Alabama Journeyman Electrician Exam: Practice Test & Licensing Guide

The Prov exam for the Alabama journeyman electrician license: 80 open-book questions on the 2023 NEC covering raceways, conductors, grounding, services and branch circuits, motors and more. 75% to pass.

Questions
80
Time limit
4 hours
Passing score
75%
Books
Open book

Full practice test: $19One-time payment · 12 months of access

Try 10 free practice questions

No sign-up. Every answer explains the rule and tells you where to find it in your book.

Question 1 of 10Grounding and Bonding

A service is supplied by 500 kcmil copper ungrounded service-entrance conductors in a single raceway. Using Table 250.66, what is the minimum size copper grounding electrode conductor to a metal underground water pipe electrode?

Requirements at a glance

AgencyAlabama Electrical Contractors Board (AECB); exam by Prov
Exam80 questions, 4 hours, 75% to pass, open book
Books allowed2023 NEC and American Electrician's Handbook, 17th Edition
Fee$115 to the Board with your application; Board license fees are separate

Electricians applying for an Alabama journeyman electrician license from the Alabama Electrical Contractors Board.

How to get licensed, step by step

  1. Meet the eligibility requirement

    The Board requires 8,000 hours of experience. Up to 2,000 of those hours can come from school or an approved apprenticeship.

    Alabama Electrical Contractors Board (opens in a new tab)

  2. Apply to the board

    Send the Board your application and the $115 exam fee. A new approval is required before each attempt.

    Alabama Electrical Contractors Board (opens in a new tab)

  3. Schedule with Prov

    Once the Board approves you, register and schedule your exam. Prov grades the exam right away and sends your result to the board. If you fail, wait 30 days before retesting.

    Schedule with Prov (opens in a new tab)

  4. Bring your references

    All of these exams are open book. Bring the exact books the bulletin lists; permanent tabs and pen highlighting are allowed, sticky notes and loose notes are not.

    Prov bookstore (reference books) (opens in a new tab)

How to prepare

  • Raceways and boxes, conductors and cables and general electrical knowledge are 10 questions each. Tab Chapters 3 and 9 and the Annex tables.
  • Service, feeders and branch circuits (9) and grounding and bonding (8) lean on Articles 220, 230, 240 and 250.
  • The bulletin lists the 2023 NEC. The Board has said testing moves to the 2026 NEC in 2027, so check the current bulletin before you buy books.
  • Start with the free questions above to find your weak topics, then drill those first.
  • Take at least two full timed simulations before exam day. Timing is where most people fail open-book exams.
  • Read every explanation, including for questions you got right, and look the section up in your own book.

Books for this exam

This is an open-book exam: you can bring the references below. Tabs and highlighting are allowed. Free online copies are read-only and can't be used in the exam room.

    Official reference list (as published by the testing agency)
    • NFPA 70, National Electrical Code (NEC), 2023 edition (allowed in the exam room)
    • American Electrician's Handbook, 17th Edition, McGraw Hill (allowed in the exam room)

    What's on the exam

    Official content outline from Prov, Inc. (number of questions per topic):

    TopicQuestions
    Lighting3
    Low Voltage2
    Motors6
    Electrical Power2
    Special Occupancies and Equipment6
    Raceways and Boxes10
    Conductors and Cables10
    Grounding and Bonding8
    Service, Feeders, and Branch Circuits9
    General Electrical Knowledge10
    Illuminated Signs2
    Overcurrent Protection5
    Safety Information5
    Fire Detection and Alarm Systems2

    Exam day details

    • Administered by Prov, Inc. for the Alabama Electrical Contractors Board.
    • Fee: $115 to the Electrical Contractors Board with your application (as of 1/17/2026). Board application and license fees are separate.
    • 80 questions in 4 hours; 75% to pass.
    • Eligibility: 8,000 hours of experience; up to 2,000 hours can come from school or an approved apprenticeship (AECB rule 303-X-3).
    • Prov (provexam.com, (801) 733-4455) gives the exam for the Alabama Electrical Contractors Board (AECB). The exam fee is paid to the Board with your application, not to Prov.
    • A new Board approval is required before each attempt, and you wait 30 days to retest.
    • The Prov bulletin (AL CIB 2026.11.09) lists the 2023 NEC. Our research notes say the Board plans to move testing to the 2026 NEC on January 1, 2027; check the current bulletin for the edition on your test date.
    • Highlighting and underlining in pen and permanent tabs are allowed in open-book references; sticky notes and handwritten notes are not.

    Frequently asked questions

    What's on the Alabama journeyman electrician exam?

    80 questions: raceways and boxes 10, conductors and cables 10, general electrical knowledge 10, service, feeders and branch circuits 9, grounding and bonding 8, motors 6, special occupancies and equipment 6, overcurrent protection 5, safety information 5, lighting 3, low voltage 2, electrical power 2, illuminated signs 2 and fire detection and alarm systems 2.

    Is the Alabama journeyman electrician exam open book?

    Yes. You may use the 2023 NEC and the American Electrician's Handbook, 17th Edition.

    How long must I wait to retest?

    30 days, and the Board must approve you again before each attempt.

    Free questions with answers

    Show all 10 free questions and answers
    1. A service is supplied by 500 kcmil copper ungrounded service-entrance conductors in a single raceway. Using Table 250.66, what is the minimum size copper grounding electrode conductor to a metal underground water pipe electrode?

      Answer: 1/0 AWG

      Table 250.66 groups copper service conductors: over 350 kcmil through 600 kcmil requires a 1/0 AWG copper grounding electrode conductor. 2 AWG is the size for conductors over 3/0 through 350 kcmil, which is one row too small for 500 kcmil.

      Reference: NFPA 70, National Electrical Code, 2023 edition, Table 250.66

    2. A 600-ampere feeder breaker supplies a 20-ft tap that ends in a single circuit breaker. The tap conductors are protected from physical damage in a raceway. Under the 25-ft tap rule, what is the minimum tap conductor ampacity?

      Answer: 200 A

      240.21(B)(2) requires tap conductors of not more than 25 ft to have an ampacity of at least one-third of the rating of the overcurrent device protecting the feeder: 600 A x 1/3 = 200 A. 60 A is the 10 percent figure from the 10-ft tap rule for field-installed taps leaving the enclosure, and 300 A and 400 A are one-half and two-thirds.

      Reference: NFPA 70, National Electrical Code, 2023 edition, 240.21(B)(2)

    3. A one-family dwelling has a 120/240-volt, single-phase, 150-ampere service that supplies all the loads of the dwelling. Using Table 310.12(A), what is the minimum size copper service-entrance conductor?

      Answer: 1 AWG

      Table 310.12(A) permits dwelling services and feeders to be sized to a conductor smaller than the plain Table 310.16 result: 150 A calls for 1 AWG copper. 1/0 AWG is the 175 A entry, and 2/0 AWG is the 200 A entry.

      Reference: NFPA 70, National Electrical Code, 2023 edition, 310.12(A) and Table 310.12(A)

    4. Using Chapter 9 Table 1 (40 percent fill), Table 4 and Table 5, what is the maximum number of 10 AWG THHN conductors permitted in 3/4-in. EMT?

      Answer: 10

      The 40 percent fill area of 3/4 in. EMT is 0.213 sq in., and a 10 AWG THHN conductor is 0.0211 sq in. 0.213 / 0.0211 = 10.09, which rounds down to 10 conductors. 16 is the count for 12 AWG THHN.

      Reference: NFPA 70, National Electrical Code, 2023 edition, Chapter 9, Tables 1, 4 and 5

    5. A single household electric range is rated 14 kW. Using Table 220.55, Column C and Note 1, what demand load is used for the range in a dwelling calculation?

      Answer: 8.8 kW

      Column C gives 8 kW for one range of 12 kW or less. Note 1 adds 5 percent per kW over 12 kW: 2 kW over adds 10 percent, so 8 kW x 1.10 = 8.8 kW. 8.0 kW ignores the note, and 9.6 kW applies 20 percent.

      Reference: NFPA 70, National Electrical Code, 2023 edition, Table 220.55 and Note 1

    6. A 480Y/277-volt panelboard has exposed live parts on its front, and a switchboard with exposed live parts faces it directly across the aisle (Condition 3). Using Table 110.26(A)(1), what is the minimum depth of working space?

      Answer: 4 ft

      A 480Y/277-volt system is 277 volts to ground, the 151-600 V row of Table 110.26(A)(1). Exposed live parts on both sides of the working space is Condition 3, which requires 4 ft. 3 ft is Condition 1, 3-1/2 ft is Condition 2 (grounded parts opposite), and 5 ft is Condition 3 for 601-1000 V.

      Reference: NFPA 70, National Electrical Code, 2023 edition, Table 110.26(A)(1)

    7. Under 110.16(A), which of these pieces of equipment must be marked with an arc-flash hazard warning if it is likely to be serviced while energized?

      Answer: A 400-A switchboard in a commercial building

      110.16(A) applies to switchboards, switchgear, enclosed panelboards, industrial control panels, meter socket enclosures and motor control centers in other than dwelling units that are likely to be examined or serviced while energized.

      Reference: NFPA 70, National Electrical Code, 2023 edition, 110.16(A)

    8. Where must the individual disconnecting means for a motor controller be located under 430.102(A)?

      Answer: In sight from the motor controller location

      430.102(A) requires an individual disconnecting means for each motor controller, located in sight from the controller location (with only the listed exceptions).

      Reference: NFPA 70, National Electrical Code, 2023 edition, 430.102(A)

    9. A permanently installed pool is installed at a dwelling. What is the maximum height above grade or the pool deck for the required general-purpose receptacle?

      Answer: 6 ft 6 in.

      680.22(A)(1) requires at least one 125-volt, 15- or 20-ampere receptacle between 6 ft and 20 ft from the inside wall of the pool, and not more than 6 ft 6 in. above the floor, platform or grade serving the pool.

      Reference: NFPA 70, National Electrical Code, 2023 edition, 680.22(A)(1)

    10. Under 410.6, what must be true of luminaires, lampholders and retrofit kits?

      Answer: All of them must be listed

      410.6 states that all luminaires, lampholders and retrofit kits shall be listed.

      Reference: NFPA 70, National Electrical Code, 2023 edition, 410.6

    Sources

    Questions last verified November 17, 2026. Licensing rules change. Always confirm current requirements with the licensing agency before you apply.