Requirements at a glance
| Agency | City of Reading (and other cities that name ICC exams); exam by ICC, delivered by Pearson VUE |
|---|---|
| Exam | ICC G17Y Journeyman Electrician: 80 questions, 4 hours, open book |
| Experience (Reading) | Work for a registered master electrician; 4 years of approved apprenticeship (144 hours of instruction a year) or 8 years under a registered master |
| Books allowed | 2017 NEC; Ugly's Electrical Reference (any edition) |
| Fees | About $120 to the testing vendor (TODO(verify): current fee); Reading journeyman license $50 a year |
Electricians applying for a City of Reading journeyman electrician license. Pennsylvania has no statewide electrician license, so other cities may name the same or a different ICC exam; check with yours.
Official links
How to get licensed, step by step
Confirm your city's rules
Pennsylvania has no statewide electrician license. Reading's application names ICC exam G17Y for journeymen; other cities may differ.
Schedule with ICC and Pearson VUE
Register through ICC and take the exam at a Pearson VUE center. If you fail, wait 10 days to retake.
Schedule with Pearson VUE (ICC exams) (opens in a new tab)ICC: National Contractor/Trades Examination Bulletin (opens in a new tab)
Apply to the city
Attach your passing results to the city's electrical trade license application.
How to prepare
- Open book on the 2017 NEC. Tab Article 220, Chapter 9 tables, Article 310 ampacities and Article 430.
- Wiring methods and materials (26%) and branch circuits and conductors (19%) are almost half of the exam.
- Pennsylvania has no statewide electrician or plumber license; each city sets its own. Confirm the exam and code edition with the city that will license you.
- Start with the free questions above to find your weak topics, then drill those first.
- Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
- Read every explanation, including for questions you got right, and look the section up in your own book.
Books for this exam
This is an open-book exam: you can bring the references below, and most questions come from the 2017 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.
2017 National Electrical Code (NEC), NFPA 70Essential
Allowed in the exam room. Most of the exam comes from it.
Ugly's Electrical References (any edition)
Allowed in the exam room. Formulas, conductor and conduit tables, motor data.
Official reference list (as published by the testing agency)
- 2017 National Electrical Code, NFPA 70 (open book)
- Ugly's Electrical Reference, any edition (open book)
What's on the exam
Official content outline from International Code Council (ICC), delivered by Pearson VUE; named by the City of Reading (number of questions per topic):
| Topic | Questions | |
|---|---|---|
| General Knowledge | 6 | |
| Services and Service Equipment | 11 | |
| Feeders | 4 | |
| Branch Circuits and Conductors | 19 | |
| Wiring Methods and Materials | 26 | |
| Equipment and Devices | 13 | |
| Control Devices | 4 | |
| Motors and Generators | 6 | |
| Special Occupancies, Equipment, and Conditions | 11 |
The outline totals 100; the other items on the 80-question exam are unscored or unassigned.
Exam day details
- Administered by International Code Council (ICC), delivered by Pearson VUE; named by the City of Reading.
- Fee: About $120 to ICC's testing vendor (national bulletin pricing). TODO(verify): current Pearson VUE fee. Reading's license fee is separate ($50 per year for a journeyman license on its application).
- 80 questions in 4 hours, open book, on the 2017 NEC. The outline is ICC's national Journeyman Electrician outline (G17).
- Reading's application names ICC exam G17Y for journeyman and G16Y for master electrician. The 2017 NEC is the edition on that application; confirm the current edition with the city.
- Reading requires journeyman applicants to work for a registered master electrician and complete 4 years of approved apprenticeship (or 8 years under a registered master).
- Pennsylvania has no statewide electrician or plumber license. Cities and counties license these trades, so confirm with your city which ICC exam and code edition it requires.
- If you fail, wait 10 days to retake an ICC exam.
Frequently asked questions
Which exam does Reading require for journeymen?
ICC exam G17Y, the journeyman electrician exam, scheduled through ICC and Pearson VUE.
Which NEC edition?
The 2017 NEC, as named on Reading's application and ICC's G17 outline. Ugly's Electrical Reference (any edition) is also allowed.
What's on the exam?
Wiring methods and materials 26%, branch circuits and conductors 19%, equipment and devices 13%, services and service equipment 11%, special occupancies 11%, general knowledge 6%, motors and generators 6%, feeders 4% and control devices 4%.
Free questions with answers
Show all 10 free questions and answers
A 120/240-volt, single-phase service uses 3/0 AWG copper ungrounded conductors in a single raceway, and the maximum unbalanced load is 40 A. What is the smallest copper grounded (neutral) service conductor permitted under 250.24(C)(1)?
Answer: 4 AWG
In the 2017 NEC, 250.24(C)(1) makes the grounded service conductor not smaller than Table 250.102(C)(1), and 3/0 AWG copper ungrounded conductors (over 2/0 through 3/0) call for 4 AWG copper. The 40 A unbalanced load alone would allow 8 AWG, but the table minimum is larger and controls.
Reference: NFPA 70, National Electrical Code, 2017, 250.24(C)(1); Table 250.102(C)(1)
A feeder has 120 A of continuous load and 30 A of noncontinuous load and uses an overcurrent device not listed for operation at 100 percent. What is the minimum standard overcurrent device rating under 215.3 and 240.6(A)?
Answer: 200 A
215.3 requires 125 percent of the continuous load plus 100 percent of the noncontinuous load: 120 x 1.25 + 30 = 150 + 30 = 180 A. The next standard size above 180 A in 240.6(A) is 200 A (175 A is too small). The 150 A answer ignores the 125 percent factor on the continuous load.
Reference: NFPA 70, National Electrical Code, 2017, 215.3; 240.6(A)
Under the Article 100 definitions, what makes equipment 'readily accessible'?
Answer: It can be reached quickly for use or inspection without climbing over or removing obstacles
Article 100 defines readily accessible as capable of being reached quickly for operation, renewal or inspection without requiring those needing access to climb over or remove obstacles or to resort to portable ladders. Equipment behind a lock, or high up, may be accessible but not readily accessible.
Reference: NFPA 70, National Electrical Code, 2017, Article 100, Definitions: Readily Accessible (Accessible, Readily)
Along an unbroken wall of a dwelling living room, what is the maximum distance between receptacle outlets under 210.52(A)(1)?
Answer: 12 ft
210.52(A)(1) is written so that no point measured horizontally along the floor line of any wall space is more than 6 ft from a receptacle outlet, which works out to receptacles no more than 12 ft apart on a continuous wall. Wall spaces 2 ft or wider are counted.
Reference: NFPA 70, National Electrical Code, 2017, 210.52(A)(1)
EMT is installed in a straight horizontal run with the structure allowing standard fastening. What are the securing requirements of 358.30(A)?
Answer: Fastened within 3 ft of each box and at intervals not over 10 ft
358.30(A) requires EMT to be securely fastened at intervals of not more than 10 ft and within 3 ft of each outlet box, junction box, device box, cabinet, conduit body or other termination. The 12 in. and 4-1/2 ft figures are the flexible metal conduit rule in 348.30.
Reference: NFPA 70, National Electrical Code, 2017, 358.30(A)
A 2-inch PVC conduit is installed exposed on a wall. What is the maximum spacing between supports under Table 352.30?
Answer: 5 ft
Table 352.30 gives 3 ft for trade sizes 1/2 through 1, 5 ft for 1-1/4 through 2, 6 ft for 2-1/2 and 3, 7 ft for 3-1/2 through 5, and 8 ft for 6 inch. The conduit must also be fastened within 3 ft of each box or termination.
Reference: NFPA 70, National Electrical Code, 2017, Table 352.30; 352.30(B)
A 4-wire delta system has one transformer winding center-tapped and grounded. How must the conductor having the higher phase voltage to ground be identified under 110.15?
Answer: With an orange outer finish or other effective means
110.15 requires the conductor or busbar having the higher phase voltage to ground (the 208-volt high leg) on a 4-wire delta system to be durably marked with an orange outer finish or other effective means, at each point where a connection is made if the grounded conductor is present. White or gray identifies the grounded conductor.
Reference: NFPA 70, National Electrical Code, 2017, 110.15
How must a single-throw knife switch be mounted under 404.6(A)?
Answer: So that gravity will not tend to close it
404.6(A) requires single-throw knife switches to be placed so gravity does not tend to close them, and those approved for the inverted position need an integral means to keep the blades open. This prevents an unintended closing of the switch.
Reference: NFPA 70, National Electrical Code, 2017, 404.6(A)
A single 5 hp, 230-volt, 3-phase continuous-duty motor has a Table 430.250 full-load current of 15.2 A. What is the minimum ampacity of the branch-circuit conductors under 430.22?
Answer: 19 A
Branch-circuit conductors for a single continuous-duty motor must be rated at 125 percent of the full-load current from the table: 15.2 x 1.25 = 19 A. The nameplate current is not used for sizing the conductor, and 22.8 A applies 150 percent.
Reference: NFPA 70, National Electrical Code, 2017, 430.22; Table 430.250
A new outdoor pool has a luminaire installed on a pole 4 ft horizontally from the inside wall of the pool. What is the minimum mounting height above maximum water level under 680.22(B)(1)?
Answer: 12 ft
680.22(B)(1) requires luminaires, lighting outlets and paddle fans in outdoor pool areas, above the pool or within 5 ft horizontally of the inside wall, to be at least 12 ft above the maximum water level. The 7-1/2 ft figure is an indoor GFCI exception for certain luminaires.
Reference: NFPA 70, National Electrical Code, 2017, 680.22(B)(1)
Sources
- City of Reading: electrical trade license application (opens in a new tab)
- ICC National Contractor/Trades Examination Information Bulletin (opens in a new tab)
Questions last verified November 17, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.