Maryland licensing exam

Maryland Master Electrician Exam: Practice Test & Licensing Guide

The PSI exam for the Maryland master electrician license: 90 items worth 100 points on the 2020 NEC, with 20 points of electrical theory and 30 points of calculations. Open book, 70% to pass.

Questions
90
Time limit
4 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Wiring and Protection

A room contains 13.8-kV switchgear with exposed live parts. Under 110.33(A), what are the minimum dimensions of the entrance to the working space?

Requirements at a glance

AgencyMaryland State Board of Electricians; exam by PSI
Experience7 years of regular, principal electrical work under a master electrician (or a similar qualified government employee); the Board may credit up to 3 years for a formal electrical course. Mailed certification of experience is required.
Exam90 items worth 100 points, 4 hours, 70% to pass
Books allowed2020 NEC (tabs allowed)
Fees$65 to PSI, plus Board application and license fees

Electricians applying for a Maryland master electrician license from the State Board of Electricians, usually after 7 years of experience under a master electrician (up to 3 years of credit for approved school).

How to get licensed, step by step

  1. Confirm you qualify

    7 years of regular, principal electrical work under a master electrician (or a similar qualified government employee); the Board may credit up to 3 years for a formal electrical course. Mailed certification of experience is required.

    Maryland Department of Labor: Occupational and Professional Licensing (opens in a new tab)Maryland Code (General Assembly) (opens in a new tab)

  2. Apply through PSI

    Submit the exam application online at the PSI site below (mailed or faxed applications are returned). PSI and the Board review your documents, then email you how to pay and schedule.

    Schedule with PSI (electricians) (opens in a new tab)

  3. Pass the open-book exam

    Exam fees are non-refundable and non-transferable. If you fail, wait 30 days from your last attempt before retaking.

    Schedule with PSI (electricians) (opens in a new tab)

  4. Apply for the license

    After you pass, the Board sends you the license application. Pay the license fee and file any required insurance.

    Maryland Department of Labor: Occupational and Professional Licensing (opens in a new tab)

How to prepare

  • Tab your books before exam day: permanent plastic tabs (Avery Swift or Redi-Tag), highlighting and underlining are allowed; Post-It flags and writing in the book are not.
  • Bring the 2020 NEC, the only reference allowed in the room. PSI supplies an on-screen calculator, but tabs and a clear index save the most time.
  • Electrical theory is a big block of both exams (20 of the points or questions): practice Ohm's law, power, series and parallel circuits and AC basics.
  • Calculations are 30 of the 100 points: practice load, conductor sizing, voltage drop, motor and box-fill problems from the NEC tables and Chapter 9.
  • The bulletin (updated 9/1/2024) lists the 2020 NEC; the Board is preparing 2026 NEC questions, so check the current bulletin.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2020 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

  • NFPA 70: National Electrical Code (NEC), 2020 EditionEssential

    The only reference allowed in the exam room. Tab Articles 100, 110, 210, 220, 230, 240, 250, 310, 430 and Chapter 9. The Board is moving toward the 2026 NEC, so check the current bulletin.

    NFPA store (opens in a new tab)

Official reference list (as published by the testing agency)
  • National Electrical Code (NFPA 70), 2020 edition (the only reference allowed in the exam room; tabs allowed)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
Electrical Theory20
Wiring and Protection14
Wiring Methods and Materials13
Equipment for General Use9
Special Occupancies8
Special Equipment4
Special Communications2
Calculations30

The outline totals 100; the other items on the 90-question exam are unscored or unassigned.

Exam day details

  • Administered by PSI Services for the Maryland State Board of Electricians.
  • Fee: $65 to PSI per exam. Board application and license fees are separate.
  • 90 items worth 100 points in 4 hours; 70 points to pass. Electrical theory is ten 2-point items, and the blueprint weights above are points, not item counts.
  • Wiring and Protection covers NEC Articles 100, 110, 200-210, 215-225, 230, 240 and 250-285; Wiring Methods and Materials covers Articles 300 and 310-398; Equipment for General Use covers 400-411, 422-427, 430-450 and 455-490.
  • Edition note: The PSI bulletin (updated 9/1/2024) lists the 2020 NEC. The Board has said it is preparing exam questions for the 2026 NEC, so check the current PSI bulletin for the edition on your test date.
  • Open book: the 2020 NEC is the only reference allowed in the room, and PSI does not provide it. You may tab it with Avery Swift or Redi-Tag permanent plastic tabs; Post-It flags are not allowed.
  • PSI gives you an on-screen calculator. Study guides are not allowed in the room.
  • PSI adds five to ten unscored experimental questions; the time spent on them does not count against your exam time.
  • Apply to PSI online first; once approved you receive an email on how to pay and schedule. The exam fee is non-refundable and non-transferable.
  • If you fail, wait 30 days from your last attempt before retaking the exam.

Frequently asked questions

What's on the Maryland master electrician exam?

90 items worth 100 points: calculations 30, electrical theory 20, wiring and protection 14, wiring methods and materials 13, equipment for general use 9, special occupancies 8, special equipment 4 and special communications 2.

Which NEC edition does the Maryland electrician exam use?

The PSI bulletin lists the 2020 NEC. The Board is preparing questions for the 2026 NEC, so check the current bulletin for your test date.

How long do I wait to retake the Maryland master electrician exam?

30 days from your most recent attempt.

Free questions with answers

Show all 10 free questions and answers
  1. A room contains 13.8-kV switchgear with exposed live parts. Under 110.33(A), what are the minimum dimensions of the entrance to the working space?

    Answer: 24 inches wide and 6-1/2 feet high

    110.33(A) requires at least one entrance not less than 24 in. wide and 6-1/2 ft high to give access to the working space about equipment over 1,000 volts. Large equipment (switchgear over 6 ft wide) needs an entrance at each end unless the working space allows a continuous and unobstructed way out. 30 in. is the working-space width of 110.26(A)(2).

    Reference: NFPA 70, National Electrical Code (NEC), 2020 edition, 110.33(A)

  2. Type UF cable will supply an outdoor 120-volt, 20-ampere branch circuit at a dwelling. The circuit is GFCI protected and installed in a lawn area. What is the minimum cover from Table 300.5?

    Answer: 12 inches

    Table 300.5, Column 4 gives 12 in for residential branch circuits rated 120 volts or less with GFCI protection and maximum overcurrent protection of 20 amperes. Without those conditions direct burial cable needs 24 in (Column 1).

    Reference: NFPA 70, National Electrical Code (NEC), 2020 edition, Table 300.5, Column 4

  3. A motor has a nameplate current of 32 amperes and a marked service factor of 1.15. What is the maximum trip setting of the overload device under the general rule?

    Answer: 40 amperes

    430.32(A)(1) sets the overload trip at not more than 125 percent of the nameplate current for motors marked with a service factor of 1.15 or more or a temperature rise of 40 C or less: 32 x 1.25 = 40 A. 36.8 A uses the 115 percent figure that applies to all other motors, 44.8 A uses 140 percent (the 430.32(C) ceiling allowed only when the 125 percent device will not let the motor start), and 35.2 A uses 110 percent.

    Reference: NFPA 70, National Electrical Code (NEC), 2020 edition, 430.32(A)(1)

  4. Under the Code's hazardous (classified) location classes, a Class II location is one that is hazardous because of the presence of which of the following?

    Answer: Combustible dust

    500.5 defines Class I as flammable gases, flammable liquid-produced vapors or combustible liquid vapors, Class II as combustible dust, and Class III as easily ignitable fibers or flyings. Class II locations include grain handling and coal dust areas.

    Reference: NFPA 70, National Electrical Code (NEC), 2020 edition, 500.5

  5. A permanently installed sound system's amplifier outputs will be wired to the loudspeakers with Class 2 cable. When does 640.9(C) permit this?

    Answer: When the amplifier is listed and marked for Class 2 wiring

    Section 640.9(C) allows amplifier output circuits carrying audio program signals to use Class 2 or Class 3 wiring methods only where the amplifier is listed and marked for use with Class 2 or Class 3 wiring, and the wiring then follows 725.133 and 725.154. Otherwise Chapter 3 wiring methods apply. Speaker impedance and fusing don't make the circuit Class 2.

    Reference: NFPA 70, National Electrical Code (NEC), 2020 edition, 640.9(C)

  6. Article 727 covers instrumentation tray cable (Type ITC) for instrumentation and control circuits. What are the maximum circuit limits under 727.1?

    Answer: 150 volts and 5 amperes

    Section 727.1 states that Article 727 covers the use, installation and construction of instrumentation tray cable for instrumentation and control circuits operating at 150 volts or less and 5 amperes or less. The 300-volt figure is the ITC insulation rating, not the circuit limit.

    Reference: NFPA 70, National Electrical Code (NEC), 2020 edition, 727.1

  7. A 240-volt dedicated branch circuit for a heater has a continuous load of 24 A and a noncontinuous load of 6 A. Terminations are rated 75 degrees C and the conductors are copper THWN. Which is the smallest conductor permitted?

    Answer: 8 AWG

    Minimum conductor ampacity = (24 x 1.25) + 6 = 30 + 6 = 36 A. In the 75 degrees C column of Table 310.16, 10 AWG is 35 A, just short of 36 A, so 8 AWG (50 A) is the smallest. 10 AWG is what you get by adding 24 + 6 = 30 A without the 125 percent factor; 12 AWG (25 A) is smaller still.

    Reference: NFPA 70, National Electrical Code (NEC), 2020 edition, 210.19(A)(1); Table 310.16

  8. Using Table 220.55 column C and its Note 1, what is the demand load for a single 16-kW household electric range?

    Answer: 9,600 W

    A single range of 12 kW or less has a column C demand of 8 kW. Note 1 increases the column C value by 5 percent for each additional kilowatt of range rating over 12 kW. 16 kW is 4 kW over, so the increase is 20 percent: 8,000 x 1.20 = 9,600 W. 8,000 W ignores Note 1, and the nameplate (16,000 W) is not used. 10,400 W is a 30 percent increase.

    Reference: NFPA 70, National Electrical Code (NEC), 2020 edition, Table 220.55, Note 1

  9. A 240-volt heating element draws 12.5 amperes. What is its resistance?

    Answer: 19.2 ohms

    R = E / I = 240 / 12.5 = 19.2 ohms. 3,000 is the power in watts (E x I), and 0.052 comes from inverting the formula (I / E).

    Reference: Electrical theory reference (Ohm's law and power formulas; PSI Maryland master electrician content outline), Ohm's law, R = E/I

  10. How much current flows in a 120-volt circuit with a total resistance of 8 ohms?

    Answer: 15 amperes

    I = E / R = 120 / 8 = 15 A. 960 is E x R, 0.067 is R / E, and 112 is E - R.

    Reference: Electrical theory reference (Ohm's law and power formulas; PSI Maryland master electrician content outline), Ohm's law, I = E/R

Sources

Questions last verified November 16, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.