South Carolina Electrician (Commercial Electrical Contractor) Exam: Practice Test & Licensing Guide

PSI's open-book technical exam for South Carolina's commercial electrical contractor classification: 80 questions on the NEC covering services, grounding, conductors, raceways, motors and safety.

Questions
80
Time limit
5 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10General Electrical Knowledge

A 480Y/277-volt, three-phase panelboard has exposed live parts behind its dead front when opened. A concrete wall (grounded) is directly opposite the front of the panel, with no other live parts across the space. Using the table for working spaces at 600 volts or less, what is the minimum clear depth of working space in front of the panel?

Requirements at a glance

AgencySouth Carolina Department of Labor, Licensing and Regulation (LLR), Contractor's Licensing Board; exams by PSI
ExperienceThe primary qualifying party needs 2 of the last 5 years of full-time experience in the classification, in a management role (S.C. Code 40-11-230)
ExamsElectrician: 80 questions, 5 hours, 70%, plus Business Management and Law (Commercial); 70% on each
Books allowedNEC 2023 or 2020 (or NEC Handbook) with SC modifications, NFPA 72, American Electricians' Handbook and 29 CFR 1926
FeesPSI exam fees ($64 to $78 per exam), plus the Board's application and license fees and a financial statement or bond

Applicants for a South Carolina Contractor's Licensing Board mechanical license in the Electrical classification.

How to get licensed, step by step

  1. Check the work needs a license

    South Carolina requires a Contractor's Licensing Board license for commercial work above $10,000 in job cost (S.C. Code 40-11-30). Commercial licenses also cover residential work.

    SC Contractor's Licensing Board (LLR) (opens in a new tab)S.C. Code Title 40 Chapter 11 (contractors) (opens in a new tab)

  2. Apply to the Board

    Apply to the Contractor's Licensing Board for an eligibility letter before you register with PSI.

    SC Contractor's Licensing Board (LLR) (opens in a new tab)

  3. Schedule Business and Law and the electrician exam with PSI

    Register for each exam separately. You may take each trade exam twice in 12 months, then once every six months. Commercial Business and Law has no such limit.

    Schedule with PSI (commercial contractors) (opens in a new tab)

  4. Apply for the license

    After you pass, the business entity applies with its primary qualifying party, a financial statement or bond, and the license fee. The group (1 to 5) sets the dollar limit of work you may bid.

    SC Contractor's Licensing Board (LLR) (opens in a new tab)S.C. Code Title 40 Chapter 11 (contractors) (opens in a new tab)

How to prepare

  • Code editions are changing. From November 1, 2026 PSI accepts the 2021 or the 2024 South Carolina codes (ICC codes with state modifications) and the 2023 or the 2020 NEC. After July 1, 2027 only the 2024 codes and the 2023 NEC. Bring one edition you know well and expect questions that read the same in both.
  • Tab your books before exam day: highlighting, underlining and permanent tabs are allowed, but sticky notes and writing during the exam are not.
  • Services, feeders and branch circuits, grounding and bonding, conductors and cables, raceways and boxes and general knowledge are 9 questions each: tab Articles 210, 215, 220, 230, 240, 250, 300 to 314 and 310.
  • South Carolina modifies NEC 210.8(A), 210.8(F) and 210.12(B); read the state changes before the exam.
  • Safety (8), electrical power (7) and motors (7) mix code and calculations: Articles 430 and 450 and Chapter 9.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (NEC) or NEC Handbook, 2023 or 2020 edition, with South Carolina modifications
  • NFPA 72, 2019 edition
  • American Electricians' Handbook, 17th Edition
  • 29 CFR Part 1926 and a Key Word Index (all on PSI's list)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
General Electrical Knowledge9
Service, Feeders, and Branch Circuits9
Grounding and Bonding9
Conductors and Cables9
Raceways and Boxes9
Special Occupancies and Equipment2
Electrical Power7
Motors7
Low Voltage2
Lighting5
Illuminated Signs2
Fire Detection and Alarm Systems2
Safety Information8

Exam day details

  • Administered by PSI Services for the South Carolina Department of Labor, Licensing and Regulation (Contractor's Licensing Board).
  • Fee: $78 to PSI. Board application and license fees are separate.
  • 80 scored questions plus 1 to 10 unscored experimental items (they count against your time) in 300 minutes; 56 correct (70%) to pass.
  • South Carolina modifies NEC 210.8(A), 210.8(F) and 210.12(B) (state Building Codes Council). Check your NEC copy against the state changes.
  • Code editions: from November 1, 2026 PSI accepts the 2021 or 2024 South Carolina codes (NEC 2023 or 2020); after July 1, 2027 only the 2024 codes and the 2023 NEC. Our questions are written to be correct under both.
  • Open book: bring the references on PSI's list. You may highlight, underline and add permanent tabs (tabs that would tear the page if removed); sticky notes and removable tabs are not allowed.
  • Apply to the Contractor's Licensing Board first. After approval you get an eligibility letter and register with PSI (855-340-3701) for each exam; the registration confirmation is valid 1 year or until a classification has been failed twice.
  • You may take each trade exam twice in 12 months, then once every six months.
  • Every Contractor's Licensing Board license needs the Business Management and Law exam and the technical exam for the classification, 70% on each (S.C. Code 40-11-230).

Frequently asked questions

What's on the South Carolina electrician exam?

80 scored questions, led by General Electrical Knowledge 9, service, feeders, and branch circuits 9, grounding and bonding 9, conductors and cables 9, raceways and boxes 9, safety information 8, electrical power 7, motors 7 and 5 smaller topics.

Which NEC edition is on the South Carolina electrician exam?

From November 1, 2026 PSI accepts the 2023 or the 2020 NEC with South Carolina modifications. After July 1, 2027 only the 2023 edition.

How are the 80 questions split?

Nine each on general knowledge, service/feeders/branch circuits, grounding and bonding, conductors and cables, and raceways and boxes; 8 on safety; 7 each on electrical power and motors; 5 on lighting; and 2 each on special occupancies, low voltage, illuminated signs and fire alarm.

Free questions with answers

Show all 10 free questions and answers
  1. A 480Y/277-volt, three-phase panelboard has exposed live parts behind its dead front when opened. A concrete wall (grounded) is directly opposite the front of the panel, with no other live parts across the space. Using the table for working spaces at 600 volts or less, what is the minimum clear depth of working space in front of the panel?

    Answer: 3 ft 6 in. (Condition 2)

    Voltage to ground is 277 V, so use the 151-600 V row of Table 110.26(A)(1). Exposed live parts on one side and a grounded wall (concrete counts as grounded) on the other is Condition 2, which is 3 ft 6 in. 3 ft would apply only if nothing grounded were opposite (Condition 1); 4 ft needs live parts on both sides.

    Reference: NEC 2020/2023 (rule identical in both), Table 110.26(A)(1)

  2. What is the minimum rating of the service disconnecting means for a new one-family dwelling?

    Answer: 100 amperes, 3-wire

    230.79(C) sets the floor for a one-family dwelling at 100 amperes, 3-wire, regardless of the calculated load. 60 amperes is the floor for 'all others' under 230.79(D), and 30 or 15 amperes apply to two-circuit and one-circuit installations.

    Reference: NEC 2020/2023 (rule identical in both), 230.79(C)

  3. A service uses 250 kcmil copper service-entrance conductors, and the grounding electrode conductor runs to a metal underground water pipe and a building steel electrode. What is the minimum size copper grounding electrode conductor?

    Answer: 2 AWG

    Table 250.66 puts 250 kcmil copper in the 'over 3/0 through 350 kcmil' row, which requires a 2 AWG copper grounding electrode conductor. The 6 AWG and 4 AWG limits in 250.66(A) and (B) apply only when the conductor runs solely to rod, pipe, plate or concrete-encased electrodes.

    Reference: NEC 2020/2023 (rule identical in both), Table 250.66

  4. Eight current-carrying 10 AWG copper THHN conductors are installed together in one conduit in a 30 degree C ambient. What is the adjusted ampacity of each conductor, starting from the 90 degree C column?

    Answer: 28 amperes

    Table 310.16 gives 10 AWG THHN 40 A in the 90 degree C column. For 7 to 9 current-carrying conductors the adjustment factor in Table 310.15(C)(1) (same number in the 2020 and 2023 NEC) is 70%, so 40 x 0.70 = 28 A. The 80% factor applies only to 4 to 6 conductors and 50% to 10 to 20 conductors.

    Reference: NEC 2020/2023 (same table number in both editions), Table 310.16; Table 310.15(C)(1)

  5. Rigid PVC conduit carrying a 240-volt, 40-ampere branch circuit for a one-family dwelling is buried under the dwelling's driveway, which is used only for dwelling-related purposes. What is the minimum cover?

    Answer: 18 in.

    Table 300.5 has a specific row for one- and two-family dwelling driveways and outdoor parking areas used only for dwelling-related purposes; nonmetallic raceways (Column 3) need 18 in. there. The 12-in. value in Column 4 applies only to residential branch circuits of 120 volts or less with GFCI protection and 20 A or less overcurrent protection, which this 240-volt circuit is not.

    Reference: NEC 2020/2023 (rule identical in both); Table 300.5 is Table 300.5(A) in 2023, Table 300.5, Column 3

  6. A single-phase 120-volt, 16-ampere load is 120 feet from the panel (one-way) on 12 AWG copper (K = 12.9 ohm-cmil/ft, 6,530 circular mils). What is the approximate voltage drop on the circuit?

    Answer: 7.6 volts

    For a single-phase circuit, VD = 2 x K x I x L / CM = 2 x 12.9 x 16 x 120 / 6,530 = 7.59 V, or 6.3% of 120 V. That is above the 3% branch-circuit figure in the voltage-drop informational note under 210.19, so a larger conductor is advisable. Leaving out the factor of 2 for the return conductor halves the drop to 3.8 V.

    Reference: NEC 2020/2023 (voltage-drop informational note under 210.19; formula uses Chapter 9 Table 8 data), 210.19 Informational Note (2023); Chapter 9, Table 8

  7. In the event of failure of the normal supply, within what maximum time must an emergency system have the required power available?

    Answer: 10 seconds

    700.12 requires emergency lighting, power or both to be available within the time required for the application but not to exceed 10 seconds. Legally required standby systems (Article 701) have a separate limit of 60 seconds.

    Reference: NEC 2020/2023 (rule identical in both), 700.12

  8. A 7.5-hp, 230-volt, three-phase squirrel-cage motor has a Table 430.250 full-load current of 22 amperes and starts normally (no increase for starting current is needed). Applying the table percentage and the next-higher-standard-size allowance, what is the maximum rating of an inverse-time circuit breaker for the branch-circuit short-circuit and ground-fault protection?

    Answer: 60 amperes (22 A x 250 percent = 55 A, next standard size)

    The motor branch-circuit protection table (Table 430.52 in 2020, Table 430.52(C)(1) in 2023) allows an inverse-time breaker of up to 250% of the full-load current: 22 x 2.5 = 55 A. 55 A is not a standard rating in 240.6(A), so the next higher standard rating, 60 A, is permitted (430.52(C)(1) Exception No. 1 in 2020, 430.52(C)(1)(a) in 2023). Rounding down to 50 A is allowed but is not the maximum, and 300% is the nontime-delay fuse percentage.

    Reference: NEC 2020/2023 (Table 430.52 and 430.52(C)(1) Exception No. 1 in 2020; Table 430.52(C)(1) and 430.52(C)(1)(a) in 2023), Table 430.52(C)(1); 430.52(C)(1)(a); 240.6(A)

  9. A contractor plans to blow insulation around a recessed luminaire that is not marked Type IC. What distance must thermal insulation be kept from the luminaire's enclosure, wiring compartment and ballast or driver?

    Answer: At least 3 in., and none above it

    410.116(B) prohibits thermal insulation above a recessed luminaire or within 75 mm (3 in.) of its enclosure, wiring compartment, ballast, transformer, LED driver or power supply, unless the luminaire is identified as Type IC for insulation contact. The 1/2 in. figure is the spacing from combustible material in 410.116(A)(1).

    Reference: NEC 2020/2023 (rule identical in both), 410.116(B)

  10. Which of these is prohibited by the OSHA construction rule for cords and cables?

    Answer: Using worn or frayed electric cords or cables

    29 CFR 1926.416(e)(1) states that worn or frayed electric cords or cables shall not be used, and (e)(2) bars fastening extension cords with staples, hanging them from nails, or suspending them by wire. The other choices describe acceptable practices that reduce cord hazards.

    Reference: 29 CFR Part 1926 (eCFR), 1926.416(e)

Sources

Questions last verified November 16, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.