Kentucky licensing exam

Kentucky Master Electrician Exam: Practice Test & Licensing Guide

The ICC Kentucky Standard Master Electrician exam (701): 100 questions in 5 hours on the 2023 NEC, from services and feeders to motors and special occupancies. Open book, 70% to pass.

Questions
100
Time limit
5 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Services and Service Equipment

The roof framing at a house makes it impracticable to mount the service head above the point where the overhead service conductors attach to the building. Under the exception to 230.54(C), how far from the point of attachment may the service head be located?

Requirements at a glance

AgencyKentucky DHBC, Division of Electrical; exam by ICC at Pearson VUE
Experience16,000 hours of verifiable experience (KRS 227A.060)
Exam100 questions, 5 hours, 70% to pass
Books allowed2023 NEC and Ugly's Electrical References (any edition)
Fees$100 exam; DHBC application and license fees are separate

Applicants for a Kentucky master electrician license from the Department of Housing, Buildings and Construction. An electrical contractor must be or employ a master electrician. The master electrician license alone does not require the Business and Law exam.

How to get licensed, step by step

  1. Apply to DHBC

    Send DHBC your license application with proof of experience. Licenses are issued by the Department, not the testing vendor.

    Kentucky Department of Housing, Buildings and Construction (DHBC) (opens in a new tab)Kentucky Revised Statutes (KRS 227A, 198B, 318) (opens in a new tab)

  2. Schedule the master electrician exam

    Register and pay the $100 exam fee ($60 for Business and Law) for a Pearson VUE testing center. If you fail, you wait 10 days before you retest. Schedule through Pearson VUE (ICC); DHBC also accepts Prov and NASCLA electrical results.

    ICC: Kentucky candidate bulletin (1/17/2026) (opens in a new tab)DHBC: Electrical new application checklists (2/4/2025) (opens in a new tab)

  3. Pass and get licensed

    You need 70% to pass. Your passing score is valid for 3 years, so file your license application and any required insurance before it expires.

    Kentucky Department of Housing, Buildings and Construction (DHBC) (opens in a new tab)815 KAR: DHBC administrative regulations (opens in a new tab)

How to prepare

  • Bring the exact editions on the bulletin: the 2023 NEC for electricians and the 2015 IMC with NFPA 54 (2009) for HVAC (the 2018 Kentucky Building Code references NFPA 54 2012, but the bulletin lists 2009). Kentucky amends the NEC, so read the state amendments.
  • Tab your books before exam day. Both ICC electrical and HVAC exams are open book with four-option questions.
  • Wiring methods and materials (19%), services (16%) and branch circuits (16%) are over half the exam: tab Chapter 3, Articles 210, 230, 240 and 250.
  • Master candidates also face general knowledge and plan reading (12%) and special occupancies (12%).
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the 2023 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • NFPA 70: National Electrical Code (NEC), 2023 edition
  • Ugly's Electrical References (any edition)

What's on the exam

Official content outline from ICC (Pearson VUE) (number of questions per topic):

TopicQuestions
General Knowledge and Plan Reading12
Services and Service Equipment16
Feeders4
Branch Circuits and Conductors16
Wiring Methods and Materials19
Equipment and Devices10
Control Devices3
Motors and Generators8
Special Occupancies, Equipment, and Conditions12

Exam day details

  • Administered by ICC (Pearson VUE) for the Kentucky Department of Housing, Buildings and Construction.
  • Fee: $100 to Pearson VUE per exam. DHBC application and license fees are separate.
  • 100 questions in 5 hours; 70% to pass (815 KAR 35:060).
  • Master license: 16,000 hours of verifiable experience (KRS 227A.060). Applications are $100, $200 or $400 by license type, and licenses renew every two years (815 KAR 35:060).
  • Kentucky also accepts the NASCLA master electrician exam (100 questions, 270 minutes, 75% to pass); NASCLA scores are valid for 3 years.
  • Open book: bring your own copies of the listed references. Check the ICC bulletin for what tabbing and highlighting is allowed.
  • If you fail, you wait 10 days before you retake the exam.
  • A passing score is valid for 3 years (815 KAR 35:060 for electricians; 815 KAR 8:010 for HVAC).

Note: DHBC accepts Pearson VUE (ICC), Prov and NASCLA electrical exams, and gives its own in-person HVAC exams; Pearson VUE is the ICC route in the 1/17/2026 bulletin. The ICC bulletin is the source for the format and topic weights, and the 70% pass score is from 815 KAR 35:060 and 815 KAR 8:010.

Frequently asked questions

What is on the Kentucky master electrician exam?

100 questions: wiring methods and materials 19%, services and service equipment 16%, branch circuits and conductors 16%, general knowledge and plan reading 12%, special occupancies 12%, equipment and devices 10%, motors and generators 8%, feeders 4% and control devices 3%.

Which NEC edition does Kentucky use?

The ICC bulletin lists the 2023 NEC. Kentucky adopts the NEC with state amendments, so check the amendments on your test date.

Can I bring Ugly's to the exam?

Yes. The bulletin allows Ugly's Electrical References in any edition, along with the 2023 NEC.

Free questions with answers

Show all 10 free questions and answers
  1. The roof framing at a house makes it impracticable to mount the service head above the point where the overhead service conductors attach to the building. Under the exception to 230.54(C), how far from the point of attachment may the service head be located?

    Answer: 24 in.

    Section 230.54(C) requires the service head to be above the point of attachment of the overhead service conductors. The exception permits it to be located not farther than 600 mm (24 in.) from the point of attachment where mounting it above is impracticable. Drip loops under 230.54(F) are still required so water cannot enter the service raceway.

    Reference: 2023 National Electrical Code, 230.54(C), Exception

  2. A 50-ampere service carries the total load of a small building and a feeder from that service supplies the entire load. What is the minimum feeder conductor ampacity relationship to the service conductors?

    Answer: The feeder ampacity must not be less than that of the service conductors

    Section 215.2(C) says feeder conductors carrying the total load supplied by service conductors with an ampacity of 55 amperes or less must have an ampacity not less than that of the service conductors, even if the calculated load is smaller.

    Reference: 2023 National Electrical Code, 215.2(C)

  3. A dwelling has a laundry receptacle supplied by the required laundry branch circuit. Which statement about that circuit is correct?

    Answer: It must be a 20-ampere circuit with no other outlets

    Section 210.11(C)(2) requires at least one additional 20-ampere branch circuit to supply the laundry receptacle outlet(s) required by 210.52(F), and this circuit may have no other outlets. The bathroom circuit in 210.11(C)(3) is likewise dedicated.

    Reference: 2023 National Electrical Code, 210.11(C)(2)

  4. Electrical metallic tubing runs horizontally along a wall between two boxes. What are the maximum securing intervals under 358.30?

    Answer: Within 3 ft of each box and at intervals not exceeding 10 ft

    Section 358.30(A) requires EMT to be securely fastened at intervals not exceeding 3 m (10 ft) and within 900 mm (3 ft) of each outlet box, junction box, device box, cabinet, conduit body or other termination. The 12 in. and 4 1/2 ft figures belong to nonmetallic-sheathed cable and flexible metal conduit.

    Reference: 2023 National Electrical Code, 358.30(A)

  5. What is the maximum distance between supports for 1-in. rigid metal conduit?

    Answer: 12 ft

    Table 344.30(B) lists 10 ft for trade sizes 1/2 and 3/4, 12 ft for trade size 1, 14 ft for 1 1/4 and 1 1/2, 16 ft for 2 and 2 1/2, and 20 ft for 3 and larger. A 14 ft spacing applies to the next larger sizes.

    Reference: 2023 National Electrical Code, Table 344.30(B)

  6. A continuous-duty, 10 hp, 460-volt, three-phase squirrel-cage induction motor is installed. Using the motor tables of Article 430, what is the minimum ampacity of the branch-circuit conductors?

    Answer: 17.5 A

    Section 430.22 requires 125 percent of the motor full-load current from the tables (430.6(A)(1)). Table 430.250 gives 14 A for a 10 hp, 460 V three-phase motor: 14 x 1.25 = 17.5 A. 14 A omits the 125 percent factor, 21 A is the table current for a 15 hp motor, and 35 A uses the 250 percent breaker multiplier.

    Reference: 2023 National Electrical Code, 430.22; Table 430.250

  7. At a new outdoor residential pool, a luminaire is to be mounted on a pole 4 ft horizontally from the inside wall of the pool. What is the minimum mounting height above the maximum water level?

    Answer: 12 ft

    Section 680.22(B)(1) requires luminaires, lighting outlets and paddle fans in new outdoor pool areas to be at least 3.7 m (12 ft) above the maximum water level when installed over the pool or within 1.5 m (5 ft) horizontally of its inside walls. A point 4 ft from the wall falls inside the 5 ft zone, so 12 ft applies. 8 ft and 10 ft are common 'overhead clearance' guesses and are too low.

    Reference: 2023 National Electrical Code, 680.22(B)(1)

  8. Which location for overcurrent protective devices in a dwelling is specifically prohibited by 240.24?

    Answer: Directly over the steps of a stairway leading to the second floor

    Section 240.24(F) states that overcurrent protective devices shall not be located over steps of a stairway. Section 240.24(E) separately prohibits them in bathrooms, and 240.24(D) keeps them away from easily ignitible material such as clothes closets. A garage, basement or laundry room is acceptable if 240.24(A) accessibility and 240.24(C) protection from physical damage are met.

    Reference: 2023 National Electrical Code, 240.24(F)

  9. A single motor controller is installed for an individual motor. Where must its individual disconnecting means be located?

    Answer: In sight from the motor controller location

    Section 430.102(A) requires an individual disconnecting means for each motor controller, and the disconnecting means must be located in sight from the controller location. The exceptions cover circuits over 1000 volts, groups of coordinated controllers on one machine, and valve actuator motor assemblies.

    Reference: 2023 National Electrical Code, 430.102(A)

  10. A multifamily building has four household electric ranges, each rated 11 kW. Using Table 220.55 with the Column C method, what is the feeder demand load for the ranges?

    Answer: 17 kW

    Table 220.55, Column C gives a maximum demand of 17 kW for four ranges not over 12 kW rating, in place of 4 x 11 = 44 kW connected. 8 kW is the Column C value for a single range, and 29 kW does not correspond to a table value for four ranges.

    Reference: 2023 National Electrical Code, 220.55; Table 220.55, Column C

Sources