Virginia licensing exam

Virginia Master Electrician Exam: Practice Test & Licensing Guide

The PSI exam for Virginia's master electrician license: 90 open-book questions on the 2020 NEC, services and feeders, grounding, motors and the Board's rules. 63 correct to pass.

Questions
90
Time limit
4.5 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Services Feeders and Branch Circuits

A restaurant has eight pieces of permanently installed commercial electric cooking equipment rated 7, 6, 5, 4, 3, 2.5, 1.5 and 1 kW. Using Table 220.56, what is the demand load for the cooking equipment?

Requirements at a glance

AgencyVirginia Department of Professional and Occupational Regulation (DPOR), Board for Contractors; exams by PSI
Experience1 year as a journeyman, 3 years as a residential license holder, or 9 years of experience
Exammaster electrician exam: 90 items, 270 minutes, 63 correct
Books allowed2020 NEC and the American Electricians' Handbook, 16th Edition
Fees$125 to PSI; $150 original DPOR license

Electricians applying to the Virginia Board for Contractors for a master electrician license, for example after a year as a journeyman.

How to get licensed, step by step

  1. Check the education and experience rules

    You must be 18 and document training and work experience. The requirements depend on the license level; see 18VAC50-30-39.

    Virginia Administrative Code 18VAC50-30 (tradesman regulations) (opens in a new tab)Virginia DPOR: Tradesmen licensing (opens in a new tab)

  2. Apply to the Board for Contractors

    The Board reviews your application first and approves you to take the exam. Disclose any convictions.

    Virginia DPOR: Tradesmen licensing (opens in a new tab)

  3. Register and schedule the master electrician exam with PSI

    After approval, pay PSI and book a seat. Your eligibility is good for one year and you can retake within that year.

    Schedule with PSI (Virginia DPOR exams) (opens in a new tab)

  4. Get licensed

    Send your passing result to the Board with the license fee ($150 for an original journeyman or master license; additional designations $105). Trade licenses run three years and need continuing education (3 hours per designation) on the current code edition.

    Virginia DPOR: Tradesmen licensing (opens in a new tab)Virginia Administrative Code 18VAC50-30 (tradesman regulations) (opens in a new tab)

How to prepare

  • Bring the editions on PSI's list: the 2020 NEC for electrical and the 2021 IPC, IMC and IFGC (Virginia Plumbing, Mechanical and Fuel Gas Codes) for plumbing, HVAC and gas. Virginia's 2024 code cycle (NEC 2023 and the 2024 I-codes) is tentatively set to take effect in October 2027; until PSI publishes a new bulletin, code questions use the 2021 USBC editions.
  • Exam fees may change: a rule effective 3/11/2026 raised the Board's exam fee caps, though DPOR still lists $100 for journeyman and $125 for master exams. Confirm the fee with PSI when you register.
  • Tab your books before exam day with permanent tabs. You can highlight, underline and index, but you can't write in them, use removable tabs or bring loose papers or study guides.
  • Ten items on every journeyman and master exam (nine on the residential exams) come from the Board's rules, 18VAC50-30. They are easy points if you read the regulation once.
  • Services, feeders and branch circuits (9), grounding and bonding (9), motors and controls (8) and raceways (8) lead the exam. Service and feeder requirements jump to 6 items, mostly load calculations in Article 220.
  • Fundamentals (5) means Ohm's law, power and voltage drop math; practice with the American Electricians' Handbook formulas.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2020 NEC and 18VAC50-30. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • National Electrical Code (NFPA 70), 2020 edition; the Virginia Electrical Code adopts it (code questions use only the listed edition)
  • American Electricians' Handbook, 16th Edition
  • Board for Contractors Individual License and Certification Regulations (18VAC50-30)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
Standards of Practice3
Standards of Conduct2
Renewal and Reinstatement2
Definitions1
Qualification for Licensure1
Revocation1
General Electrical Knowledge4
Requirements for Electrical Installations4
Electrical-Electronic Fundamentals5
Services Feeders and Branch Circuits9
Service and Feeder Requirements6
Grounding and Bonding9
Conductors and Cables7
Raceways and Boxes8
Special Occupancies4
Special Equipment2
Electrical Signs and Outline Lighting2
Motors and Controls8
Utilization Equipment6
Lighting2
General Low Voltage1
Communication Systems1
Fire Detection and Alarm2

Exam day details

  • Administered by PSI Services for the Virginia Department of Professional and Occupational Regulation (DPOR), Board for Contractors.
  • Fee: $125 to PSI per exam, not refundable or transferable and valid for one year. DPOR application and license fees are separate.
  • 90 items in 270 minutes; 63 correct (70%) to pass.
  • The PSI bulletin (1/14/2025) lists the 2020 NEC (the 2017 edition was also accepted until 5/1/2025). Code questions are based only on the listed edition. Check the current bulletin for the edition on your test date.
  • Eligibility: 1 year as a journeyman, 3 years as a residential license holder, or 9 years of experience, as decided by the Board (18VAC50-30-39).
  • Open book: bring your own bound copies of the listed references. You may highlight, underline and index them beforehand and add permanent tabs, but removable tabs, loose papers, writing and study guides are not allowed.
  • PSI may add unscored experimental questions to the exam.
  • Exam fees may change: a rule effective 3/11/2026 raised the Board's exam fee caps, though DPOR still lists $100 (journeyman) and $125 (master). Confirm the fee with PSI when you register.
  • The Board for Contractors must approve your application first (education and experience); then you pay and register with PSI. Your exam eligibility is good for one year and you can retake within that year.
  • Every Virginia tradesman exam includes 10 items on the Board's rules (18VAC50-30): standards of practice, standards of conduct, renewal and reinstatement, definitions, qualification for licensure and revocation.

Note: These facts come from the PSI bulletin dated 1/14/2025; no newer bulletin was found. The 2021 Virginia USBC (NEC 2020 and the 2021 I-codes) is in force now. Virginia's 2024 code cycle (NEC 2023 and the 2024 I-codes) is tentatively scheduled to take effect in October 2027, and PSI will likely update its bulletin then; that date is not confirmed. Check the current PSI bulletin before you test.

Frequently asked questions

How is the master exam different from the journeyman exam?

It is longer (90 items vs. 70) and weights services and feeders, grounding, motors and fundamentals more heavily. Both are open book on the 2020 NEC.

How many do I need to pass?

63 of 90 items.

How long do I get?

270 minutes (4.5 hours).

Free questions with answers

Show all 10 free questions and answers
  1. A restaurant has eight pieces of permanently installed commercial electric cooking equipment rated 7, 6, 5, 4, 3, 2.5, 1.5 and 1 kW. Using Table 220.56, what is the demand load for the cooking equipment?

    Answer: 19.5 kW

    Connected load = 7 + 6 + 5 + 4 + 3 + 2.5 + 1.5 + 1 = 30.0 kW. Table 220.56 allows 65% for six or more units: 30.0 x 0.65 = 19.5 kW, more than the two largest units (7 + 6 = 13 kW). 70% (21.0 kW) is the five-unit factor, 80% (24.0 kW) the four-unit factor and 30.0 kW applies no demand at all.

    Reference: NFPA 70, National Electrical Code, 2020, 220.56, Table 220.56

  2. Overhead 120/240-volt service conductors cross a non-residential driveway used by delivery trucks. What is the minimum vertical clearance above the driveway under 230.24(B)?

    Answer: 18 ft

    Section 230.24(B) sets 18 ft over public streets, roads, non-residential driveways, truck-traffic areas and other land traversed by vehicles. 12 ft applies only over residential property and residential driveways at 300 volts or less to ground, and 10 ft over areas accessible only to pedestrians. 15 ft applies to residential areas above 300 volts to ground.

    Reference: NFPA 70, National Electrical Code, 2020, 230.24(B)(4)

  3. A service uses two parallel sets of 3/0 AWG copper ungrounded conductors per phase (3/0 AWG = 167,800 circular mils). Using Table 250.66, what is the minimum copper grounding electrode conductor to a metal underground water pipe electrode?

    Answer: 2 AWG

    For parallel sets, size the grounding electrode conductor from the total circular-mil area of the conductors in one phase: 2 x 167,800 = 335,600 CM, about 336 kcmil. Table 250.66 requires 2 AWG copper for ungrounded conductors over 3/0 through 350 kcmil. 4 AWG is for a single 2/0 or 3/0 conductor, 1/0 is for over 350 through 600 kcmil, and 3/0 is the largest size in the table, used only for very large services.

    Reference: NFPA 70, National Electrical Code, 2020, Table 250.66; 250.66

  4. Seven current-carrying 4 AWG THHN copper conductors are installed in one conduit at a 30 degrees C ambient. Table 310.16 gives 95 A at 90 degrees C and 85 A at 75 degrees C, and the terminals are rated 75 degrees C. What ampacity may be used for each conductor?

    Answer: 66.5 A

    Seven to nine current-carrying conductors take a 70% adjustment, applied to the 90 degrees C ampacity: 95 x 0.70 = 66.5 A. That is below the 85 A terminal limit, so 66.5 A governs. 76 A uses the 80% factor for 4 to 6 conductors, 59.5 A applies 70% to the 75 degrees C value, and 85 A ignores the adjustment.

    Reference: NFPA 70, National Electrical Code, 2020, 310.15(C)(1), Table 310.16

  5. Two 3/0 AWG THHN conductors (0.2679 sq in each) and four 10 AWG THHN conductors (0.0211 sq in each) are to be installed in EMT. The 40% fill areas from Chapter 9 Table 4 are: 1 in = 0.346 sq in, 1-1/4 in = 0.598 sq in, 1-1/2 in = 0.814 sq in, 2 in = 1.342 sq in. What is the smallest trade size of EMT?

    Answer: 1-1/2 in

    Conductor area = 2 x 0.2679 + 4 x 0.0211 = 0.5358 + 0.0844 = 0.6202 sq in. More than two conductors are limited to 40% fill (Chapter 9, Table 1). 1-1/4 in EMT allows only 0.598 sq in, just short, so the smallest size is 1-1/2 in (0.814 sq in). 1 in is much too small and 2 in is larger than necessary.

    Reference: NFPA 70, National Electrical Code, 2020, Chapter 9, Table 1, Table 4 (EMT), Table 5

  6. The four motors in a feeder have Table 430.250 full-load currents of 40, 27, 21 and 11 A. The branch-circuit inverse time breaker for the 40 A motor is 100 A (250% of full-load current). What is the maximum standard rating of the feeder overcurrent device under 430.62(A)?

    Answer: 150 A

    The feeder device may not exceed the largest branch-circuit protective device plus the full-load currents of the other motors: 100 + 27 + 21 + 11 = 159 A. The next lower standard size, 150 A, is the maximum; 160 A is not a standard size and 175 A exceeds the limit. 125 A is permitted but is not the largest permitted.

    Reference: NFPA 70, National Electrical Code, 2020, 430.62(A); 240.6(A)

  7. A 5,500-watt, 240-volt storage-type water heater with a capacity of 50 gallons is supplied by its own branch circuit. What is the minimum standard rating of the overcurrent device, considering the heater load at 125 percent?

    Answer: 30 A

    Heater current = 5,500 / 240 = 22.9 A. A storage water heater is treated as a continuous load under 422.13, so the branch-circuit rating must be at least 125%: 22.9 x 1.25 = 28.6 A. The next standard size in 240.6(A) is 30 A. 25 A is the next size above the load without the factor and 20 A is below the load; 35 A is larger than necessary.

    Reference: NFPA 70, National Electrical Code, 2020, 422.13; 240.6(A)

  8. On a 4-wire delta system with the midpoint of one winding grounded (240/120 volts), how must the conductor with the higher voltage to ground be identified?

    Answer: By an outer finish of orange color or other effective means

    Section 110.15 requires the phase conductor with the higher voltage to ground (about 208 V, the high leg) to be durably marked orange or identified by other effective means at each point where a connection is made if the grounded conductor is also present. White is reserved for the grounded conductor.

    Reference: NFPA 70, National Electrical Code, 2020, 110.15

  9. A 5,000-watt, 240-volt electric heating element is connected to a 208-volt supply. Assuming its resistance does not change, what power does it draw?

    Answer: About 3,756 W

    Resistance R = E squared / P = 240 x 240 / 5,000 = 11.52 ohms. At 208 volts P = 208 x 208 / 11.52 = 3,756 W. Power varies with the square of the voltage, so scaling linearly (5,000 x 208/240 = 4,333 W) overstates it, and 6,657 W inverts the ratio.

    Reference: General electrical theory: power and Ohm's law, Ohm's law and power formulas: P = E squared / R

  10. A Class A ground-fault circuit interrupter used for personnel protection opens the circuit when the ground-fault current reaches about what value?

    Answer: About 5 mA, within a range of 4 to 6 mA of current leaving on the ground path

    The Article 100 definition of a GFCI refers to the Class A device, which trips when the current to ground is in the 4 to 6 milliampere range (UL 943). The larger values are within the range that can cause fatal ventricular fibrillation, so devices set that high would not protect people.

    Reference: NFPA 70, National Electrical Code, 2020, Article 100, Definitions (Ground-Fault Circuit Interrupter)

Sources

Questions last verified November 14, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.