Tennessee licensing exam

Tennessee Limited Licensed Electrician (LLE) Exam: Practice Test & Licensing Guide

The Prov exam for Tennessee's limited licensed electrician (LLE) license: 40 open-book questions on the 2017 NEC for electrical work under $25,000.

Questions
40
Time limit
2 hours
Passing score
73%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10General Knowledge

Informational Notes in the 2017 NEC are best described as

Requirements at a glance

AgencyTennessee Board for Licensing Contractors; exams by Prov
LicenseLimited licensed electrician (LLE, work under $25,000)
Exams40 questions, 2 hours, 73%
Books allowed2017 NEC, Ugly's Electrical References 2020 and 29 CFR 1926
Fees$53 per Prov exam attempt, plus the license fee

Electricians doing work under $25,000 where the State Fire Marshal's office handles permits and inspections, who need an LLE license.

How to get licensed, step by step

  1. Apply to the Board

    Send the Board your application. CMC and CMC-A applicants need pre-approval first (3 years of experience; $50 request). Trade-exam waivers exist for reciprocity states and NASCLA exams.

    Board: how to get a contractor license (opens in a new tab)Tennessee Board for Licensing Contractors (opens in a new tab)

  2. Schedule the LLE exam with Prov

    Register with Prov and test at a testing center or at home with Examroom. You can retake with no waiting period at $53 per attempt.

    Schedule with Prov (Tennessee contractors) (opens in a new tab)Prov: register for your exam (opens in a new tab)

  3. Pass at 73%

    Every Tennessee contractor exam is open book and needs 73% to pass.

    Schedule with Prov (Tennessee contractors) (opens in a new tab)

  4. Get licensed

    Send your results to the Board with the license fee.

    Board: how to get a contractor license (opens in a new tab)

How to prepare

  • Bring the editions on Prov's list: the 2017 NEC for electrical, the 2021 IPC, IMC and IFGC for plumbing and HVAC, the 2018 IRC for residential building and the 2021 IBC for commercial, industrial and mechanical. PSI-era books are accepted until 1/1/2027, then only Prov-recommended ones.
  • Tab your books before exam day with permanent tabs only. You can highlight, but moveable tabs are not allowed, and only a simple 4-function calculator is permitted.
  • Tennessee has no state journeyman or master license; cities and counties run their own cards and tests. These exams are for contractor classifications and the limited licenses (LLE and LLP).
  • Services, feeders and branch circuits (7) is the biggest section, followed by grounding and bonding (5), raceways and boxes (5) and hazardous locations and special occupancies (5).
  • The NEC edition on the list is 2017. Tennessee makes available fault current (110.24) and some AFCI locations optional.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2017 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (NEC), 2017
  • Ugly's Electrical References, 2020
  • 29 CFR 1926 (OSHA Construction)

What's on the exam

Official content outline from Prov (number of questions per topic):

TopicQuestions
General Knowledge4
Installation Requirements3
Services, Feeders, and Branch Circuits7
Overcurrent Protection2
Grounding and Bonding5
Conductors and Cables4
Raceways and Boxes5
Hazardous Locations and Special Occupancies5
Low Voltage Alarms, Signaling Systems, and Communications2
Lighting, Signs, and General Use Equipment3

Exam day details

  • Administered by Prov for the Tennessee Board for Licensing Contractors.
  • Fee: $53 per exam to Prov, for a first attempt or a retake. Board application and license fees are separate.
  • 40 questions in 2 hours; 73% to pass.
  • LLE fees: $50 initial, $50 renewal (biennial). Tennessee has no LLE reciprocity, and only about 65 counties accept the license.
  • The Prov bulletin lists the 2017 NEC. Tennessee adopts it with amendments: available fault current (110.24) is optional, and AFCIs are optional in bathrooms, laundry areas, garages, unfinished basements and refrigeration circuits. We could not check the 2017 NEC text itself against an official copy, so confirm the edition on the current Prov bulletin for your test date.
  • Open book: bring your own copies of the listed references. You may highlight and add permanent tabs, but moveable tabs are not allowed. Only a simple 4-function calculator is permitted.
  • Test at a Prov testing center or at home with Examroom (remote proctoring). All Tennessee contractor exams need 73% to pass.
  • You may retake as many times as needed with no waiting period, at $53 per attempt. If you fail within 10 points of 73% you can request a review of your exam.
  • Prov replaced PSI as the Tennessee vendor on 7/1/2026. Reference lists accept PSI-era books until 1/1/2027, then only Prov-recommended ones.
  • Every new contractor takes the Business and Law exam plus a trade exam for the classification. Reciprocity or NASCLA exams can waive the trade exam.

Note: The Prov bulletin lists the 2017 NEC. Tennessee adopts it with amendments: available fault current (110.24) is optional, and AFCIs are optional in bathrooms, laundry areas, garages, unfinished basements and refrigeration circuits. We could not check the 2017 NEC text itself against an official copy, so confirm the edition on the current Prov bulletin for your test date.

Frequently asked questions

What's on the Tennessee LLE exam?

40 questions: services, feeders and branch circuits 7, grounding and bonding 5, raceways and boxes 5, hazardous locations and special occupancies 5, and smaller sections.

Who needs an LLE?

Electricians doing work under $25,000 where the State Fire Marshal's office handles permits and inspections.

Which NEC edition is used?

The Prov bulletin lists the 2017 NEC, with Ugly's Electrical References (2020).

Free questions with answers

Show all 10 free questions and answers
  1. Informational Notes in the 2017 NEC are best described as

    Answer: explanatory material that is not enforceable as a requirement

    Section 90.5(C) says Informational Notes are for information only and are not enforceable as requirements of the Code. Only text using shall or shall not is mandatory.

    Reference: 2017 National Electrical Code (NFPA 70), 90.5(C)

  2. A 120/240-volt, single-phase panelboard is installed with a grounded concrete wall directly opposite the working space. Using Table 110.26(A)(1), what is the minimum depth of working space in front of the panel?

    Answer: 3 ft

    For 0 to 150 volts to ground, Table 110.26(A)(1) requires 3 ft for Conditions 1, 2 and 3. A 120/240 V single-phase panel is only 120 V to ground, so the opposite-wall condition does not increase the depth. The 3.5 ft and 4 ft figures apply in the 151 to 600 V row.

    Reference: 2017 National Electrical Code (NFPA 70), Table 110.26(A)(1)

  3. A branch circuit will carry 16 amperes of continuous load and 8 amperes of noncontinuous load. All terminals are rated 75 degrees C. What is the smallest THWN copper conductor that meets Section 210.19(A)(1) using Table 310.15(B)(16)?

    Answer: 10 AWG, which is rated 35 amperes at 75 degrees C

    Minimum ampacity = 16 A x 1.25 + 8 A = 20 + 8 = 28 A. In the 75 degree C column 12 AWG is rated only 25 A, so 10 AWG (35 A) is the smallest that qualifies, and it also stays within the 30 A overcurrent limit of 240.4(D) for 10 AWG copper. Adding the loads without the 125 percent factor (24 A) wrongly points to 12 AWG.

    Reference: 2017 National Electrical Code (NFPA 70), 210.19(A)(1); Table 310.15(B)(16)

  4. A 6 AWG copper conductor has an ampacity of 55 amperes at the 60 degrees C column. Where Section 240.4(B) applies, what is the highest standard overcurrent device rating that may protect it?

    Answer: 60 amperes

    Section 240.4(B) permits the next higher standard rating when the ampacity does not match a standard size, up to 800 A, provided it is not a multioutlet branch circuit for portable cord-and-plug loads. The next standard size above 55 A is 60 A; 55 A is not a standard rating.

    Reference: 2017 National Electrical Code (NFPA 70), 240.4(B); 240.6(A)

  5. When two ground rods are installed together to meet the supplemental electrode rule, how far apart must they be?

    Answer: At least 6 ft

    Section 250.53(A)(3) requires multiple rod, pipe or plate electrodes installed to meet the supplemental electrode requirement to be not less than 6 ft apart. The Informational Note adds that spacing them twice the rod length improves paralleling efficiency.

    Reference: 2017 National Electrical Code (NFPA 70), 250.53(A)(3)

  6. Using the 75 degrees C column of Table 310.15(B)(16), what is the ampacity of a 1 AWG copper conductor connected to a 75 degree C rated terminal?

    Answer: 130 amperes

    The 75 degree C column of Table 310.15(B)(16) lists 130 A for 1 AWG copper. 110 A is the 60 degree C value and 150 A is the 90 degree C value; the 90 degree C value can be used only as a starting point for derating, since Section 110.14(C) limits the terminal temperature.

    Reference: 2017 National Electrical Code (NFPA 70), Table 310.15(B)(16); 110.14(C)

  7. A straight pull is made in a pull box through a 2-inch conduit. What is the minimum length of the box under Section 314.28(A)(1)?

    Answer: 16 inches

    For a straight pull, the length of the box must be at least eight times the trade size of the largest raceway: 8 x 2 in. = 16 in. 12 in. uses six times the diameter, which is the angle-pull rule.

    Reference: 2017 National Electrical Code (NFPA 70), 314.28(A)(1)

  8. In a Class I, Division 1 location, a conduit enters an enclosure that contains arcing devices such as switches and circuit breakers. Where must the conduit seal be located under Section 501.15(A)(1)?

    Answer: Within 18 inches of the enclosure

    Section 501.15(A)(1) requires a seal in each conduit entering an enclosure that houses arcing or sparking equipment, located as close as practicable and in no case more than 18 in. from the enclosure. The seal keeps explosive gases and flames from traveling through the conduit.

    Reference: 2017 National Electrical Code (NFPA 70), 501.15(A)(1)

  9. For a one-family dwelling, the grounding conductor for a communications protector must be copper no smaller than which size and no longer than which length, according to Section 800.100(A)?

    Answer: 14 AWG, as short as practicable and not over 20 ft

    Section 800.100(A) requires communications grounding conductors to be copper or other corrosion-resistant conductive material, not smaller than 14 AWG, and as short as practicable. In one- and two-family dwellings it should not exceed 20 ft.

    Reference: 2017 National Electrical Code (NFPA 70), 800.100(A)

  10. A 50-gallon, 4,500-watt, 240-volt storage water heater is supplied by copper NM-B cable (60 degree C column). Applying Section 422.13, what is the smallest conductor size?

    Answer: 10 AWG

    Current = 4,500 W / 240 V = 18.75 A. Section 422.13 treats a storage water heater of 120 gal or less as a continuous load, so the branch circuit is sized at 125 percent under 422.10(A): 18.75 x 1.25 = 23.4 A. 12 AWG in the 60 degree C column is only 20 A, so 10 AWG (30 A) is the smallest that works.

    Reference: 2017 National Electrical Code (NFPA 70), 422.13; 422.10(A); Table 310.15(B)(16)

Sources

Questions last verified November 15, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.