licensing Board (Macon; (404) 424-9966). The Board must approve you before you can register with PSI.
Georgia Division of Electrical Contractors (CILB) (opens in a new tab)Georgia Rules 121-3 (CILB license requirements) (opens in a new tab)
Register with PSI
After approval, register and pay PSI online or at 855-898-0711. Bring the allowed references and a silent, non-programmable calculator.
Schedule with PSI (Georgia CILB exams) (opens in a new tab)PSI bulletin: Georgia electrical contractors (opens in a new tab)
Take the exam
Scaled score, 70 to pass. If you fail twice, the PSI bulletin requires a Board-approved review course before a third attempt.
PSI bulletin: Georgia electrical contractors (opens in a new tab)
Finish licensing
Send your results and the license fee to the Board. Georgia has no statewide journeyman or master electrician license; local jurisdictions license those workers.
Georgia Division of Electrical Contractors (CILB) (opens in a new tab)
How to prepare
- Georgia's exams are scaled with 70 to pass. The Board's 2026 reference lists apply to exams through December 31, 2026; check for the updated list if you test later.
- Tab your books with permanent tabs before exam day. Highlighting and underlining are allowed; notes, sticky flags and loose papers are not.
- Interior electrical systems (30), controls and devices (22) and basic circuits (21) are 73 of the 140 questions.
- Transformers (7) and rotating equipment (9) are light on Class I compared with Class II.
- Start with the free questions above to find your weak topics, then drill those first.
- Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
- Read every explanation, including for questions you got right, and look the section up in your own book.
Books for this exam
This is an open-book exam: you can bring the references below, and most questions come from the 2023 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.
NFPA 70: National Electrical Code (NEC), 2023 Edition (or the NEC Handbook), with Georgia amendmentsEssential
Allowed in the exam room. The Georgia State Electrical Code. Tab Articles 100, 110, 210, 220, 230, 240, 250, 310, 430, 450 and Chapter 9.
NFPA store (opens in a new tab)Free online access (opens in a new tab)
American Electricians' Handbook, 17th Edition (2021), McGraw-Hill
On the electrical exam list. Trade practice, motors, transformers and controls.
Contractors Guide to Business, Law, and Project Management: Georgia Construction Industry Licensing Board, 5th Edition (NASCLA)
On the Board's reference lists for the electrical, conditioned air and plumbing exams.
Ugly's Electrical References, 2023 Edition
On the electrical and low voltage lists. Formulas for voltage drop, power, motors and transformers.
Official reference list (as published by the testing agency)
- Georgia State Electrical Code: 2023 NEC or NEC Handbook with Georgia amendments (NFPA 70)
- American Electricians' Handbook, 17th Edition (2021), McGraw-Hill
- Contractors Guide to Business, Law, and Project Management, Georgia Construction Industry Licensing Board, 5th Edition (NASCLA)
- Employer's Tax Guide (IRS Circular E, Publication 15), 2025 or 2026
- 29 CFR Part 1926 (OSHA construction standards)
- Ugly's Electrical References, 2023
What's on the exam
Official content outline from PSI Services (number of questions per topic):
| Topic | Questions | |
|---|---|---|
| Comply with Laws | 10 | |
| Comply with Regulations | 9 | |
| Comply with Administrative Requirements | 6 | |
| Plan and Organize Work | 5 | |
| Maintain Basic Electrical Circuits | 21 | |
| Install and Maintain Electrical Controls and Devices | 22 | |
| Install and Maintain D-C and A-C Rotating Equipment | 9 | |
| Install, Size, and Maintain Transformers | 7 | |
| Install and Maintain Interior Electrical Systems | 30 | |
| Special Equipment, Conditions, and Locations | 21 |
Exam day details
- Administered by PSI Services for the Georgia Construction Industry Licensing Board.
- Fee: The Board's initial application fee is $40 ($30 plus a $10 processing fee). The PSI exam fee and the license fee are not published in the candidate bulletin, so check PSI and the Board before you apply.
- 140 scored questions plus 15 unscored pretest questions in 8 hours, split into two 4-hour parts with a break.
- Open book: bring only the references on the Board's list (listed here for exams through December 31, 2026). Highlighting, underlining and permanent tabs are allowed; notes and extra papers are not.
- Class I has the same law and administration sections as Class II but weighs basic circuits, controls and interior systems more heavily and transformers and rotating equipment less.
- The Board must approve your application before you can register with PSI. Scores are scaled and you need 70 to pass.
- The time limit includes the unscored beta (pretest) questions mixed into the exam.
- If you fail twice, the PSI bulletin requires a Board-approved review course before a third attempt.
- Georgia has no statewide journeyman or master electrician exam and no statewide HVAC technician exam; local jurisdictions license those workers.
Frequently asked questions
What's on the Georgia Class I electrical contractor exam?
140 scored questions: laws 10, regulations 9, administrative requirements 6, planning and organizing work 5, basic circuits 21, controls and devices 22, rotating equipment 9, transformers 7, interior electrical systems 30 and special equipment, conditions and locations 21.
What can a Class I electrical contractor do in Georgia?
Restricted work: single-phase service of 200 amps or less. Class II is unrestricted.
Is the Class I exam different from Class II?
They are separate exams from the same outline with different weights. Our two banks are built for each class.
Free questions with answers
Show all 10 free questions and answers
Three references are required with a statewide electrical contractor application. Who must at least one of the three be?
Answer: A licensed electrical contractor who lists his or her registration number
Rule 121-3-.01(3) requires three references on the required form from persons who can attest to the applicant's electrical experience; at least one must be from a licensed electrical contractor who gives his or her registration number. Architects and engineers are the reference for the six-year alternative in (8)(c).
Reference: Ga. Comp. R. & Regs. 121-3-.01 (Statewide Electrical Contractor License), 121-3-.01(3)
An electrician is installing conduit along the unprotected edge of a roof on a building under construction. At what height above a lower level must the employer provide fall protection under 29 CFR 1926 Subpart M?
Answer: 6 feet
29 CFR 1926.501(b)(1) requires fall protection for employees on a walking/working surface with an unprotected side or edge that is 6 feet or more above a lower level. The 10-foot figure is the scaffold threshold in 1926.451(g)(1), and 4 feet is the general-industry figure in 1910.28.
Reference: 29 CFR Part 1926 (OSHA Safety and Health Regulations for Construction), 1926.501(b)(1)
A nonexempt journeyman earns $32.00 per hour and works 46 hours in one workweek, all at the same rate. Under the FLSA, what are his gross wages for the week?
Answer: $1,568.00
Hours over 40 in a workweek are paid at 1.5 times the regular rate. Regular pay: 40 x $32.00 = $1,280. Overtime: 6 x ($32.00 x 1.5 = $48.00) = $288. Total = $1,280 + $288 = $1,568. $1,472 pays all 46 hours at straight time; $1,664 pays all 46 hours at time-and-a-half.
Reference: Fair Labor Standards Act, 29 U.S.C. 207(a)(1), 29 U.S.C. 207(a)(1)
A rough-in is estimated at 120 labor hours. A 3-person crew works 8-hour days on the job. How many working days are needed, assuming the crew works the whole time?
Answer: 5 days
Crew capacity is 3 workers x 8 hours = 24 labor hours per day. 120 / 24 = 5 days. 15 days would result from dividing by 8 only, as if one person did the work.
Reference: General business practice: crew scheduling, Labor-hour scheduling
A 12-ohm resistive heating element is connected to a 208-volt single-phase supply. What power does it dissipate?
Answer: About 3,605 watts
P = E squared / R = 208 x 208 / 12 = 43,264 / 12 = 3,605 W. The current is 208 / 12 = 17.3 A; 17,300 W mistakes that current for the power, and 2,500 W would divide E squared by 17.3.
Reference: General electrical theory (Ohm's law and power formula), P = E squared / R
What is the maximum height above the floor of the center of the operating handle of a snap switch or circuit breaker when it is in its highest position?
Answer: 6 feet 7 inches
404.8(A) and 240.24(A) limit the center of the grip of the operating handle of a switch or circuit breaker, in its highest position, to not more than 2.0 m (6 ft 7 in.) above the floor or working platform. Exceptions exist for some busway and service equipment installations.
Reference: NEC 2023 (NFPA 70), 404.8(A) and 240.24(A)
When sizing the branch-circuit conductors for a general-purpose single-phase motor, which current value does 430.6(A)(1) tell you to use?
Answer: The full-load current from the Table 430.248 for the horsepower and voltage
430.6(A)(1) requires the table full-load current values (Table 430.248 for single-phase motors) to be used for conductor ampacity and for disconnect and short-circuit protection sizing, rather than the nameplate current. The nameplate current is used for overload protection under 430.6(A)(2).
Reference: NEC 2023 (NFPA 70), 430.6(A)(1)
A 10-kVA single-phase transformer with a 240-volt primary (41.7 amperes) has primary-only overcurrent protection and no secondary protection. Using 450.3(B) and its notes, what is the maximum standard overcurrent device rating?
Answer: 60 amperes
For primary-only protection on a transformer with primary current of 9 A or more, Table 450.3(B) permits 125 percent: 41.7 x 1.25 = 52.1 A. Note 1 permits the next higher standard rating, which is 60 A. 50 A and 45 A are standard sizes below the calculated value, and 100 A would be about 240 percent.
Reference: NEC 2023 (NFPA 70), Table 450.3(B) and Note 1; 240.6(A)
A copper water supply line is planned to run horizontally 4 feet above a new panelboard in a basement utility room, directly over the enclosure. What is the problem?
Answer: Piping foreign to the electrical system may not run in the dedicated space above the panelboard
110.26(E)(1) reserves a dedicated space equal to the width and depth of the panelboard, extending from the floor to 6 ft above the equipment or to the structural ceiling, whichever is lower. Pipes, ducts and other foreign systems may not be located in that zone. The room itself may contain piping elsewhere.
Reference: NEC 2023 (NFPA 70), 110.26(E)(1)
A photovoltaic source circuit has a module short-circuit current (Isc) of 11.2 amperes. Applying the two 125 percent factors in 690.8(A) and 690.8(B), what is the minimum conductor ampacity before any other adjustments?
Answer: 17.5 amperes
690.8(A) sets the maximum circuit current at 125 percent of Isc: 11.2 x 1.25 = 14.0 A. 690.8(B) requires conductors and devices to carry 125 percent of that value: 14.0 x 1.25 = 17.5 A (156 percent of Isc overall). 14.0 A applies only one factor, and 22.4 A is Isc doubled.
Reference: NEC 2023 (NFPA 70), 690.8(A) and 690.8(B)
Sources
- PSI: Georgia Electrical Contractors Candidate Information Bulletin (Class I and Class II) (opens in a new tab)
- Georgia State Board of Electrical Contractors (Secretary of State) (opens in a new tab)
- Georgia Rules 121-3 (Construction Industry Licensing Board) (opens in a new tab)
Questions last verified November 14, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.