Question 1 of 10General Knowledge

A 240-volt, single-phase resistive heater draws 15 amperes. How many watts does it use?

Requirements at a glance

AgencyNo state card: local jurisdictions license journeymen. New Orleans Class D requires an ICC F17 results report; exam given by ICC through Pearson VUE
Exam80 questions, 4 hours, open book; passing score not published by ICC
Books allowedNEC and Ugly's Electrical References per the ICC bulletin (F17 lists the 2014 NEC; R17 lists the 2023 NEC)
Fees$120 to Pearson VUE; New Orleans Class D license $60 per year
Other jurisdictionsShreveport sends applicants to ICC or the LSLBC; Kenner requires a Jefferson Parish or LSLBC state electrical license; Jefferson Parish runs its own exam (details unconfirmed)

Electricians applying for a local journeyman license in a Louisiana city that accepts the ICC exam, such as New Orleans (Class D). Louisiana has no state journeyman card.

How to get licensed, step by step

  1. Confirm the exam and NEC edition

    New Orleans names ICC F17, which ICC ties to the 2014 NEC. ICC's R17 uses the 2023 NEC with the same weights. Ask ICC and your jurisdiction which code and edition apply before you test.

    ICC exams through Pearson VUE (opens in a new tab)

  2. Register with Pearson VUE

    Schedule the ICC exam online or at 1-888-422-7233 ($120).

    ICC exams through Pearson VUE (opens in a new tab)

  3. Pass and get the official report

    New Orleans requires the ICC Official Results Report; a stamped unofficial copy is rejected.

    ICC exams through Pearson VUE (opens in a new tab)

  4. Apply to the city

    In New Orleans, apply for the Class D license through the One Stop App. You must work under a Class A electrical contractor.

    City of New Orleans One Stop App (opens in a new tab)

How to prepare

  • Weights favor wiring methods and materials (26%) and branch circuits and conductors (19%): tab NEC Chapters 3 and 2 and the Chapter 9 tables.
  • Our questions use the 2023 NEC. If your jurisdiction tests F17 (2014 NEC), article and table numbers may differ, so verify against the edition you bring.
  • Tab Ugly's for voltage drop, load and motor calculations; they carry a lot of the open-book calculation items.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2023 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (NEC). New Orleans names exam F17, which ICC bases on the 2014 NEC; ICC's R17 version of the same exam uses the 2023 NEC. Our questions use the 2023 NEC.
  • Ugly's Electrical References (any edition)

What's on the exam

Official content outline from International Code Council (ICC), given by Pearson VUE (number of questions per topic):

TopicQuestions
General Knowledge6
Services and Service Equipment11
Feeders4
Branch Circuits and Conductors19
Wiring Methods and Materials26
Equipment and Devices13
Control Devices4
Motors and Generators6
Special Occupancies, Equipment, and Conditions11

The outline totals 100; the other items on the 80-question exam are unscored or unassigned.

Exam day details

  • Administered by International Code Council (ICC), given by Pearson VUE.
  • Fee: $120 to Pearson VUE. City license fees are separate (New Orleans Class D: $60 per year).
  • 80 questions in 4 hours, open book. ICC's bulletin does not print a passing score; we use 70% as a practice target only.
  • Edition warning: the City of New Orleans names ICC exam F17 (National Standard Journeyman Electrician), and ICC's bulletin ties F17 to the 2014 NEC. ICC's R17 exam has the same weights and uses the 2023 NEC, which Louisiana adopts on January 1, 2027. Our questions are written to the 2023 NEC; confirm the exam code and NEC edition with ICC and your jurisdiction before you test.
  • New Orleans requires the ICC Official Results Report (an unofficial stamped copy is rejected). A New Orleans journeyman must work under a Class A electrical contractor.
  • Shreveport sends journeyman testing applicants to ICC. Kenner does not examine: it requires a current Jefferson Parish license or an LSLBC state electrical license. Jefferson Parish runs its own electrical exam application; we could not confirm its format, so check with the parish.
  • Schedule with Pearson VUE (1-888-422-7233). Bring your own NEC and references as the bulletin allows.

Frequently asked questions

Does Louisiana have a state journeyman electrician exam?

No. Local jurisdictions license journeymen. New Orleans (Class D) requires a passing ICC F17 results report; Shreveport directs applicants to ICC or the LSLBC; Kenner accepts a Jefferson Parish or LSLBC state electrical license.

What's on the ICC journeyman electrician exam?

80 questions by weight: wiring methods and materials 26%, branch circuits and conductors 19%, equipment and devices 13%, services 11%, special occupancies 11%, general knowledge 6%, motors and generators 6%, feeders 4%, control devices 4%.

Which NEC edition is tested?

It depends on the exam code. ICC lists the 2014 NEC for F17, the code New Orleans names, and the 2023 NEC for R17 with the same weights. Our questions use the 2023 NEC. Confirm the edition with ICC and your jurisdiction.

What is the passing score?

ICC does not publish it in its exam bulletin. Check the ICC exam catalog or Pearson VUE.

Free questions with answers

Show all 10 free questions and answers
  1. A 240-volt, single-phase resistive heater draws 15 amperes. How many watts does it use?

    Answer: 3,600 W

    For a resistive load P = E x I = 240 x 15 = 3,600 W. 255 comes from adding the values, 16 from dividing volts by amps (which gives ohms), and 225 from squaring the current.

    Reference: NFPA 70, National Electrical Code (2023), General electrical theory: power formula (Ugly's)

  2. Under the 2023 NEC, a service uses 250 kcmil copper ungrounded conductors. The grounding electrode conductor runs only to a single driven ground rod. What is the largest copper size the Code requires for that grounding electrode conductor?

    Answer: 6 AWG

    Table 250.66 would call for 2 AWG for a 250 kcmil conductor, but 250.66(A) caps the conductor at 6 AWG copper when it goes only to rod, pipe or plate electrodes. 4 AWG is the cap for a concrete-encased electrode under 250.66(B), and 8 AWG applies only to 2 AWG and smaller service conductors.

    Reference: NFPA 70, National Electrical Code (2023), 250.66(A) and Table 250.66

  3. Under the 2023 NEC, a feeder serves 96 amperes of continuous load and 64 amperes of noncontinuous load. Terminations are rated 75 C and no correction or adjustment factors apply. What is the smallest copper THWN feeder conductor permitted, using Table 310.16?

    Answer: 3/0 AWG

    Section 215.2(A)(1) requires an ampacity of at least the noncontinuous load plus 125 percent of the continuous load: 64 + (1.25 x 96 = 120) = 184 A. In the 75 C copper column of Table 310.16, 2/0 AWG is 175 A (too small) and 3/0 AWG is 200 A, so 3/0 AWG is the minimum. 2/0 AWG would satisfy only the 160 A sum without the 125 percent factor, 1/0 AWG (150 A) is too small even for that, and 4/0 AWG (230 A) is larger than needed.

    Reference: NFPA 70, National Electrical Code (2023), 215.2(A)(1) and Table 310.16

  4. Under the 2023 NEC, what is the minimum conductor ampacity for a branch circuit supplying a continuous 24-ampere load?

    Answer: 30 A

    Section 210.19(A)(1)(a) requires the conductor to carry 125 percent of the continuous load: 24 x 1.25 = 30 A. 24 A ignores the factor, 36 A applies 150 percent, and 20 A is below the load itself.

    Reference: NFPA 70, National Electrical Code (2023), 210.19(A)(1)

  5. Under the 2023 NEC, what is the minimum cover for PVC conduit buried in a general location (not under a building, street or driveway) with no concrete or other protection?

    Answer: 18 in.

    Table 300.5(A), Column 3 (nonmetallic raceways listed for direct burial without concrete encasement) requires 18 in. in all locations not specified otherwise. 6 in. is for rigid metal or IMC, 24 in. is for direct-burial cables, and 12 in. is for GFCI-protected residential 120-volt, 20-ampere circuits.

    Reference: NFPA 70, National Electrical Code (2023), Table 300.5(A)

  6. Under the 2023 NEC, Type UF cable supplies a 120-volt, 20-ampere outdoor receptacle circuit at a one-family dwelling. The circuit has GFCI protection and no concrete cover. What is the minimum burial depth?

    Answer: 12 in.

    Table 300.5(A), Column 4 allows 12 in. for residential branch circuits rated 120 volts or less with GFCI protection and overcurrent protection of 20 A or less. Without these conditions, direct-burial cable needs 24 in. (Column 1).

    Reference: NFPA 70, National Electrical Code (2023), Table 300.5(A), Column 4

  7. Under the 2023 NEC, a cord-connected pendant luminaire is to hang over a bathtub. How close may any part of it be to the tub rim?

    Answer: It may not be within 3 ft horizontally or 8 ft vertically of the tub rim

    Section 410.10(D) keeps cord-, chain-, cable- or pendant-supported luminaires and paddle fans out of the zone 3 ft horizontally and 8 ft vertically from the bathtub rim or shower threshold. Enclosing the lamp does not remove the restriction.

    Reference: NFPA 70, National Electrical Code (2023), 410.10(D)

  8. Under the 2023 NEC, a general-use ac snap switch is rated 20 amperes. What is the largest motor load it may control?

    Answer: 16 A

    Section 404.14(A)(3) limits motor loads on an ac general-use snap switch to 80 percent of the switch ampere rating: 20 x 0.80 = 16 A. 20 A ignores the derating, 25 A is 125 percent, and 12 A is 60 percent.

    Reference: NFPA 70, National Electrical Code (2023), 404.14(A)(3)

  9. Under the 2023 NEC, a 10 hp, 230-volt, three-phase motor has a nameplate of 26 A. What minimum ampacity is required for the branch-circuit conductors?

    Answer: 35 A

    Section 430.22 requires 125 percent of the motor full-load current taken from Table 430.250, not the nameplate: the 10 hp, 230 V table value is 28 A, and 28 x 1.25 = 35 A. 26 A is the nameplate, 28 A is the table value, and 32.5 A is 125 percent of the nameplate.

    Reference: NFPA 70, National Electrical Code (2023), 430.6(A)(1), 430.22 and Table 430.250

  10. Under the 2023 NEC, how quickly must an emergency system supply power after loss of normal power?

    Answer: Within 10 seconds

    Section 700.12 requires emergency systems to be available within 10 seconds of loss of the normal supply. Legally required standby systems have a 60-second window (701.12), and optional standby has no time limit.

    Reference: NFPA 70, National Electrical Code (2023), 700.12