Colorado licensing exam

Colorado Residential Wireman Exam: Practice Test & Licensing Guide

The PSI Residential Wireman exam for the Colorado State Electrical Board: 90 questions on the 2026 NEC, open book, 70% to pass.

Questions
90
Time limit
4 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10General Electrical Knowledge

A 120/240-volt panelboard in a house garage faces a concrete block wall on the opposite side of the working space (Condition 2). Using Table 110.26(A)(1), what is the minimum depth of working space in front of the panel?

Requirements at a glance

AgencyColorado State Electrical Board (DORA); exam by PSI
Experience4,000 hours of residential-only experience over at least 2 years
Exam90 scored questions (plus unscored ones) in 240 minutes, 70% (63) to pass
Code book2026 NEC and a formula page
Fees$78 PSI exam ($73 retest), plus DORA's application fee

Electricians who work only on one- to four-family dwellings and have 4,000 hours of residential experience earned over at least two years.

How to get licensed, step by step

  1. Get your hours

    Work under a licensed electrician and keep records your supervisors can verify. 4,000 hours of residential-only experience over at least 2 years.

  2. Register with PSI

    Register and schedule online or by phone. The exam fee is good for one year.

    Schedule with PSI (Colorado electrical) (opens in a new tab)PSI: Colorado electrical candidate bulletin (opens in a new tab)

  3. Pass the Residential Wireman exam

    90 scored questions (plus unscored ones) in 240 minutes, 70% (63) to pass. The 2026 NEC and a formula page is provided at the test center.

  4. Apply to DORA

    After you pass, apply to the State Electrical Board with your experience verification. Passing doesn't guarantee a license until the board approves your hours.

    DORA: Electrical Board applications and requirements (opens in a new tab)

How to prepare

  • PSI hands you an unmarked code book: no tabs, highlights or notes. Practice with a clean copy and learn the index and the article/chapter layout instead of relying on tabs.
  • There's no per-section minimum, so don't get stuck. Skip hard lookups, finish the easy ones, then come back.
  • Services, feeders and branch circuits (18) and general knowledge (17) are over a third of the exam: dwelling receptacle, GFCI/AFCI and branch-circuit rules first.
  • Load calcs are in the new Article 120 in the 2026 NEC. Learn where the dwelling standard method lives.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2026 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (NEC), 2026 Edition, and a formula page (both provided at the test center)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
General Electrical Knowledge17
Services, Feeders, and Branch Circuits18
Grounding and Bonding13
Overcurrent Protection5
Conductors and Cables9
Raceways and Boxes9
Special Equipment5
Electrical Devices8
Electrical Calculations6

Exam day details

  • Administered by PSI Services for the Colorado State Electrical Board (DORA).
  • Fee: $78 to PSI ($73 to retake). The fee is valid for one year. DORA's license application fee is separate.
  • 90 scored questions in 240 minutes, plus up to 7 unscored questions with 30 extra minutes. You need 63 correct (70%).
  • Since August 1, 2026 the exam is based on the 2026 NEC. You can ask for the 2023 book until December 1, 2026. Load calculations moved to the new Article 120 in 2026.
  • PSI provides the code book and formula page. You can't bring your own books or write, highlight or tab the ones provided, so practice finding things in an unmarked code.
  • Overall score only: there is no minimum per section.
  • No Colorado law questions; the exam is NEC, theory and calculations.

Frequently asked questions

What NEC edition is the Colorado Residential Wireman exam based on?

The 2026 NEC since August 1, 2026. PSI will hand out the 2023 book on request until December 1, 2026; after that only the 2026 edition is offered.

What's on the Colorado Residential Wireman exam?

90 scored questions. The biggest areas are services, feeders and branch circuits (18), general electrical knowledge (17) and grounding and bonding (13), followed by conductors and cables (9) and raceways and boxes (9).

How many hours do I need for a Colorado residential wireman license?

4,000 hours of residential-only experience earned over no less than two years, verified to the State Electrical Board.

Free questions with answers

Show all 10 free questions and answers
  1. A 120/240-volt panelboard in a house garage faces a concrete block wall on the opposite side of the working space (Condition 2). Using Table 110.26(A)(1), what is the minimum depth of working space in front of the panel?

    Answer: 3 ft

    Each leg of a 120/240-volt system is 120 V to ground, which falls in the 0-150 V row of Table 110.26(A)(1). That row requires 3 ft (900 mm) for Conditions 1, 2 and 3 alike, so the concrete wall does not increase the depth. 3 ft 6 in. and 4 ft are Condition 2 and 3 values for the 151-600 V row; 30 in. is the minimum width of the space, not its depth.

    Reference: 2026 National Electrical Code (NFPA 70), Section 110.26(A)(1) and Table 110.26(A)(1)

  2. A new one-family house is being wired, and no separate emergency disconnect under 225.41 is planned. Under the 2026 NEC, where must the service disconnecting means go?

    Answer: Readily accessible outdoors, on the house or within sight of it

    For one- and two-family dwellings, 230.70(A)(1) requires the service disconnecting means in a readily accessible outdoor location, either on the dwelling or within sight of it, so first responders can cut power from outside. An exception applies where an emergency disconnect complying with 225.41 is installed. The nearest-point-of-entrance rule is the general rule for other buildings in 230.70(A)(2).

    Reference: 2026 National Electrical Code (NFPA 70), Section 230.70(A)(1)

  3. At a house, a single ground rod is tested and shows 40 ohms to earth. It is the only made electrode. What does 250.53(A) require?

    Answer: One supplemental electrode; a second rod must be 6 ft or more away

    Under 250.53(A)(2), a single rod, pipe or plate electrode must be supplemented by an additional electrode unless it has a resistance to earth of 25 ohms or less. One supplemental electrode satisfies the rule; the code does not require you to keep adding rods until 25 ohms is reached. Under 250.53(A)(3), multiple rods must be at least 6 ft apart, so 3 ft is too close.

    Reference: 2026 National Electrical Code (NFPA 70), Section 250.53(A)(2) and (A)(3)

  4. A large house has 250-kcmil copper service-entrance conductors. One grounding electrode conductor runs only to the concrete-encased electrode in the footing and goes to no other electrode. What is the largest copper GEC size the code requires for that conductor?

    Answer: 4 AWG

    Table 250.66 would require 2 AWG copper for copper conductors over 3/0 AWG through 350 kcmil. But 250.66(B) says the portion of the GEC that is the sole connection to a concrete-encased electrode is not required to be larger than 4 AWG copper. 2 AWG is the unreduced table value, and 6 AWG is the cap for rod, pipe or plate electrodes in 250.66(A), not for a concrete-encased electrode.

    Reference: 2026 National Electrical Code (NFPA 70), Section 250.66(B) and Table 250.66

  5. A 240-volt branch circuit to a house air handler uses 6 AWG THWN-2 copper with all terminations rated 75°C. There are three current-carrying conductors at a 30°C ambient. Using Table 310.16, what ampacity may be used for the circuit?

    Answer: 65 A

    Table 310.16 lists 6 AWG copper at 55 A (60°C), 65 A (75°C) and 75 A (90°C). THWN-2 is a 90°C insulation, but 110.14(C) limits the usable ampacity to the lowest-rated termination, here 75°C, so 65 A is used. 75 A would apply only if every termination were rated 90°C, 55 A is the 60°C value, and 50 A is 8 AWG at 75°C.

    Reference: 2026 National Electrical Code (NFPA 70), Table 310.16 and Section 110.14(C)

  6. A metal device box with internal cable clamps contains two 12/2 NM cables and one 12/3 NM cable, all with a bare equipment grounding conductor, plus one duplex receptacle. Splices are made with twist-on connectors. Using 314.16(B), what is the minimum box volume?

    Answer: 24.75 in³

    Count 12 AWG volume allowances: insulated conductors 2 + 2 + 3 = 7; internal cable clamps (any number) = 1; the receptacle yoke = 2; all equipment grounding conductors together = 1. Total 11 × 2.25 in³ (Table 314.16(B)(1), 12 AWG) = 24.75 in³. Splicing connectors get no allowance. 22.50 in³ leaves out the clamps, 29.25 in³ counts each ground separately, and 22.00 in³ uses the 14 AWG volume of 2.00 in³.

    Reference: 2026 National Electrical Code (NFPA 70), Section 314.16(B) and Table 314.16(B)(1)

  7. A 15-ampere general-purpose receptacle circuit in a house bedroom will supply a single cord-and-plug-connected window air conditioner. Under 210.23(B)(1), what is the maximum rating of that one appliance?

    Answer: 12 A

    Section 210.23(B)(1) limits a single cord-and-plug-connected utilization equipment item on a 15- or 20-ampere branch circuit to 80% of the branch-circuit rating: 15 × 0.80 = 12 A. 7.5 A is the 50% limit for fastened-in-place equipment under 210.23(B)(2), and 15 A ignores the 80% limit.

    Reference: 2026 National Electrical Code (NFPA 70), Section 210.23(B)(1)

  8. Unless another section specifically permits otherwise, what is the largest overcurrent device allowed on a 12 AWG copper branch circuit in a house?

    Answer: 20 A

    Section 240.4(D) limits small copper conductors: 14 AWG to 15 A, 12 AWG to 20 A, and 10 AWG to 30 A, after any correction and adjustment factors. 25 A is the 75°C table ampacity of 12 AWG copper, but 240.4(D) caps the overcurrent device at 20 A. 15 A is the limit for 14 AWG and 30 A is the limit for 10 AWG.

    Reference: 2026 National Electrical Code (NFPA 70), Section 240.4(D)

  9. A homeowner wants a chain-hung pendant luminaire over the master bathtub. Under 410.10(D), within what zone measured from the top of the tub rim is this type of luminaire not allowed?

    Answer: 3 ft horizontally and 8 ft vertically

    Section 410.10(D) prohibits any part of cord-connected luminaires, chain-, cable- or cord-suspended luminaires, lighting track, pendants and ceiling-suspended (paddle) fans within a zone 3 ft horizontally and 8 ft vertically from the top of the bathtub rim or shower stall threshold. The 5 ft and 12 ft values come from the outdoor pool rule in 680.22(B), and 6 ft 7 in. is the switch and breaker handle height limit.

    Reference: 2026 National Electrical Code (NFPA 70), Section 410.10(D)

  10. A house service will supply four fastened-in-place appliances: a 1,150-VA dishwasher, a 1,000-VA disposal, a 4,000-VA water heater and a 1,400-VA built-in microwave. There is no range, dryer, space heating or air conditioning among them. Under 120.53, what load is used for these appliances?

    Answer: 5,663 VA

    Section 120.53 allows a 75% demand factor for four or more fastened-in-place appliances (other than ranges, dryers, space heating, air conditioning and EVSE) on the same service, each rated at least 1/4 hp or 500 W. Total nameplate 1,150 + 1,000 + 4,000 + 1,400 = 7,550 VA, and 7,550 × 0.75 = 5,662.5 VA, or about 5,663 VA. 7,550 VA applies no demand factor, 6,040 VA uses 80%, and 3,775 VA uses 50%.

    Reference: 2026 National Electrical Code (NFPA 70), Section 120.53