Georgia licensing exam

Georgia Conditioned Air Contractor Exam (Class I and Class II): Practice Test & Licensing Guide

The PSI exam for Georgia's Class I and Class II conditioned air (HVAC) contractor licenses: 100 questions on system design, installation, and maintenance under the 2024 Georgia mechanical and gas codes. Open book, 70 to pass.

Questions
100
Time limit
7 hours
Passing score
70%

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10System Design

A furnace has an output capacity of 60,000 Btu/h and the manufacturer specifies a 45 degree F air temperature rise. What supply airflow is needed to deliver that rise (standard air)?

Requirements at a glance

AgencyGeorgia Construction Industry Licensing Board (Division of Conditioned Air Contractors); exams by PSI
ExperienceClass I: 4 years of experience; Class II: 5 years, including systems above 175,000 Btu/h heating and 60,000 Btu/h cooling. Both need an EPA certification and a Board-approved heat loss/gain and duct design course.
Exam100 questions, 7 hours in two 3.5-hour parts, open book, 70 to pass (same content for Class I and II)
Books allowed2024 Georgia Mechanical Code and Gas Code, 2023 NEC, ACCA Manuals D and J, Refrigeration and Air Conditioning Technology 10th Edition or Modern Refrigeration and Air Conditioning 22nd Edition, the NASCLA Georgia guide and 29 CFR 1926
Fees$40 application fee ($30 plus a $10 processing fee) per the Secretary of State form. The PSI exam fee and license fee are not published in the candidate bulletin; confirm them with PSI and the Board.

Qualifying agents for a Georgia conditioned air contractor license from the Construction Industry Licensing Board. Class I is limited to systems up to 175,000 Btu/h heating and 60,000 Btu/h cooling; Class II is unrestricted.

How to get licensed, step by step

  1. Apply to the Board

    Submit the application, three references on the Board's form and the $40 fee to the Construction Industry Licensing Board (Macon; (404) 424-9966). The Board must approve you before you can register with PSI.

    Georgia Division of Conditioned Air Contractors (CILB) (opens in a new tab)Georgia Rules 121-3 (CILB license requirements) (opens in a new tab)

  2. Register with PSI

    After approval, register and pay PSI online or at 855-898-0711. Bring the allowed references and a silent, non-programmable calculator.

    Schedule with PSI (Georgia CILB exams) (opens in a new tab)PSI bulletin: Georgia conditioned air contractors (opens in a new tab)

  3. Take the exam

    Scaled score, 70 to pass. If you fail twice, the PSI bulletin requires a Board-approved review course before a third attempt.

    PSI bulletin: Georgia conditioned air contractors (opens in a new tab)

  4. Finish licensing

    Send your results and the license fee to the Board.

    Georgia Division of Conditioned Air Contractors (CILB) (opens in a new tab)

How to prepare

  • Georgia's exams are scaled with 70 to pass. The Board's 2026 reference lists apply to exams through December 31, 2026; check for the updated list if you test later.
  • Tab your books with permanent tabs before exam day. Highlighting and underlining are allowed; notes, sticky flags and loose papers are not.
  • System design is 55 of the 100 questions: load calculations (Manual J), duct sizing (Manual D), equipment selection and refrigeration cycle.
  • Since May 1, 2026 the exam is based only on the 2024 Georgia Mechanical and Gas Codes. Tab IMC Chapters 4 through 8 and IFGC Chapters 4, 5 and 6.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below, and most questions come from the Georgia Mechanical Code and the Georgia Gas Code and the ACCA manuals and the 2023 NEC. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

Official reference list (as published by the testing agency)
  • 2024 Georgia Mechanical Code (2024 International Mechanical Code with Georgia amendments)
  • 2024 Georgia Gas Code (2024 International Fuel Gas Code with Georgia amendments)
  • Georgia State Electrical Code (2023 NEC or NEC Handbook)
  • ACCA Manual D (3rd Edition, 2016, v2.5) and Manual J (8th Edition, 2016, v2.5)
  • Refrigeration and Air Conditioning Technology, 10th Edition (Whitman and Johnson) or Modern Refrigeration and Air Conditioning, 22nd Edition (Althouse, Turnquist, Bracciano)
  • Contractors Guide to Business, Law, and Project Management, Georgia Construction Industry Licensing Board, 5th Edition (NASCLA)
  • 29 CFR Part 1926 (OSHA) and Carrier System Design Manuals (1 to 3)

What's on the exam

Official content outline from PSI Services (number of questions per topic):

TopicQuestions
Regulations, Laws, and Administration: Laws1
Regulations, Laws, and Administration: Regulations2
Regulations, Laws, and Administration: Administrative Requirements5
System Design55
Installation: Equipment2
Installation: Duct Systems4
Installation: Flue Venting6
Installation: Gas Piping3
Installation: Refrigerant Piping3
Installation: Condensate1
Installation: Electrical Control3
Installation: Place in Operation3
Maintain and Repair: General7
Maintain and Repair: Electrical5

Exam day details

  • Administered by PSI Services for the Georgia Construction Industry Licensing Board.
  • Fee: The Board's initial application fee is $40 ($30 plus a $10 processing fee). The PSI exam fee and the license fee are not published in the candidate bulletin, so check PSI and the Board before you apply.
  • 100 scored questions plus 20 unscored pretest questions in 7 hours, split into two 3.5-hour parts. Class I and Class II candidates take the same number of questions.
  • Open book: only the references on the Board's list are allowed (listed here for exams through December 31, 2026). The 2018 code editions were allowed until May 1, 2026; since then the exam is based only on the 2024 Georgia codes.
  • System design (load calculation and duct sizing from Manuals J and D) is 55 of the 100 questions.
  • The Board must approve your application before you can register with PSI. Scores are scaled and you need 70 to pass.
  • The time limit includes the unscored beta (pretest) questions mixed into the exam.
  • If you fail twice, the PSI bulletin requires a Board-approved review course before a third attempt.
  • Georgia has no statewide journeyman or master electrician exam and no statewide HVAC technician exam; local jurisdictions license those workers.

Frequently asked questions

What's on the Georgia conditioned air contractor exam?

100 scored questions: system design 55, installation 25 (equipment, duct, flue venting, gas piping, refrigerant piping, condensate, electrical control, place in operation), maintain and repair 12 and regulations, laws and administration 8.

Is there one exam for Class I and Class II?

The two classes take separate PSI exams with the same content outline and question counts. One question bank here prepares you for both.

Which code editions are on the exam?

The 2024 Georgia Mechanical Code and 2024 Georgia Gas Code (2024 IMC and IFGC with Georgia amendments). The 2018 editions were accepted only until May 1, 2026.

Free questions with answers

Show all 10 free questions and answers
  1. A furnace has an output capacity of 60,000 Btu/h and the manufacturer specifies a 45 degree F air temperature rise. What supply airflow is needed to deliver that rise (standard air)?

    Answer: About 1,235 CFM

    Rearrange Q = 1.08 x CFM x delta-T to CFM = Q / (1.08 x delta-T) = 60,000 / (1.08 x 45) = 60,000 / 48.6 = 1,235 CFM. 1,333 divides by the temperature rise only and omits 1.08. 926 uses a 60 degree rise. 1,111 uses 1.2 in place of 1.08.

    Reference: General HVAC engineering practice, Airflow from sensible heat equation, CFM = Q / (1.08 x delta-T)

  2. What is the maximum allowed length of a flexible air connector used between a duct and an air terminal, and may it pass through a wall?

    Answer: 14 ft, and it may not pass through a wall, floor or ceiling

    Section 603.6.2.1 limits flexible air connectors to 14 feet in length and Section 603.6.2.2 prohibits them from passing through any wall, floor or ceiling. Georgia's Section 603.6.1.1 does not limit the length of flexible air ducts, which are a different product from connectors.

    Reference: 2024 Georgia Mechanical Code (IMC 2024), Sections 603.6.2.1 and 603.6.2.2

  3. A Type B gas vent rises 20 ft above a furnace. What is the maximum horizontal length of a single-wall metal vent connector serving the appliance?

    Answer: 15 ft

    Section 503.10.9 limits the horizontal length of a single-wall connector to 75 percent of the height of the vent: 0.75 x 20 = 15 feet. A Type B double-wall connector may run 100 percent of the height (20 ft here), which is why 20 ft is tempting. 10 ft and 25 ft are not code values for this height.

    Reference: 2024 Georgia Gas Code (IFGC 2024), Section 503.10.9

  4. A new natural gas piping system in a house has a maximum working pressure of 0.5 psig. What is the minimum test pressure under the Georgia Gas Code?

    Answer: 3 psig

    Section 406.4.1 sets the test pressure at not less than 1-1/2 times the proposed maximum working pressure but not less than 3 psig. 1.5 x 0.5 = 0.75 psig, which is below the 3 psig floor, so 3 psig governs. 0.75 psig applies the multiplier but ignores the minimum.

    Reference: 2024 Georgia Gas Code (IFGC 2024), Section 406.4.1

  5. At what refrigerant charge must the installing contractor issue a certificate of test to the code official for a field-erected refrigerant piping system?

    Answer: 55 lb or more

    Section 1110.7 requires the installing contractor or registered design professional to issue a certificate of test for refrigeration systems containing 55 pounds (25 kg) or more of refrigerant. The certificate lists the test date, refrigerant, test medium and the field test pressure for the high and low sides. 6.6 lb and 100 lb are the thresholds for stop-valve requirements in Section 1109.6.

    Reference: 2024 Georgia Mechanical Code (IMC 2024), Section 1110.7

  6. A contractor's direct cost for an installation is $10,000. The contractor wants a gross profit margin of 20 percent of the selling price. What should the selling price be?

    Answer: $12,500

    Margin is a percentage of the selling price, so price = cost / (1 - margin) = 10,000 / 0.80 = $12,500. Check: $12,500 x 20% = $2,500 profit, and $12,500 - $2,500 = $10,000 cost. $12,000 is a 20 percent markup on cost (10,000 x 1.20), which gives only a 16.7 percent margin. $8,000 subtracts 20 percent from cost.

    Reference: General business practice, Markup versus gross margin in pricing

  7. A residential 24 V control transformer is rated 40 VA. What is the maximum continuous current the secondary can supply?

    Answer: About 1.67 A

    Current = VA / volts = 40 / 24 = 1.67 A. 0.6 A inverts the ratio (24 / 40). 16.7 A moves the decimal, and 960 A multiplies VA by volts. Adding accessories such as a humidifier or a second contactor can overload a 40 VA transformer and blow its fuse.

    Reference: General HVAC service practice, Control transformer rating (VA = volts x amps)

  8. At start-up of a natural gas furnace, what manifold gas pressure is normally set, unless the manufacturer's data plate says otherwise?

    Answer: About 3.5 in. w.c.

    Natural gas appliances are normally adjusted to about 3.5 inches of water column manifold pressure, while propane appliances use about 10 inches of water column. The data plate and installation instructions govern, and the setting is made with a manometer. 7 psig is a supply-side pressure for a higher-pressure system, not a manifold setting.

    Reference: General HVAC service practice, Natural gas manifold pressure at start-up

  9. A dual-run capacitor section is rated 35 microfarads with a tolerance of plus or minus 6 percent. A capacitance meter reads 31.5 microfarads on that section. What should the technician do?

    Answer: Replace it, because it is below the 32.9 microfarad lower limit

    Tolerance range = 35 x 0.94 = 32.9 to 35 x 1.06 = 37.1 microfarads. A reading of 31.5 is below the range, so the capacitor is weak and should be replaced. 29.4 would be a 16 percent allowance, which is not the rating. 31.5 does not exceed the upper limit. Always discharge the capacitor before testing.

    Reference: General HVAC service practice, Capacitor testing with a capacitance meter

  10. On a system with a metering device, the suction line temperature at the evaporator outlet reads 55 degrees F and the suction pressure corresponds to a saturation temperature of 40 degrees F. What is the evaporator superheat?

    Answer: 15 degrees F

    Superheat = suction line temperature - saturation temperature at suction pressure = 55 - 40 = 15 degrees F. 95 adds the two readings. 25 and 5 do not follow from the stated values. Superheat shows how much of the evaporator is used for boiling versus heating vapor.

    Reference: General HVAC service practice, Superheat = suction line temperature - evaporator saturation temperature

Sources

Questions last verified November 14, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.