District of Columbia Journeyman A/C and Refrigeration Mechanic Exam: Practice Test & Licensing Guide

The PSI exam for the District of Columbia journeyman air conditioning and refrigeration license: 60 multiple-choice questions on the 2012 IMC and Modern Refrigeration and Air Conditioning. Open book, 2 hours.

Questions
60
Time limit
2 hours
Passing score
Not published by District of Columbia

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Theory, System Types, Terminology, and General Requirements

A water-cooled chiller cools 60 gpm of water from 54 degrees F entering to 44 degrees F leaving. Using Q = 500 x gpm x TD, what is the chiller load in tons of refrigeration?

Requirements at a glance

AgencyD.C. Board of Industrial Trades, Department of Licensing and Consumer Protection (DLCP); exam by PSI
Exam60 multiple-choice questions, 2 hours (exam ID 312); Pass score not published; PSI reports PASS or FAIL
ExperienceNot confirmed; see the Board's page
BooksOpen book: bound references only, permanent tabs, notes in ink or highlighting in code sections only; no writing during the exam
Fees$52 to PSI per exam; D.C. application and license fees are separate

Refrigeration and air conditioning mechanics applying to the Board of Industrial Trades for a journeyman license.

How to get licensed, step by step

  1. Meet the experience requirement

    The DLCP refrigeration instructions were not available to us; check the Board's page for the experience and documents required.

    D.C. Board of Industrial Trades (DLCP) (opens in a new tab)

  2. Apply to the District

    Submit the online application and fees to the Board of Industrial Trades. Approved candidates receive a notice of eligibility.

    D.C. online license application (opens in a new tab)

  3. Register with PSI

    Register by phone at (855) 557-0616 or online, giving the exam ID and title. Pay the $52 exam fee by credit or debit card when you book.

    Register with PSI: refrigeration exams (opens in a new tab)PSI: Washington D.C. Candidate Information Bulletin (8/25/2022) (opens in a new tab)

  4. Take the exam

    Bring your listed references and matching ID. You see PASS or FAIL right after the exam. To retest you must reapply with the District first.

    PSI: Washington D.C. Candidate Information Bulletin (8/25/2022) (opens in a new tab)

How to prepare

  • Theory and general requirements are 32% of the exam; refrigerants and operating procedures including safety are 12% each.
  • The PSI bulletin (8/25/2022) lists older editions than the District's adopted 2017 DC Construction Codes (2014 NEC, 2015 ICC codes). Confirm the current reference list with PSI (855-557-0616) or the DLCP before you buy books.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2012 IMC and Modern Refrigeration. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

  • 2012 International Mechanical Code (IMC), ICCEssential

    The edition on the PSI bulletin (8/25/2022). Confirm the current list with PSI or the DLCP.

    ICC (opens in a new tab)

  • Modern Refrigeration and Air Conditioning (2004 edition)Essential

    Listed on the PSI bulletin for the refrigeration and air conditioning exams.

Official reference list (as published by the testing agency)
  • 2012 International Mechanical Code (IMC)
  • Modern Refrigeration and Air Conditioning (2004 edition)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
Theory, System Types, Terminology, and General Requirements32
Refrigerant and Condensate Piping12
Evaporators, Compressors, Condensers, Chillers, Cooling Towers, Heat Pumps, Heating and AC Appliances10
Conditioned Air, Supply, Return, Makeup, Combustion Air, Air Ducts, Dampers, and Insulation5
Electrical Fundamentals and Controls9
Refrigerants12
Operating Procedures, including Safety12
Maintenance and Repairs8

The outline totals 100; the other items on the 60-question exam are unscored or unassigned.

Exam day details

  • Administered by PSI Services for the District of Columbia Board of Industrial Trades (DLCP).
  • Fee: $52 to PSI per computer-based exam. D.C. application and license fees are separate.
  • PSI exam ID 312: 60 multiple-choice questions, open book, 2 hours. The content outline is the PSI bulletin's.
  • The bulletin's references are the 2012 IMC and Modern Refrigeration and Air Conditioning (2004); the District's adopted construction codes are newer (2015 ICC codes). Confirm the current list with PSI or the DLCP.
  • You apply to the Board online and pay the application fees first. Approved candidates get a notice of eligibility, then register with PSI at (855) 557-0616 or on PSI's D.C. pages using the exam ID and title.
  • Open book: bring only the references the bulletin lists. They must be bound (original, three-ring binder or stapled); photocopies of copyrighted material are not allowed. Notes in ink or highlighting are allowed in code sections only, and tabs must be permanently attached.
  • You may not write or mark in your references during the exam. PSI gives you a whiteboard, markers and scratch paper. Bring a battery-operated, non-programmable calculator without a printer.
  • Your name on the reservation must match your ID or you cannot test and forfeit the fee. Restroom breaks are limited to 5 minutes and the clock keeps running.
  • You see your result right after the exam. Passing candidates are told PASS with no numeric score; candidates who fail get diagnostic feedback by content area.
  • To retest you must reapply with the District before each attempt. The bulletin recommends allowing time to study before registering again.

Note: The PSI bulletin (updated 8/25/2022) lists the 2011 NEC and the 2012 IPC, IFGC and IMC, while the District's adopted construction codes are the 2017 DC Construction Codes (2014 NEC and 2015 ICC codes with D.C. amendments, effective May 29, 2020). We follow the editions on the bulletin. Confirm the current reference list with PSI (855-557-0616) or the DLCP before you buy books. No pass score is published.

Frequently asked questions

How many questions are on the D.C. journeyman a/c and refrigeration mechanic exam?

PSI lists 60 multiple-choice questions in 2 hours (exam ID 312), open book. The biggest areas are Theory, System Types, Terminology, and General Requirements (32%), Refrigerant and Condensate Piping (12%), Refrigerants (12%).

What is the passing score?

Neither PSI nor the Board of Industrial Trades publishes a passing score. PSI shows PASS or FAIL right after the exam, with no numeric score for passing candidates and diagnostic feedback for those who fail.

Which code edition does the exam use?

PSI's bulletin lists the 2012 International Mechanical Code and Modern Refrigeration and Air Conditioning (2004). The District has since adopted the 2015 ICC codes in the 2017 DC Construction Codes, so confirm the current reference list with PSI or the DLCP before you buy books.

Free questions with answers

Show all 10 free questions and answers
  1. A water-cooled chiller cools 60 gpm of water from 54 degrees F entering to 44 degrees F leaving. Using Q = 500 x gpm x TD, what is the chiller load in tons of refrigeration?

    Answer: 25 tons

    Q = 500 x 60 gpm x 10 F = 300,000 Btu/h. Dividing by 12,000 Btu/h per ton gives 25 tons. Using a 12 degree TD gives 30 tons, a slipped decimal gives 2.5, and 8.33 x 60 x 10 = 4,998 Btu/h (0.42 ton) leaves out the 60 minutes per hour.

    Reference: General practice (refrigeration), Water sensible heat formula Q = 500 x gpm x TD

  2. An air handler moves 4,000 cfm. Air entering the coil has an enthalpy of 30.0 Btu per pound of dry air and leaves at 21.0 Btu per pound. Using Q = 4.5 x cfm x change in enthalpy, what is the total cooling capacity?

    Answer: 162,000 Btu/h

    The enthalpy change is 30.0 - 21.0 = 9.0 Btu/lb. Q = 4.5 x 4,000 x 9.0 = 162,000 Btu/h. The 1.08 sensible factor would give 38,880, using the 30 Btu/lb entering value alone gives 540,000, and omitting the enthalpy change gives 18,000.

    Reference: General practice (refrigeration), Total heat of air: Q = 4.5 x cfm x change in enthalpy

  3. Under Section 1107.3 of the 2012 IMC, for which erected-on-the-premises refrigerant piping must rigid or flexible metal enclosures be provided?

    Answer: Soft annealed copper tubing carrying a Group A2 refrigerant

    Section 1107.3 applies to soft annealed copper tubing used for refrigerant piping that contains other than Group A1 or B1 refrigerants, so a Group A2 refrigerant triggers the enclosure. There is also an exception for condensing-unit-to-riser-box connections of 6 feet or less.

    Reference: 2012 International Mechanical Code, Section 1107.3

  4. Section 1107.2.2 of the 2012 IMC generally prohibits refrigerant piping from penetrating floors, ceilings and roofs. Which penetration is allowed by an exception?

    Answer: A penetration connecting the top floor and a machinery penthouse or roof installation

    The exceptions to Section 1107.2.2 include connections between the basement and first floor, the top floor and a machinery penthouse or roof installation, and adjacent floors served by the refrigeration system. Other penetrations need the small-quantity or enclosed-shaft conditions of the remaining exceptions.

    Reference: 2012 International Mechanical Code, Section 1107.2.2, Exceptions

  5. Which type of compressor has an external motor connected by a shaft that passes through a shaft seal, so the seal can leak refrigerant and oil?

    Answer: Open-drive compressor

    In an open-drive compressor the motor sits outside the crankcase and drives the compressor through a shaft seal, which is a wear item and a potential leak point. Hermetic and semi-hermetic compressors enclose the motor in the refrigerant circuit, so they have no shaft seal.

    Reference: General practice (refrigeration), Compressor types: open, hermetic, semi-hermetic

  6. A duct has internal liner insulation and an electric-resistance heater is added in the duct. Under Section 604.8 of the 2012 IMC, how must the liner be handled near the heater?

    Answer: The liner must stop at least 6 inches upstream and 6 inches downstream of the heater

    Section 604.8 requires linings to be interrupted at the operating area of a fire damper and at least 6 inches upstream and 6 inches downstream of electric-resistance and fuel-burning heaters. Section 604.9 then calls for a covering of equal thermal performance where the liner is interrupted.

    Reference: 2012 International Mechanical Code, Section 604.8

  7. A 24-volt contactor coil draws 0.5 ampere. Using Ohm's law, what is the resistance of the coil?

    Answer: 48 ohms

    R = E / I = 24 V / 0.5 A = 48 ohms. Multiplying the two values gives 12, which is watts rather than ohms, dividing the other way gives 0.02, and adding the numbers has no basis in Ohm's law.

    Reference: General practice (refrigeration), Ohm's law

  8. According to the refrigerant listing in Table 1103.1 of the 2012 IMC, R-410A is a zeotropic blend of which two refrigerants?

    Answer: R-32 and R-125, in equal parts by weight

    Table 1103.1 lists R-410A as R-32/125 (50/50) with a Group A1 safety classification. It is not interchangeable with R-22, and its pressures are much higher.

    Reference: 2012 International Mechanical Code, Table 1103.1

  9. A refrigerant detector in a machinery room activates the emergency ventilation. The largest system in the room holds 400 pounds of refrigerant. Using Q = 100 x the square root of G from Section 1105.6.3.2 of the 2012 IMC, what airflow must the ventilation system exhaust?

    Answer: 2,000 cfm

    The square root of 400 is 20, so Q = 100 x 20 = 2,000 cfm. Using G directly gives 40,000, multiplying the root by 10 gives 200, and the square root alone is 20. This applies to machinery rooms with other than ammonia systems.

    Reference: 2012 International Mechanical Code, Section 1105.6.3.2

  10. Why must a container of polyolester (POE) oil be kept tightly capped when it is not being poured into a system?

    Answer: POE oil readily absorbs moisture from the air, which can form acids in the system

    POE oil is hygroscopic, so an open container takes in moisture that can cause acid formation and sludge after it is in a system. It is used with HFC refrigerants such as R-410A and R-134a, where mineral oil does not mix well.

    Reference: General practice (refrigeration), Compressor oils: POE handling

Sources

Questions last verified November 17, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.