Colorado licensing exam

Colorado Master Electrician Exam: Practice Test & Licensing Guide

The PSI Master Electrician exam for the Colorado State Electrical Board: 90 questions on the 2026 NEC, weighted toward grounding, services and special occupancies.

Questions
90
Time limit
4 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Electrical Calculations

Eight current-carrying 6 AWG THHN copper conductors are installed in one raceway where the ambient temperature is 40 degrees C (104 degrees F). Starting from the 90 degree C column of Table 310.16, what is the adjusted ampacity of each conductor?

Requirements at a glance

AgencyColorado State Electrical Board (DORA); exam by PSI
Experience10,000 hours over at least 5 years, or an EE degree + 2,000 hours, or trade school + 8,000 hours, including planning/layout and supervision as a journeyman
Exam90 scored questions (plus unscored ones) in 240 minutes, 70% (63) to pass
Code book2026 NEC and a formula page
Fees$78 PSI exam ($73 retest), plus DORA's application fee

Electricians with 10,000 hours over at least five years (or an EE degree or trade-school route), including planning and layout and time supervising as a licensed journeyman.

How to get licensed, step by step

  1. Get your hours

    Work under a licensed electrician and keep records your supervisors can verify. 10,000 hours over at least 5 years, or an EE degree + 2,000 hours, or trade school + 8,000 hours, including planning/layout and supervision as a journeyman.

  2. Register with PSI

    Register and schedule online or by phone. The exam fee is good for one year.

    Schedule with PSI (Colorado electrical) (opens in a new tab)PSI: Colorado electrical candidate bulletin (opens in a new tab)

  3. Pass the Master Electrician exam

    90 scored questions (plus unscored ones) in 240 minutes, 70% (63) to pass. The 2026 NEC and a formula page is provided at the test center.

  4. Apply to DORA

    After you pass, apply to the State Electrical Board with your experience verification. Passing doesn't guarantee a license until the board approves your hours.

    DORA: Electrical Board applications and requirements (opens in a new tab)

How to prepare

  • PSI hands you an unmarked code book: no tabs, highlights or notes. Practice with a clean copy and learn the index and the article/chapter layout instead of relying on tabs.
  • There's no per-section minimum, so don't get stuck. Skip hard lookups, finish the easy ones, then come back.
  • Special occupancies and special equipment are 18 questions: hazardous locations, health care, assembly, and Chapter 6 equipment.
  • Expect commercial load calculations and motor feeder sizing in the 9 calculation questions.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2026 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (NEC), 2026 Edition, and a formula page (both provided at the test center)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
General Electrical Knowledge6
Services, Feeders, and Branch Circuits11
Grounding and Bonding14
Overcurrent Protection5
Conductors and Cables4
Raceways and Boxes5
Special Conditions2
Special Occupancies9
Special Equipment9
Electrical Devices4
Motors8
Transformers4
Electrical Calculations9

Exam day details

  • Administered by PSI Services for the Colorado State Electrical Board (DORA).
  • Fee: $78 to PSI ($73 to retake). The fee is valid for one year. DORA's license application fee is separate.
  • 90 scored questions in 240 minutes, plus up to 10 unscored questions with 30 extra minutes. You need 63 correct (70%).
  • Since August 1, 2026 the exam is based on the 2026 NEC. You can ask for the 2023 book until December 1, 2026. Load calculations moved to the new Article 120 in 2026.
  • PSI provides the code book and formula page. You can't bring your own books or write, highlight or tab the ones provided, so practice finding things in an unmarked code.
  • Overall score only: there is no minimum per section.
  • No Colorado law questions; the exam is NEC, theory and calculations.

Frequently asked questions

What NEC edition is the Colorado master electrician exam based on?

The 2026 NEC since August 1, 2026, provided at the test center along with a formula page.

What's on the Colorado Master Electrician exam?

90 scored questions. Grounding and bonding (14) and services, feeders and branch circuits (11) lead, then special occupancies, special equipment and calculations (9 each) and motors (8).

What experience does a Colorado master electrician need?

One of: 10,000 hours over at least five years; an electrical engineering degree plus 2,000 hours; or trade school plus 8,000 hours. Some hours must be planning and layout, and some must be supervision while holding a journeyman license.

Free questions with answers

Show all 10 free questions and answers
  1. Eight current-carrying 6 AWG THHN copper conductors are installed in one raceway where the ambient temperature is 40 degrees C (104 degrees F). Starting from the 90 degree C column of Table 310.16, what is the adjusted ampacity of each conductor?

    Answer: 47.8 A

    Table 310.16, 90 degree C column: 6 AWG THHN = 75 A. Table 310.15(B)(1)(1) correction for 36-40 degrees C in the 90 degree C column = 0.91. Table 310.15(C)(1) adjustment for 7-9 current-carrying conductors = 70%. 75 x 0.91 x 0.70 = 47.8 A. 68.3 A applies only the temperature correction, 52.5 A only the bundling adjustment, and 40.0 A starts from the 75 degree C column (65 A x 0.88 x 0.70).

    Reference: 2026 National Electrical Code (NFPA 70), Table 310.16; Table 310.15(B)(1)(1); Table 310.15(C)(1)

  2. A 40 hp, 460-volt, 3-phase squirrel-cage motor (not Design B energy-efficient, BE or CE) is protected by an inverse-time circuit breaker. Using Table 430.52(C)(1) and the next-size-up provision, what is the largest breaker permitted for branch-circuit short-circuit and ground-fault protection without applying the increased limits of 430.52(C)(1)(b)?

    Answer: 150 A

    Table 430.250: 40 hp at 460 V = 52 A. Table 430.52(C)(1) allows an inverse-time breaker at 250%: 52 x 2.5 = 130 A. 130 A is not a standard rating, so 430.52(C)(1)(a) permits the next higher standard size from 240.6(A), 150 A. 125 A rounds down, 110 A is about 210%, and 175 A goes beyond the next standard size.

    Reference: 2026 National Electrical Code (NFPA 70), Table 430.250; Table 430.52(C)(1); 430.52(C)(1)(a); 240.6(A)

  3. An office building's step-down unit (112.5 kVA, three-phase, 480 V delta to 208Y/120 V) has overcurrent devices on both its line side and its load side. Under Table 450.5(B), what is the highest standard rating allowed for the load-side device?

    Answer: 400 A

    Secondary current = 112,500 / (208 x 1.732) = 312.3 A. With primary and secondary protection, Table 450.5(B) limits the secondary device to 125% for currents of 9 A or more: 312.3 x 1.25 = 390.3 A. Note 1 allows the next higher standard rating, 400 A. 350 A is below the calculated value (allowed but not the largest), and 450 A and 500 A exceed the next-size-up allowance.

    Reference: 2026 National Electrical Code (NFPA 70), Table 450.5(B) and Note 1; 240.6(A)

  4. A 208Y/120-volt panelboard in an office building has exposed live parts on its front only. Directly across the working space is a concrete block wall. Using Table 110.26(A)(1), what minimum depth of working space is required in front of the panelboard?

    Answer: 3 ft

    Table 110.26(A)(1) is entered by nominal voltage to ground, not line-to-line voltage. A 208Y/120-volt system is 120 volts to ground, so the 0-150 volt row applies, and that row requires 3 ft for Conditions 1, 2 and 3. The concrete wall (grounded) would make this Condition 2, but the answer is still 3 ft. 3-1/2 ft is the Condition 2 value for the 151-600 volt row; it applies only if you enter the table with 208 V.

    Reference: 2026 National Electrical Code (NFPA 70), 110.26(A)(1); Table 110.26(A)(1)

  5. A commercial feeder supplies 180 A of continuous load and 60 A of noncontinuous load. The conductors are THWN copper and all terminations are rated 75 degrees C. No adjustment or correction factors apply. What is the minimum conductor size under 215.4(A)(1)?

    Answer: 300 kcmil

    215.4(A)(1) requires a minimum ampacity of 125% of the continuous load plus 100% of the noncontinuous load: (180 x 1.25) + 60 = 225 + 60 = 285 A. In the 75 degrees C column of Table 310.16, 250 kcmil is 255 A (too small) and 300 kcmil is 285 A, so 300 kcmil is the minimum. 250 kcmil comes from forgetting the 125% (180 + 60 = 240 A). 350 kcmil (310 A) works but is not the minimum, and 4/0 AWG (230 A) is too small either way.

    Reference: 2026 National Electrical Code (NFPA 70), 215.4(A)(1); Table 310.16

  6. Under 215.18(A), a surge-protective device must be installed where a feeder supplies which of the following?

    Answer: Guest rooms and guest suites of a hotel

    215.18(A) lists the feeder loads that require an SPD: dwelling units; dormitories; guest rooms and guest suites of hotels, motels and dormitories; areas of nursing homes and limited-care facilities used only as patient sleeping rooms; and sleeping quarters in fire, police, ambulance, rescue, ranger and similar stations. Retail, restaurant and office feeders are not on the list (although an SPD is always allowed).

    Reference: 2026 National Electrical Code (NFPA 70), 215.18(A)

  7. A 480Y/277-volt service has three parallel sets of 400 kcmil copper ungrounded conductors per phase. The grounding electrode conductor runs to the building steel and the water pipe electrode. Using Table 250.66, what is the minimum copper grounding electrode conductor?

    Answer: 3/0 AWG

    For parallel service conductors, Table 250.66 is entered with the equivalent area of the largest ungrounded conductor set: 3 x 400 = 1200 kcmil. The row for copper over 1100 kcmil requires a 3/0 AWG copper GEC. 1/0 AWG is the answer for a single 400 kcmil set (over 350 through 600 kcmil), which forgets to add the parallel sets. Table 250.66 tops out at 3/0, so 4/0 and 250 kcmil are never required by this table.

    Reference: 2026 National Electrical Code (NFPA 70), 250.66; Table 250.66

  8. A detached commercial building is supplied by a 4-wire feeder that includes an equipment grounding conductor. At the building disconnecting means, how must the grounded (neutral) conductor be treated under 250.32(B)(1)?

    Answer: It must not be connected to the equipment grounding conductors or the grounding electrodes

    250.32(B)(1) requires the EGC run with the feeder to be connected to the building disconnect enclosure and to the grounding electrode conductor, and it prohibits connecting the grounded conductor to the EGCs or to the grounding electrodes. A neutral-to-ground bond at the second building would put neutral current on the EGC and on metal paths between buildings. Only installations made under earlier editions that permitted it may keep using the neutral as the fault return path (Exception No. 1).

    Reference: 2026 National Electrical Code (NFPA 70), 250.32(B)(1)

  9. Branch circuits serving patient care spaces in a hospital are run in Type MC cable whose armor qualifies as an equipment grounding conductor. Under the 2026 wording of 517.13(A), which box may be used at the receptacle outlets?

    Answer: A metallic outlet box

    517.13(A) requires branch circuits serving patient care spaces to have an effective ground-fault current path by installation in a metal raceway system or a cable with a metallic armor or sheath assembly. The 2026 NEC added that this includes metallic outlet boxes, device boxes, junction boxes, fittings and other wiring enclosures. A nonmetallic box would break the metallic path that forms one half of the redundant grounding scheme (the other half is the insulated copper EGC required by 517.13(B)).

    Reference: 2026 National Electrical Code (NFPA 70), 517.13(A)

  10. Under the 2026 revision of 680.26(B)(2), the perimeter surface around a permanently installed swimming pool that must be bonded extends how far?

    Answer: 3 ft horizontally from the inside walls, between 3 ft above and 3 ft below the maximum water level

    The 2026 NEC revised 680.26(B)(2) so that the perimeter surface to be bonded extends 3 ft horizontally beyond the inside walls of the pool, at a height between 3 ft above and 3 ft below the maximum water level. The surface includes unpaved surfaces, concrete, masonry pavers and other paving. Surfaces separated from the pool by a permanent wall or building 5 ft or more in height need bonding only on the pool side. The older text measured from a point 2 ft below the water level.

    Reference: 2026 National Electrical Code (NFPA 70), 680.26(B)(2)