Nevada C-2F Residential Wiring Contractor Exam: Practice Test & Licensing Guide

The PSI trade exam for Nevada's C-2F Residential Wiring license: 50 questions on dwelling wiring under the 2017 NEC, open book.

Questions
50
Time limit
2 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Service, Feeders, and Branch Circuits

A house has 2,400 sq ft of living area, two small-appliance circuits and one laundry circuit. Using 220.12, 220.52 and the Table 220.42 demand factors, what is the net general lighting and appliance load?

Requirements at a glance

AgencyNevada State Contractors Board (NSCB); exams by PSI
Experience4 years as a journeyman, foreman, supervisor or contractor in the classification within the last 15 years (up to 3 years can be education)
Exams50 questions, 2 hours, 70%, plus the Construction Management Survey (business and law)
Books allowed2017 NEC
Fees$95 per PSI exam ($140 for a trade exam plus the CMS), plus NSCB application and license fees and a bond

Qualifying individuals for a Nevada C-2F license: electrical work up to 600 volts on buildings no more than three stories above ground.

How to get licensed, step by step

  1. Pick your classification

    Find the NSCB classification that covers your work, and name the qualifying individual (an owner or a qualified employee) with 4 years of experience in it.

    NSCB: License classifications (opens in a new tab)

  2. Apply to the NSCB

    Submit the application with your experience verification, financial statement and fingerprints. The Board sends you an exam eligibility notice once it accepts your qualifications.

    Nevada State Contractors Board (opens in a new tab)

  3. Schedule the CMS and C-2F trade exam with PSI

    Book both exams with PSI. Bring the allowed references, tabbed. If you fail, wait 2 weeks; you get three attempts and must pass within 6 months of filing.

    Schedule with PSI (Nevada contractors) (opens in a new tab)PSI: Nevada "C" classification bulletin and outlines (opens in a new tab)

  4. Post your bond and get licensed

    After you pass, the Board sets your monetary limit and bond amount ($1,000 to $500,000). File the bond and pay the license fee to receive your license.

How to prepare

  • Bring the exact editions on PSI's outline. Nevada's trade exams use the 2017 NEC, the 2018 IBC/IRC and the 2018 UPC/UMC; a newer book gives some wrong answers.
  • Tab your books with permanent tabs before exam day. Sticky notes are removed at check-in, and you can't write in the books.
  • OSHA 1926 isn't allowed in the room, but every trade exam has a safety section from it. Learn the common numbers (fall protection at 6 ft, ladders 3 ft above the landing, trenches 5 ft).
  • Services, feeders and branch circuits (10) and general knowledge (9) are 19 of the 50 questions: dwelling receptacle spacing, GFCI and AFCI rules, and the Article 220 dwelling load calculation.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2017 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

  • NFPA 70: National Electrical Code, 2017 EditionEssential

    The edition PSI's Nevada outline lists (the 2017 NEC Handbook is also allowed). Newer editions renumber key tables and rules.

    NFPA store (opens in a new tab)

  • 29 CFR 1926 (OSHA Construction Standards), sections on your reference list

    Not allowed in the room, but every Nevada trade exam has safety questions written from it: fall protection, scaffolds, ladders, excavations.

    Read free (eCFR) (opens in a new tab)

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (or NEC Handbook), 2017 (allowed in the exam room)
  • 29 CFR Part 1926, OSHA Construction (not allowed in the room)
  • Ugly's Electrical References (not allowed in the room)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
General Electrical Knowledge9
Service, Feeders, and Branch Circuits10
Grounding and Bonding7
Conductors and Cables7
Overcurrent Protection4
Electrical Power2
Low Voltage2
Fire and Intrusion Detection and Alarm Systems2
Safety Information4
Raceways and Enclosures3

Exam day details

  • Administered by PSI Services for the Nevada State Contractors Board (NSCB).
  • Fee: $95 to PSI for one exam, $140 for a trade exam plus the CMS. NSCB application and license fees are separate.
  • 50 questions in 2 hours; 35 correct (70%) to pass.
  • The exam uses the 2017 NEC. Bring the 2017 code book.
  • Open book: bring your own copies of the allowed references. You may highlight and add permanent tabs beforehand, but not write in them; sticky notes are removed.
  • PSI may add up to 10 unscored trial questions, which count against your time.
  • If you fail, wait 2 weeks to retake. You get three attempts, and you must pass within 6 months of filing your application; a third failure voids the application.
  • Every Nevada contractor license needs both the Construction Management Survey (business and law) and the trade exam for the classification, plus 4 years of experience in the last 15.

Frequently asked questions

What's on the Nevada C-2F exam?

50 questions: services, feeders and branch circuits 10, general electrical knowledge 9, grounding and bonding 7, conductors and cables 7, overcurrent protection 4, safety 4, raceways and enclosures 3, and 2 each on electrical power, low voltage and alarm systems.

C-2 or C-2F?

C-2F is limited to 600 volts on buildings up to three stories, which covers most residential work. Commercial and industrial work needs the full C-2 license and its 80-question exam.

Which NEC edition do I need?

The 2017 NEC (or the 2017 NEC Handbook). Code questions are based only on that edition.

Free questions with answers

Show all 10 free questions and answers
  1. A house has 2,400 sq ft of living area, two small-appliance circuits and one laundry circuit. Using 220.12, 220.52 and the Table 220.42 demand factors, what is the net general lighting and appliance load?

    Answer: 6,045 VA

    General lighting: 2,400 × 3 VA (Table 220.12) = 7,200 VA. Add 2 × 1,500 VA small-appliance (220.52(A)) and 1,500 VA laundry (220.52(B)): 11,700 VA. Table 220.42: first 3,000 VA at 100% = 3,000; remaining 8,700 at 35% = 3,045. Total 6,045 VA. 11,700 is before demand factors, and 7,200 is lighting only.

    Reference: NFPA 70, National Electrical Code, 2017, 220.12, 220.52, Table 220.42

  2. A 120/240-V residential panelboard in a garage faces a concrete wall 30 inches away. Under 110.26(A)(1), is that working space deep enough?

    Answer: No; Table 110.26(A)(1) requires at least 3 ft for 0–150 V to ground under every condition

    Table 110.26(A)(1) requires a working-space depth of 3 ft for 0–150 V to ground under Conditions 1, 2 and 3; a concrete wall (grounded) is Condition 2, but for 0–150 V all conditions are 3 ft. 30 inches is the minimum width (110.26(A)(2)), not depth. Greater depths start at 151–600 V.

    Reference: NFPA 70, National Electrical Code, 2017, 110.26(A)(1), Table 110.26(A)(1)

  3. A dwelling service uses 3/0 AWG copper service-entrance conductors, and the GEC runs to a metal water pipe electrode. Using Table 250.66, what is the minimum copper GEC?

    Answer: 4 AWG

    Table 250.66 requires a 4 AWG copper GEC for 2/0 or 3/0 AWG copper service conductors (4/0 or 250 kcmil aluminum). 2 AWG applies over 3/0 through 350 kcmil copper. Because this GEC goes to a water pipe, the 250.66(A) reduction for rods doesn't apply.

    Reference: NFPA 70, National Electrical Code, 2017, Table 250.66

  4. Three 10 AWG copper THWN-2 conductors (90°C) run through a Las Vegas attic where the ambient is 48°C (118°F). Using Table 310.15(B)(16) and the 2017 Table 310.15(B)(2)(a) correction factor, what is the corrected ampacity before any termination limit?

    Answer: 32.8 A

    10 AWG copper at 90°C = 40 A (Table 310.15(B)(16)). For 46–50°C ambient, the 90°C correction factor in Table 310.15(B)(2)(a) is 0.82: 40 × 0.82 = 32.8 A. 34.8 A uses 0.87 (41–45°C). With three conductors no adjustment factor applies. The result is also limited by terminal ratings under 110.14(C).

    Reference: NFPA 70, National Electrical Code, 2017, Table 310.15(B)(16), Table 310.15(B)(2)(a)

  5. Under the 2017 NEC, which of these 125-V, 15/20-A dwelling receptacles requires GFCI protection under 210.8(A)?

    Answer: A receptacle in the laundry area

    210.8(A) requires GFCI protection in dwelling bathrooms, garages and accessory buildings, outdoors, crawl spaces, unfinished basements, kitchen countertops, within 6 feet of sinks, boathouses, within 6 feet of bathtubs or showers, and laundry areas (210.8(A)(10)). Bedrooms, living rooms and hallways need AFCI protection (210.12), not GFCI.

    Reference: NFPA 70, National Electrical Code, 2017, 210.8(A)(10)

  6. A device box will hold three 12/2 NM cables with ground, one duplex receptacle and internal cable clamps. Using 314.16(B) and Table 314.16(B), what minimum box volume is required?

    Answer: 22.50 cu in

    Each 12 AWG volume allowance is 2.25 cu in. Conductors: 6 insulated × 2.25 = 13.50. All grounds together count as one: 2.25. The receptacle (one yoke) counts as two conductors: 4.50. Internal clamps (any number) count as one: 2.25. Total = 13.50 + 2.25 + 4.50 + 2.25 = 22.50 cu in. Forgetting the clamps gives 20.25.

    Reference: NFPA 70, National Electrical Code, 2017, 314.16(B), Table 314.16(B)

  7. A 4,000-W baseboard heater operates at 240 V. What current does it draw and what is its resistance?

    Answer: 16.7 A; 14.4 ohms

    I = P ÷ E = 4,000 ÷ 240 = 16.7 A. R = E² ÷ P = 240² ÷ 4,000 = 57,600 ÷ 4,000 = 14.4 ohms (check: 240 ÷ 16.7 = 14.4). 33.3 A uses 120 V. Because heaters are continuous loads, the branch circuit must be at least 125% of 16.7 A (424.3(B)).

    Reference: General electrical theory, Ohm's law and the power formula

  8. An installer wants to cable-tie a Class 2 thermostat cable to the outside of an EMT raceway that carries power conductors for an unrelated load (not the equipment the thermostat controls). Under 725.143, is that allowed?

    Answer: No; Class 2 cables may not be strapped, taped or attached to the outside of a raceway for support

    725.143 prohibits Class 2 and Class 3 circuit conductors from being strapped, taped or attached by any means to the exterior of any conduit or other raceway as a means of support. The narrow allowance in 300.11 for Class 2 control wiring connected to the equipment served by that raceway doesn't apply here, because the raceway feeds an unrelated load. Being metal or plenum rated doesn't change the rule.

    Reference: NFPA 70, National Electrical Code, 2017, 725.143

  9. A 120-V branch circuit supplies a household fire alarm control unit. Under 760.41(B) and 760.121(B), what is required of that circuit?

    Answer: It must be an individual branch circuit, not supplied through GFCI or AFCI devices

    760.41(B) (non-power-limited) and 760.121(B) (power-limited) both require the branch circuit supplying fire alarm equipment to supply no other loads (an individual branch circuit) and prohibit supplying it through GFCI or AFCI devices. The circuit disconnect must be identified in red, accessible only to qualified personnel and identified as "FIRE ALARM CIRCUIT." GFCI protection is the top distractor because a nuisance trip would silently disable the alarm.

    Reference: NFPA 70, National Electrical Code, 2017, 760.41(B), 760.121(B)

  10. Under 29 CFR 1926.1053(b)(12), what type of portable ladder must be used where the employee or ladder could contact exposed energized electrical equipment?

    Answer: A ladder with nonconductive side rails

    1926.1053(b)(12) requires ladders to have nonconductive side rails (fiberglass or wood) if they are used where the employee or the ladder could contact exposed energized electrical equipment. Taping a metal ladder doesn't make it nonconductive.

    Reference: 29 CFR Part 1926, 1926.1053(b)(12)

Sources

Questions last verified October 22, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.