Requirements at a glance
| Agency | Virginia Department of Professional and Occupational Regulation (DPOR), Board for Contractors; exams by PSI |
|---|---|
| Experience | Journeyman: 8 years of experience alone, or school hours plus fewer years; master: 1 year as a journeyman or 9 years of experience |
| Exam | HVAC exam (journeyman and master): 85 items, 210 minutes, 60 correct (journeyman) or 64 (master) |
| Books allowed | 2021 IMC (Virginia Mechanical Code), NFPA 31 (2011) and Modern Refrigeration and Air Conditioning, 22nd Edition |
| Fees | $100 (journeyman) or $125 (master) to PSI; $150 original DPOR license |
HVAC mechanics applying to the Virginia Board for Contractors for a journeyman or master HVAC license. Both levels take the same exam with different pass scores.
Official links
How to get licensed, step by step
Check the education and experience rules
You must be 18 and document training and work experience. The requirements depend on the license level; see 18VAC50-30-39.
Virginia Administrative Code 18VAC50-30 (tradesman regulations) (opens in a new tab)Virginia DPOR: Tradesmen licensing (opens in a new tab)
Apply to the Board for Contractors
The Board reviews your application first and approves you to take the exam. Disclose any convictions.
Register and schedule the HVAC exam (journeyman and master) with PSI
After approval, pay PSI and book a seat. Your eligibility is good for one year and you can retake within that year.
Schedule with PSI (Virginia DPOR exams) (opens in a new tab)
Get licensed
Send your passing result to the Board with the license fee ($150 for an original journeyman or master license; additional designations $105). Trade licenses run three years and need continuing education (3 hours per designation) on the current code edition.
Virginia DPOR: Tradesmen licensing (opens in a new tab)Virginia Administrative Code 18VAC50-30 (tradesman regulations) (opens in a new tab)
How to prepare
- Bring the editions on PSI's list: the 2020 NEC for electrical and the 2021 IPC, IMC and IFGC (Virginia Plumbing, Mechanical and Fuel Gas Codes) for plumbing, HVAC and gas. Virginia's 2024 code cycle (NEC 2023 and the 2024 I-codes) is tentatively set to take effect in October 2027; until PSI publishes a new bulletin, code questions use the 2021 USBC editions.
- Exam fees may change: a rule effective 3/11/2026 raised the Board's exam fee caps, though DPOR still lists $100 for journeyman and $125 for master exams. Confirm the fee with PSI when you register.
- Tab your books before exam day with permanent tabs. You can highlight, underline and index, but you can't write in them, use removable tabs or bring loose papers or study guides.
- Ten items on every journeyman and master exam (nine on the residential exams) come from the Board's rules, 18VAC50-30. They are easy points if you read the regulation once.
- Warm air heating, ventilation and air conditioning are 8 items each. Tab IMC Chapters 4, 5, 6 and 9 and Chapter 8 for chimneys and vents.
- Commercial kitchen venting (5) comes from IMC Chapter 5 (Type I and II hoods); boilers (5) from Chapter 10.
- Start with the free questions above to find your weak topics, then drill those first.
- Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
- Read every explanation, including for questions you got right, and look the section up in your own book.
Books for this exam
This is an open-book exam: you can bring the references below, and most questions come from the Virginia Mechanical Code and 18VAC50-30. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.
2021 Virginia Mechanical Code (2021 IMC with Virginia amendments)Essential
Allowed in the exam room. The core of both HVAC exams.
ICC store (opens in a new tab)Read free (UpCodes) (opens in a new tab)
NFPA 31: Standard for the Installation of Oil-Burning Equipment, 2011
Allowed in the HVAC exam room. Fuel oil piping and storage.
Modern Refrigeration and Air Conditioning, 22nd Edition (Goodheart-Willcox)
Allowed in the exam room. Refrigeration cycle, components, controls and piping.
Board for Contractors Individual License and Certification Regulations (18VAC50-30)Essential
Free online. Ten items on every journeyman and master exam come from this regulation.
Virginia Administrative Code 18VAC50-30 (tradesman regulations) (opens in a new tab)
Official reference list (as published by the testing agency)
- International Mechanical Code (IMC), 2021, with Virginia amendments (Virginia Mechanical Code)
- NFPA 31, Standard for the Installation of Oil-Burning Equipment, 2011
- Modern Refrigeration and Air Conditioning, 22nd Edition, Goodheart-Willcox
- Board for Contractors Individual License and Certification Regulations (18VAC50-30)
What's on the exam
Official content outline from PSI Services (number of questions per topic):
| Topic | Questions | |
|---|---|---|
| Standards of Practice | 3 | |
| Standards of Conduct | 2 | |
| Renewal and Reinstatement | 2 | |
| Definitions | 1 | |
| Qualification for Licensure | 1 | |
| Revocation | 1 | |
| Warm Air Heating | 8 | |
| Ventilation | 8 | |
| Air Conditioning | 8 | |
| Duct Systems | 6 | |
| Chimneys Flues and Vents | 6 | |
| Boilers | 5 | |
| Hot Water Piping | 4 | |
| Combustion Air | 4 | |
| Controls/Low Voltage | 4 | |
| Fuel Oil Piping and Storage | 3 | |
| Insulation | 3 | |
| Commercial Kitchen Venting | 5 | |
| Refrigerants | 3 | |
| Refrigerant Piping | 3 | |
| Chilled and Condenser Water Piping | 3 | |
| Firestopping/Penetration | 2 |
Exam day details
- Administered by PSI Services for the Virginia Department of Professional and Occupational Regulation (DPOR), Board for Contractors.
- Fee: $100 (journeyman) or $125 (master) to PSI per exam, not refundable or transferable and valid for one year. DPOR application and license fees are separate.
- 85 items in 210 minutes. Journeyman passing score 60 (about 71%); master passing score 64 (about 75%).
- Eligibility: 8 years of experience alone, or school hours plus fewer years for a journeyman; 1 year as a journeyman or 9 years of experience for a master (18VAC50-30-39).
- Open book: bring your own bound copies of the listed references. You may highlight, underline and index them beforehand and add permanent tabs, but removable tabs, loose papers, writing and study guides are not allowed.
- PSI may add unscored experimental questions to the exam.
- Exam fees may change: a rule effective 3/11/2026 raised the Board's exam fee caps, though DPOR still lists $100 (journeyman) and $125 (master). Confirm the fee with PSI when you register.
- The Board for Contractors must approve your application first (education and experience); then you pay and register with PSI. Your exam eligibility is good for one year and you can retake within that year.
- Every Virginia tradesman exam includes 10 items on the Board's rules (18VAC50-30): standards of practice, standards of conduct, renewal and reinstatement, definitions, qualification for licensure and revocation.
Note: These facts come from the PSI bulletin dated 1/14/2025; no newer bulletin was found. The 2021 Virginia USBC (NEC 2020 and the 2021 I-codes) is in force now. Virginia's 2024 code cycle (NEC 2023 and the 2024 I-codes) is tentatively scheduled to take effect in October 2027, and PSI will likely update its bulletin then; that date is not confirmed. Check the current PSI bulletin before you test.
Frequently asked questions
What score do I need on the Virginia HVAC exam?
60 of 85 for a journeyman license and 64 of 85 for a master license. It is one shared exam.
Which books can I bring?
The 2021 International Mechanical Code (Virginia Mechanical Code), NFPA 31 (2011) and Modern Refrigeration and Air Conditioning, 22nd Edition.
Does the HVAC exam cover gas piping?
Gas piping is on Virginia's separate gasfitter exams, which are not part of this exam.
Free questions with answers
Show all 10 free questions and answers
A 400-square-foot office is to be ventilated by natural means. What is the minimum openable area to the outdoors that the Virginia Mechanical Code requires?
Answer: 16 square feet
Section 402.2 sets the minimum openable area to the outdoors at 4 percent of the floor area being ventilated. 0.04 x 400 = 16 square feet. 8 percent (32 sq ft) is the figure used for openings to adjoining rooms in 402.3, and 5 percent is not used here.
Reference: 2021 Virginia Mechanical Code (IMC 2021 as amended), Section 402.2
A floor furnace is to be installed in a new house. Which installation is permitted under IMC Section 910.2?
Answer: In a wood-framed floor over a crawl space, with the thermostat in the same room
Section 910.2 prohibits floor furnaces in concrete floor construction built on grade, in the floor of an aisle or passageway of an assembly room or in an egress element from it, and requires that drapery not be nearer than 12 inches to the register. The thermostat must be in the same room or in an adjacent room permanently open to it.
Reference: 2021 Virginia Mechanical Code (IMC 2021 as amended), Section 910.2
A basement mechanical room holds an 80,000 Btu/h furnace and a 40,000 Btu/h water heater. Using the standard method for indoor combustion air, what minimum room volume is required?
Answer: 6,000 cubic feet
Section 304.5.1 requires 50 cubic feet per 1,000 Btu/h of the total appliance input. Total input = 80,000 + 40,000 = 120,000 Btu/h, so 120 x 50 = 6,000 cubic feet. 2,400 uses 20 cubic feet per 1,000 Btu/h, and 12,000 doubles the factor.
Reference: 2021 Virginia Fuel Gas Code (IFGC 2021 as amended), Section 304.5.1
A return air system has a design capacity of 2,500 cfm, and the building is not protected throughout by area smoke detectors. Where is the duct smoke detector placed under Section 606.2.1?
Answer: In the return duct or plenum upstream of filters and outdoor air connections
Section 606.2.1 requires smoke detectors in return air systems with a design capacity greater than 2,000 cfm, installed in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections or decontamination equipment. On activation the system shuts down in accordance with Section 606.4.
Reference: 2021 Virginia Mechanical Code (IMC 2021 as amended), Section 606.2.1
An oil-fired furnace is vented with a Type L vent through a roof. How far above the highest point of the roof penetration must the vent terminate, under Section 802.5?
Answer: At least 2 feet, and at least 2 feet higher than any building portion within 10 feet
Section 802.5 requires Type L vents to terminate not less than 2 feet above the highest point of the roof penetration and not less than 2 feet higher than any portion of a building within 10 feet. Section 802.4 also requires a listed and labeled cap on a Type L vent.
Reference: 2021 Virginia Mechanical Code (IMC 2021 as amended), Section 802.5
What minimum unobstructed width must passageways around all sides of a boiler have under Section 1004.3, unless otherwise approved?
Answer: 18 inches
Section 1004.3 requires clearances that permit inspection, servicing, repair, replacement and visibility of gauges, and passageways around all sides of boilers must be unobstructed at least 18 inches wide unless otherwise approved.
Reference: 2021 Virginia Mechanical Code (IMC 2021 as amended), Section 1004.3
Under Section 1006.8, what is the maximum control voltage allowed for a boiler's electrical control system?
Answer: 150 volts nominal, line to line
Section 1006.8 limits boiler control voltage to 150 volts nominal line to line, requires control and limit devices to interrupt the ungrounded side of the circuit, and requires a manual disconnect that can be locked in the off position and is readily accessible.
Reference: 2021 Virginia Mechanical Code (IMC 2021 as amended), Section 1006.8
The maximum operating temperature of a hydronic system is 180 degrees F. What is the minimum flash point of the heat transfer fluid under Section 1207.1?
Answer: 230 degrees F
Section 1207.1 requires the flash point of the transfer fluid to be not less than 50 degrees F above the maximum system operating temperature. 180 + 50 = 230 degrees F.
Reference: 2021 Virginia Mechanical Code (IMC 2021 as amended), Section 1207.1
What minimum thickness of steel or stainless steel does Section 506.3.1.1 require for a grease duct serving a Type I hood (not factory-built)?
Answer: No. 16 gage (0.0575 inch) steel or No. 18 gage (0.0450 inch) stainless steel
Section 506.3.1.1 requires grease ducts to be steel of at least 0.0575 inch (No. 16 gage) or stainless steel of at least 0.0450 inch (No. 18 gage). The 18 gage steel / 20 gage stainless thickness is for the Type I hood itself (Section 507.2.3).
Reference: 2021 Virginia Mechanical Code (IMC 2021 as amended), Section 506.3.1.1
An installer needs a discharge point for an apartment air conditioner's condensate drain. Which discharge point does Section 307.2.1.1 allow?
Answer: A floor sink in the same dwelling unit
Section 307.2.1.1 says condensate drains shall not directly connect to any plumbing drain, waste or vent pipe, and may discharge into a floor sink, floor drain, trench drain, mop sink, hub drain, standpipe, utility sink or laundry sink. Except where discharging to grade outdoors, the discharge point must be in the same occupancy, tenant space or dwelling unit as the source, so a drain in another apartment is not allowed.
Reference: 2021 Virginia Mechanical Code (IMC 2021 as amended), Section 307.2.1.1
Sources
- PSI: Virginia Individual License and Certification Candidate Information Bulletin (1/14/2025) (opens in a new tab)
- Virginia DPOR: Tradesmen licensing (opens in a new tab)
- Virginia Administrative Code 18VAC50-30 (tradesman regulations) (opens in a new tab)
Questions last verified November 14, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.