National certification

ICC Master Mechanical Exam (29): Practice Test & Licensing Guide

ICC's National Standard exam 29 for HVAC and mechanical contractors: 100 questions in 4 hours, open book on the 2021 IMC and IFGC.

Questions
100
Time limit
4 hours
Passing score
75%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Administration and General Regulations

Work under a mechanical permit stopped for 8 months. No changes have been or will be made to the approved construction documents. Before work resumes, what does IMC Section 106.4.3 require?

Requirements at a glance

Who requires itMechanical/HVAC contractor licenses in Denver, PPRBD (H-A), Fort Collins, Larimer and Boulder counties, Jefferson County and many Midwest cities
Exam100 questions, 4 hours, open book
Books allowed2021 IMC and 2021 IFGC
Fee$120 per attempt (Pearson VUE), plus your jurisdiction's license fee

HVAC and mechanical contractor qualifiers in jurisdictions that use ICC exams, including Denver (heating, ventilation and refrigeration), PPRBD (H-A), Fort Collins (all HVAC classes), Larimer and Boulder counties, Jefferson County (Mechanical A) and many Midwest cities.

How to get certified, step by step

  1. Check your jurisdiction's requirement

    Find your license class on your city or county's contractor page and note the exact ICC exam ID. The letter shows the code year (G = 2018, T = 2021), and from December 1, 2026 the T-series ID also shows whether you need 70% or 75%.

    Denver: contractor licenses and supervisor certificates (opens in a new tab)Pikes Peak Regional Building Department: contractor licensing (opens in a new tab)

  2. Register with ICC

    Create an ICC account, buy the exam from ICC's catalog, then schedule with Pearson VUE at a test center or online.

    ICC exam catalog and registration (opens in a new tab)

  3. Bring the right code books

    Open book: 2021 IMC and 2021 IFGC. Tabs and highlighting are allowed; loose notes aren't.

    ICC 2021 National Contractor/Trades bulletin (PDF) (opens in a new tab)

  4. Pass and apply

    Results are immediate. Submit your passing score with your license application, insurance and fees. If you fail, wait 10 days to retake.

How to prepare

  • Tab your code book by chapter before exam day; most questions are lookups, and 4 hours goes fast.
  • General regulations and installation are 30% of the exam: IMC Chapter 3 and IFGC Chapter 3 (clearances, access, condensate, combustion air).
  • Practice gas pipe sizing with IFGC Table 402.4 and vent sizing in Chapter 5.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2021 IMC and the 2021 IFGC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • International Mechanical Code (IMC), 2021
  • International Fuel Gas Code (IFGC), 2021

What's on the exam

Official content outline from International Code Council (ICC), delivered by Pearson VUE (number of questions per topic):

TopicQuestions
Administration and General Regulations30
Appliances and Mechanical Equipment27
Exhaust and Ventilation Systems11
Duct Systems12
Combustion Air6
Chimneys and Vents8
Fuel Supply Systems6

Exam day details

  • Administered by International Code Council (ICC), delivered by Pearson VUE.
  • Fee: $120 per attempt (Pearson VUE). Your city or county license fee is separate.
  • 100 multiple-choice questions in 4 hours, open book.
  • Exam IDs show the code year: F = 2015 codes (retired December 1, 2026), G = 2018, T = 2021. Our questions use the 2021 codes; check which edition your jurisdiction requires.
  • From December 1, 2026 the 2021 (T-series) exams come in 70% and 75% passing versions, and each jurisdiction picks one. ICC has historically used a scaled 75.
  • Open book: bring the listed references. Four-option multiple choice, no penalty for guessing. Results are immediate, and you wait 10 days to retake.

Frequently asked questions

What books are allowed on the ICC 29 Master Mechanical exam?

The International Mechanical Code and International Fuel Gas Code for your exam's edition (2021 for T29, 2018 for G29).

What's on the ICC Master Mechanical exam?

100 questions: general regulations, installation and testing (30%), appliances and equipment (27%), ducts (12%), exhaust and ventilation (11%), chimneys and vents (8%), combustion air (6%) and fuel gas piping (6%).

Is there an ICC residential mechanical exam?

ICC's Residential Mechanical (32) exam is only offered on the 2015 IRC and retires December 1, 2026 with no newer version announced. Several Colorado jurisdictions still list it; check with yours.

Free questions with answers

Show all 10 free questions and answers
  1. Work under a mechanical permit stopped for 8 months. No changes have been or will be made to the approved construction documents. Before work resumes, what does IMC Section 106.4.3 require?

    Answer: A new permit, at one-half the fee for a new permit

    Suspension for 180 days or more voids the permit, so a new permit is needed before work recommences. Section 106.4.3 sets that fee at one-half the new-permit amount, provided the construction documents are unchanged and the suspension has not exceeded 1 year. The full fee would apply only if those conditions were not met. An extension under Section 106.4.4 is for a permit that is still unexpired.

    Reference: 2021 International Mechanical Code, Section 106.4.3

  2. Under IMC Section 306.1, what minimum level working space must be provided in front of the control side of an appliance for service?

    Answer: 30 inches deep by 30 inches wide

    Section 306.1 requires a level working space at least 30 inches deep and 30 inches wide in front of the control side to service an appliance. The 36-inch dimension is the width of the passageway to a room containing appliances in Section 306.2. 24 inches is the minimum passageway width for appliances in a dwelling-unit compartment or alcove.

    Reference: 2021 International Mechanical Code, Section 306.1

  3. A listed heater requires 12 inches of clearance to a combustible wall without protection. The listing does not prohibit clearance reduction. The installer mounts 24-gage galvanized sheet steel spaced 1 inch off the wall on noncombustible spacers. Using IMC Table 308.4.2, what is the reduced clearance?

    Answer: 4 inches

    Table 308.4.2 has no 12-inch column, so Section 308.4.2 calls for linear interpolation. For vertical assemblies with 24-gage sheet steel spaced 1 inch off, 9 inches reduces to 3 inches and 18 inches reduces to 6 inches. Interpolating: 3 + (12 - 9) / (18 - 9) x (6 - 3) = 3 + 1 = 4 inches. Answering 3 inches uses the 9-inch column without interpolating. 6 inches uses the 18-inch column. 5 inches comes from the horizontal-above-the-heat-source column for 9 inches.

    Reference: 2021 International Mechanical Code, Section 308.4.2 and Table 308.4.2

  4. A 2,000-square-foot open office area is designed at the default occupant density in IMC Table 403.3.1.1. Using Equation 4-1 (Vbz = Rp x Pz + Ra x Az), what is the breathing-zone outdoor airflow?

    Answer: 170 cfm

    Table 403.3.1.1 lists office spaces at 5 people per 1,000 sq ft, Rp = 5 cfm/person and Ra = 0.06 cfm/sq ft. Population = 2,000 / 1,000 x 5 = 10 people. Vbz = 5 x 10 + 0.06 x 2,000 = 50 + 120 = 170 cfm. Using only the area term gives 120 cfm, and using only the people term gives 50 cfm. Using 7.5 cfm/person (the rate for many retail and assembly spaces) gives 75 + 120 = 195 cfm.

    Reference: 2021 International Mechanical Code, Table 403.3.1.1 and Section 403.3.1.1.1.1

  5. A new furnace return grille is planned in a basement mechanical room that also contains a natural-draft water heater with a draft hood. Under IMC Section 601.5, how far must the return air opening be from the draft hood?

    Answer: At least 10 feet in any direction

    Item 1 of Section 601.5 prohibits return air openings less than 10 feet, measured in any direction, from an open combustion chamber or draft hood of another appliance in the same room or space. This keeps the return from depressurizing the draft hood and pulling in flue gases. The 5-foot figure comes from the exception for a return in a dwelling kitchen near an electric cooking appliance.

    Reference: 2021 International Mechanical Code, Section 601.5, Item 1

  6. An enclosure holds appliances with a total input of 140,000 Btu/h. Combustion air will come from two permanent openings that communicate directly with the outdoors (IFGC Section 304.6.1). What is the minimum free area of each opening?

    Answer: 35 square inches

    Section 304.6.1 requires two openings, one starting within 12 inches of the top and one within 12 inches of the bottom of the enclosure. Where they communicate directly with the outdoors or through vertical ducts, each needs 1 sq in per 4,000 Btu/h: 140,000 / 4,000 = 35 sq in. 70 sq in is the horizontal-duct rate (1 per 2,000). 47 sq in is the one-opening rate (1 per 3,000). 140 sq in is the indoor same-story rate (1 per 1,000).

    Reference: 2021 International Fuel Gas Code, Section 304.6.1

  7. A sediment trap is not built into the appliance. Under IFGC Section 408.4, which of these new gas appliances must have a field-installed sediment trap?

    Answer: A water heater

    Section 408.4 requires a sediment trap downstream of the appliance shutoff valve, as close to the appliance inlet as practical, unless one is built into the appliance. The section exempts illuminating appliances, ranges, clothes dryers, decorative vented appliances for vented fireplaces, gas fireplaces and outdoor grills. A water heater isn't on that list, so it needs the trap (typically a tee with a capped vertical nipple, as in Figure 408.4).

    Reference: 2021 International Fuel Gas Code, Section 408.4

  8. Under IFGC Section 503.6.6, a Type B gas vent must terminate at least how far in vertical height above the highest connected appliance draft hood or flue collar?

    Answer: 5 feet

    Section 503.6.6 requires Type B and Type L gas vents to terminate at least 5 feet vertically above the highest connected draft hood or flue collar. The 12-foot figure applies to Type B-W vents, measured above the bottom of the wall furnace. Section 503.5.4 gives chimneys the same 5-foot rule.

    Reference: 2021 International Fuel Gas Code, Section 503.6.6

  9. An installer is running the discharge pipe from a hot water boiler's pressure relief valve. Which detail violates IMC Section 1006.6?

    Answer: The pipe ends with a threaded coupling 10 inches above the floor

    Section 1006.6 requires relief valve discharge piping to be rigid, rated for the temperature, full size to an air break in the same room, untrapped, gravity-flowing, free of valves and tees, and to terminate no more than 6 inches above the floor or waste receptor. It also prohibits a threaded connection at the end of the pipe. A threaded end at 10 inches violates two of these rules. The other choices comply.

    Reference: 2021 International Mechanical Code, Section 1006.6

  10. A den measures 12 ft x 14 ft with an 8-ft ceiling, and its only door can be closed. Under IFGC Section 621.5, what is the maximum aggregate input of unvented appliances allowed in the den?

    Answer: 26,880 Btu/h

    Section 621.5 limits the total input of all unvented appliances in a room to 20 Btu/h per cubic foot of room volume. Volume = 12 x 14 x 8 = 1,344 cu ft, and 1,344 x 20 = 26,880 Btu/h. An adjacent room's volume can be added only when it connects through an opening that can't be closed, so it doesn't count here. 40,000 Btu/h is the single-heater cap in Section 621.3, which this room's volume limit undercuts. 13,440 uses 10 Btu/h per cu ft, and 67,200 uses 50.

    Reference: 2021 International Fuel Gas Code, Section 621.5

Sources

Questions last verified October 21, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.