Mississippi licensing exam

Mississippi Master Electrician Exam: Practice Test & Licensing Guide

The PSI trade exam for Mississippi electrical contractors: 80 questions on the 2020 NEC covering services, grounding, conductors, raceways, motors and safety. Open book, 70% to pass.

Questions
80
Time limit
3 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10General Electrical Knowledge

What must the marking on each service, feeder or branch-circuit disconnecting means show when its purpose is not evident from its location and arrangement?

Requirements at a glance

AgencyMississippi State Board of Contractors (MSBOC); exams by PSI
LicenseCommercial Certificate of Responsibility (projects of $50,000 or more)
Exams80 questions, 3 hours, 70%, plus the Law and Business Management exam
Books allowed2020 NEC, 29 CFR 1926 and Ugly's Electrical References
Fees$120 per PSI exam portion (nonrefundable), plus the MSBOC application fee ($400 commercial; $100 for each added classification)

Qualifying individuals for a Mississippi commercial electrical contractor classification. This is the state contractor trade exam, not a local master electrician card.

How to get licensed, step by step

  1. Apply to the MSBOC

    Send the application, fee and a CPA-reviewed financial statement to the Board. The firm names a qualifying individual who takes the exams.

    MSBOC: contractor licenses (opens in a new tab)Mississippi State Board of Contractors (MSBOC) (opens in a new tab)

  2. Schedule the Law and Business exam and the master electrician exam with PSI

    After the Board approves you it notifies PSI. Book both exams ($120 per portion). You have 6 months from eligibility to pass, with unlimited retests in that window.

    Schedule with PSI (Mississippi contractors) (opens in a new tab)PSI: Mississippi contractor exam bulletin and outlines (opens in a new tab)

  3. Pass both exams at 70%

    Both exams are open book and need 70% to pass.

    PSI: Mississippi contractor exam bulletin and outlines (opens in a new tab)

  4. Get licensed

    The Board reviews applications weekly and issues the license in about 5 working days after approval. Licenses renew annually.

    Mississippi State Board of Contractors (MSBOC) (opens in a new tab)

How to prepare

  • Bring the exact editions on PSI's list: the 2020 NEC for electrical, the 2021 IPC, IMC and IFGC for commercial plumbing and mechanical, and the 2018 Fuel Gas Code with the 2021 IRC on the residential lists. Code questions use only the listed edition.
  • Tab your books before exam day with permanent tabs only. You can highlight, underline and index them, but you can't write in them or add loose papers; sticky notes are removed.
  • Mississippi licenses contractor firms, not individual tradespeople. These are the exams the firm's qualifying individual takes; journeyman and master cards are local.
  • Services, feeders and branch circuits (10) and conductors and cables (10) are the biggest sections: tab Articles 210, 215, 220, 230, 240 and 310.
  • The NEC edition on the list is 2020. Use that edition's tables and rules, not a newer book.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2020 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (NEC), 2020 Edition
  • 29 CFR 1926 (OSHA construction standards)
  • Ugly's Electrical References, 2011, 2014 or 2017 edition

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
General Electrical Knowledge6
Service Feeders and Branch Circuits10
Grounding and Bonding7
Conductors and Cables10
Raceways and Boxes7
Special Occupancies and Equipment7
Electrical Power6
Motors6
Low Voltage2
Lighting3
Illuminated Signs2
Fire Detection and Alarm Systems3
Safety Information5
Overcurrent Protection6

Exam day details

  • Administered by PSI Services for the Mississippi State Board of Contractors (MSBOC).
  • Fee: $120 per exam portion to PSI, nonrefundable. MSBOC application and license fees are separate.
  • 80 scored questions in 3 hours; 56 correct (70%) to pass. PSI adds about 10% unscored experimental items.
  • Open book: bring only the exact editions on PSI's list for this exam. You may highlight, underline and index them with permanent tabs, but not write in them; sticky notes are removed. A silent, non-programmable calculator is allowed.
  • After the MSBOC approves your application it notifies PSI, and you have 6 months from eligibility to pass; retests within that window are unlimited.
  • Every Mississippi contractor license needs the Law and Business Management exam plus the trade exam for the classification.
  • State-specific code rules override the national code, and code questions use only the listed edition.

Frequently asked questions

What's on the Mississippi Master Electrician Exam?

80 scored questions: Service Feeders and Branch Circuits 10, conductors and cables 10, grounding and bonding 7, raceways and boxes 7, special occupancies and equipment 7, general electrical knowledge 6, electrical power 6, motors 6, overcurrent protection 6, safety information 5, lighting 3, fire detection and alarm systems 3, low voltage 2, illuminated signs 2.

Which books can I bring to the Mississippi Master Electrician Exam?

The 2020 NEC, 29 CFR 1926 and Ugly's Electrical References (2011, 2014 or 2017 edition).

Does Mississippi license individual tradespeople at the state level?

No. The MSBOC licenses contractor firms, and each firm names a qualifying individual who takes these exams. Journeyman and master cards are issued locally by cities.

Free questions with answers

Show all 10 free questions and answers
  1. What must the marking on each service, feeder or branch-circuit disconnecting means show when its purpose is not evident from its location and arrangement?

    Answer: Its purpose, in a legible marking that is durable enough for the environment

    Section 110.22(A) requires each disconnecting means to be legibly marked to indicate its purpose unless the location and arrangement make the purpose evident. The marking must withstand the environment where it is installed.

    Reference: 2020 National Electrical Code (NFPA 70), 110.22(A)

  2. A 120/240-volt overhead service drop passes over a commercial parking lot where truck traffic is expected. What is the minimum clearance above the pavement?

    Answer: 18 ft

    Section 230.24(B)(4) requires 18 ft over public streets, alleys, roads, parking areas subject to truck traffic, driveways on other than residential property, and other land traversed by vehicles such as cultivated or grazing land. 15 ft applies only to residential property and driveways and commercial areas not subject to truck traffic.

    Reference: 2020 National Electrical Code (NFPA 70), 230.24(B)(4)

  3. A commercial service is supplied by two parallel sets of 350 kcmil copper conductors per phase. The grounding electrode conductor runs to the building's metal underground water pipe. Using Table 250.66, what is the minimum size of the copper grounding electrode conductor?

    Answer: 2/0 AWG copper

    For parallel sets, Table 250.66 uses the equivalent area: 2 x 350 = 700 kcmil copper, which falls in the over 600 through 1,100 kcmil row, giving 2/0 AWG copper. 2 AWG is the row for one 350 kcmil set, 1/0 AWG is for over 350 through 600 kcmil, and 3/0 AWG is for over 1,100 kcmil.

    Reference: 2020 National Electrical Code (NFPA 70), Table 250.66 (and Note 1)

  4. A 100-ampere noncontinuous load is supplied by a 100-ampere breaker. The equipment terminals are rated 75 degrees C and the conductors are THWN copper. Using Table 310.16, what is the smallest conductor size permitted?

    Answer: 3 AWG

    In the 75 C copper column of Table 310.16, 3 AWG is rated 100 A and 4 AWG is 85 A. 4 AWG is too small; 2 AWG (115 A) and 1 AWG (130 A) are larger than required.

    Reference: 2020 National Electrical Code (NFPA 70), Table 310.16; 110.14(C)

  5. A metal box contains six 12 AWG insulated conductors (none are grounds), three 12 AWG equipment grounding conductors, internal cable clamps and one single-pole switch on a yoke. Using 2.25 cu in per 12 AWG conductor, which is the smallest standard metal box that has enough volume?

    Answer: 4 in square x 2-1/8 in deep (30.3 cu in)

    Count: 6 conductors + 1 for all the grounds + 1 for the clamps + 2 for the switch yoke = 10 allowances. 10 x 2.25 = 22.5 cu in. Table 314.16(A) shows the 4 in x 2-1/8 in square box at 30.3 cu in; the 21.0 and 21.5 cu in boxes are slightly too small.

    Reference: 2020 National Electrical Code (NFPA 70), 314.16(B); Table 314.16(A)

  6. In a Class I location, what makes an area Division 2 instead of Division 1?

    Answer: Ignitable concentrations are handled or stored in closed containers and occur only under abnormal conditions

    In Class I, Division 1 ignitable concentrations of gas or vapor can exist under normal operating conditions; in Division 2 they are handled in closed containers or systems and occur only in case of accidental rupture or abnormal operation. Dust belongs in Class II.

    Reference: 2020 National Electrical Code (NFPA 70), 500.5(B)

  7. A 45-kVA, 3-phase, 208-volt transformer secondary supplies a load. What is the full-load secondary current?

    Answer: 125 A

    For three-phase, I = VA / (1.732 x E) = 45,000 / (1.732 x 208) = 45,000 / 360.3 = 124.9 A, about 125 A. 216 A leaves out the factor 1.732, and 188 A divides by 240 V as if the load were single-phase.

    Reference: General electrical knowledge, General electrical principle (3-phase power formula)

  8. A 15-hp, 230-volt, 3-phase squirrel-cage motor has a Table 430.250 full-load current of 42 A. Using an inverse-time breaker for branch-circuit short-circuit and ground-fault protection, what is the maximum standard rating permitted under Table 430.52 and its next-size allowance?

    Answer: 110 A

    Table 430.52 allows an inverse-time breaker up to 250 percent of the full-load current: 42 x 2.5 = 105 A. Section 430.52(C)(1) Exception 1 permits the next higher standard size when 105 A does not correspond to one, which is 110 A. 100 A is the next size below and is permitted but not the maximum.

    Reference: 2020 National Electrical Code (NFPA 70), 430.52(C)(1); Table 430.52; 240.6(A)

  9. Under 29 CFR 1926 Subpart M, at what height above a lower level must an employee on an unprotected side or edge be protected from falling?

    Answer: 6 ft

    Section 1926.501(b)(1) requires each employee on a walking or working surface with an unprotected side or edge 6 ft or more above a lower level to be protected by guardrails, safety nets or personal fall arrest systems.

    Reference: 29 CFR 1926, 29 CFR 1926.501(b)(1)

  10. A feeder uses 2 AWG THWN copper rated 115 A at 75 degrees C. It carries 112 A and is not a multioutlet receptacle branch circuit. What is the largest standard overcurrent device permitted under the next-size rule?

    Answer: 125 A

    Section 240.4(B) allows the next higher standard size above the conductor ampacity (115 A is not standard) when the circuit is not a multioutlet receptacle branch circuit and the device is 800 A or less. The next standard size above 115 A is 125 A (240.6(A)). 110 A is permitted but is not the largest.

    Reference: 2020 National Electrical Code (NFPA 70), 240.4(B); 240.6(A)

Sources

Questions last verified November 14, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.